Professional Documents
Culture Documents
Proposed Battery
Cell Mfr: Hawker Cell Type: KH..P Nominal Capacity: 200 Ah
Environment
Aging Factor: 1 Design Margin: 1 Requirements Margin: 0.98
State of Charge Factor: 1
Nominal Temperature: 20 °C Used Plate Format: 1 Number of Strings: 1
(Lowest 20 °C, Highest 20 °C)
Voltages
Maximum System Voltage: 30.74 V Minimum System Voltage: 17 V Average System Voltage: 17 V Maximum Voltage Drop: 0 V
Charging Voltage per Cell: 1.54 V End Voltage per Cell: 0.85 V Used Curve: 0.85 V Float Correction: applied
Duty Cycle
Period Load in kA Duration Minutes
1.68 0.00:00:01 0.02
Total Duration Duty Cycle 0.00:00:01 0.02
Random Section 0.00:00:00 0
Load in [kA] Duty Cycle
-2
-4
-6
-8
-10 Minutes
0 0 0 0 0 0 0
Battery Data
Total Number of Blocks (Number of Blocks X Number of Strings) 20
Block Dimensions (L X W X H) in mm 164 X 158 X 360
Number of Packing Units (1150 mm X 750 mm each) 1
Total / Block Weight in kg 312.6 / 15.63
Total / Block Electrolyte Weight in kg 96 / 4.8
Short Circuit Current in A 4000
Additional Information
Standard used IEC / EN 60623
Container material Translucent plastic