CHECK LIST INVERTER SIROCCO FAN

Model Unit : Inverter Model :


Serial Number : Serial Number :
No. Comp. : Tanggal checking :

Inspection Inspection Good


Subject Of Inspection Inspection Methods
Item results Conditions
R-S
Use Multitester or
Voltage (V)
S-T 400 V ± 10%
other
R-T
R
Use Multitester or
Input Power Current (I) S 8 A ± 15%
other
T
R
Use Multitester or
Frequency (Hz) S 50 Hz ± 5%
other
T
Power
U-V
Use Multitester or
Voltage (V) V-W 400 V ± 10%
other
U-W
U
Use Multitester or
Output Power Current (I) V 8 A ± 15%
other
W
U
Use Multitester or
Frequency (Hz) V 50 Hz ± 5%
other
W
U - Ground
Insulation Test V - Ground ≥ 20 Mꭥ Use Insulation Tester
Motor Fan W - Ground
Vibration Of Load Side Tidak Noise Touch/Hearing on
Bearing Unload Side Tidak Noise cover bearing)
Temperature Ruangan < 450C Use Thermometer
Kondisi
Lingkungan Temperature Inverter < 50 C
0
Use Thermometer
Debu, Ceceran Oli, Dll. Bersih Eye Check
Command Mode Selection Cnod 0
Freq. Setting Mode Selection 1 Fnod 1
Maximun Frequency (Hz) FH 65
Upper Limit Frequency (Hz) UL 65
Parameter Lower Limit Frequency (Hz) LL 5
On Monitor Inverter
Setting Inverter Output Terminal Selection F132 10
VIA Input Point 1 Freq. (Hz) F202 5
VIA Input Point 2 Sett. (%) F203 50
VIA Input Point 2 Freq. (Hz) F204 65
PWM Carrier Freq. (kHz) F300 4