1. Product selection
Kanontec's KAC host series products are divided into four series, KAC001, KAC002, KAC005 and KAC008, each series supports Daikin/Toshiba/Mitsubishi Electric/Hitachi
Direct connection to the internal bus (HBS) of the four central air-conditioning systems. Details are as
Logic control
server function
1xHBS
- HBS air conditioner direct connection port (U1/U2)
1xAPP
- KNX/EIB interface -
KAC008-(DK/TB/MSE/HT) 1xKNX
Logic control - Various
1xRS485
protocols based on RS485 - Various
1xRS232
protocols based on RS232 - Logic
control
Home Bus System (HBS) is a concept jointly proposed by Japanese companies: Hitachi, Mitsubishi, Panasonic, Toshiba, etc.
Developed by the HBS Standards Committee of the Wire Engineering Electronics Society. Today's air-conditioning brands basically use the HBS bus protocol as the standard for data exchange within the air-conditioning system.
The VRV/VRF air conditioner bus brands and descriptions supported by KAC series products are as follows:
Air conditioner brand Air conditioner bus name Terminals Air Conditioning Bus Polarity (Positive and Negative) Supported Number of Indoor Units
By using KAC series gateway products, the smart home system or building automation system can directly manage and control Toshiba central air conditioners in a centralized manner;
Applicable to all Toshiba central air conditioner series, please consult our sales or pre-sales technical support for specific model details.
KAC generally connects U1 and U2 to U1 and U2 of the outdoor unit of the air conditioner, regardless of positive or negative. If inconvenient, it can also be connected to U1 and U2 on a certain indoor unit
Connect the wiring according to the schematic diagram in Section 3.2. Connect U1 and U2 on the KAC to U1 and U2 on the outdoor unit or indoor unit.
to the steps shown in Section 3.3 for the setting of the air conditioner address.
Note: After the KAC is powered on, there will be a self-test process and a query process. The phenomenon is that the red and green lights flash synchronously every 3 seconds.
4. Use the integration point table or APP to complete the system docking. (see Chapter 4)
The default parameters are Slave ID: 1, Baudrate: 9600, 8, 1, N. The integration example is as follows:
Indoor unit function Air conditioning value Air conditioning control point Air Conditioner Status Point
Mode Choice 0=COOL, 1=HEAT, 2=Fan, 3=DRY, 4=Auto 0x03/0x06 40003+(n-1)*10 0x04 30003+(n-1)*10
n=1~16 Fan Speed 0=Auto, 1=L, 2=M, 3=H 0x03/0x06 40005+(n-1)*10 0x04 30005+(n-1)*10
Prohibit setting 0=No, 1=switch, 2=mode, 3=switch/mode 0x03/0x06 40007+(n-1)*10 0x04 30007+(n-1)*10
Error code - - -
0x04 30009+(n-1)*10
Mode Choice 0=COOL, 1=HEAT, 2=Fan, 3=DRY, 4=Auto 0x03/0x06 40259+(n-17)*10 0x04 30259+(n-17)*10
Prohibit setting 0=No, 1=switch, 2=mode, 3=switch/mode 0x03/0x06 40263+(n-17)*10 0x04 30263+(n-17)*10
Error code - - -
0x04 30265+(n-17)*10
Indoor unit function Air conditioning value Air conditioning control point Air Conditioner Status Point
Mode Choice 0=COOL, 1=HEAT, 2=Fan, 3=DRY, 4=Auto EIS6 14/0/2+(n-1)*10 EIS6 15/0/2+(n-1)*10
n=1~16 Fan Speed 0=Auto, 1=L, 2=M, 3=H EIS6 14/0/4+(n-1)*10 EIS6 15/0/4+(n-1)*10
Prohibit setting 0=No, 1=switch, 2=mode, 3=switch/mode 0x03/0x06 14/0/6+(n-1)*10 0x04 15/0/6+(n-1)*10
Error code - - -
0x04 15/0/8+(n-1)*10
Mode Choice 0=COOL, 1=HEAT, 2=Fan, 3=DRY, 4=Auto EIS6 14/1/2+(n-17)*10 EIS6 15/1/2+(n-17)*10
Prohibit setting 0=No, 1=switch, 2=mode, 3=switch/mode 0x03/0x06 14/1/6+(n-17)*10 0x04 15/1/6+(n-17)*10
Error code - - -
0x04 15/1/8+(n-17)*10