PILE CAPACITIES FOR BIFACIAL MODULE -JAGANNATH GROWERS

PILE CAPACITIES - MEYERHOF'S FORMULAE

Maximum compressive or axial load from the above table 1=4 kN


=
Maximum Uplift load or tension load from the above table 15
= kN
=
Maximum lateral load 2= kN
=
N values from the soil report
minimum N value 42

PILE TYPE : BORED CAST -IN-SITU


VERTICAL AND UPLIFT CAPACITY AS PER CLAUSE B-4.2 OF IS 2911
Vertical Capacity
Ultimate Vertical Capacity Qu = 10N(L/B) Ap+NAs/0.60 (End Bearing + Skin Friction)
D (Diameter of pile) = 0.3 m
Average SPT N along the shaft = 42
L (Length below ground) = 1.5 m
As (Surface area of Pile shaft) = 1.414 m2
Ap (Cross Sectional Area) = 0.071 m2
FOS (Factor Of Safety) = 2.5
Qu = 247.4 kN
Allowable Vertical Capacity Qa = 99.0 kN

Uplift Capacity
Ultimate Uplift Capacity Qu = NAs/0.60
Qu = 99.0 kN
FOS (Factor Of Safety) = 3 (Considering no Load Tests)
Self weight of pile = 1.6 kN
Allowable Uplift Capacity Qa = 34.6 kN

Lateral Capacity (Brom's approach)


3
Ultimate Lateral Capacity Hu = 0.5 x γ’ x D x L x KP / (e + L)
Kp (Passive earth pressure) = (1 + sinφ) / (1 - sinφ)
e (eccentricity) = 0.25 m
3
kN/m ( assumed since data is
γ’ 17.0
= not available)
φ (friction angle) = 33.0 0
FOS (Factor Of Safety) = 2.5
Kp = 3.4
Hu = 16.7 kN
Allowable Lateral Capacity = 6.7 kN

Design requirement (kN)


* Above pile length is based of the soil report .If
Structure Axial Uplift Lateral
any mismatch to the actual site condition and soil
report this document is not applicable Required 14.000 15.00 2.0
Geotechnical Capacity (kN)
.*if location having hard rock with top soil then Computed 98.960 34.58 6.67
pile length will be with minimum socketing length
of 3 times of dia i.e L=top soil depth+ 3 x dia of Design summary
pile Design safe Safe Safe Safe