PROJECT IN AIR-
CONDITIONING AND
VENTILATION
(HVAC LOAD CALCULATION)

Bicaldo, Michael Jan O.


-BSME 4D

Engr. Joeffrey D. Bustinera


-Instructor

November, 2023
Republic of the Philippines
CAMARINES SUR POLYTECHNIC COLLEGES
Nabua, Camarines Sur
COLLEGE OF ENGINEERING AND ARCHITECTURE
Republic of the Philippines
CAMARINES SUR POLYTECHNIC COLLEGES
Nabua, Camarines Sur
COLLEGE OF ENGINEERING AND ARCHITECTURE

Windows Data:

Door Data:

Windo Width Height Area Widt Height


Door Area (ft^2)
w (ft) (ft) (ft^2) h (ft) (ft)
W1 4 3 12 D1 8 3 16
W2 2.5 2 5 D2 7 2.5 17.5
W3 4 3 12 D3 8 3 16
W4 5 4 20 D4 8 3 16

Rooms Data:

Width Length Area


Room
(ft) (ft) (ft^2)
Bedroom 1 6.23 7.85 48.9
Bedroom 2 8 14 112
Bath Room 4 4.50 18

Data (For Room 1, 48.9 ft2)

D3 …………………………………………... 16

W3 …………………………………………. 12

Ceiling Height ……………………………………... 12 ft.

U-Wall ………………………………………………. 0.48 𝐵𝑡𝑢/𝑓𝑡2−ℎ𝑟−°F

U-Floor ………………………………………………. 0. 𝐵𝑡𝑢/𝑓𝑡2−ℎ𝑟−°F

U-Partition …………………………………………… 0.645 𝐵𝑡𝑢/𝑓𝑡2−ℎ𝑟−°F

U-Glass ………………………………………………. 0.94 𝐵𝑡𝑢/𝑓𝑡2−ℎ𝑟−°F

U-Ceiling ……………………………………………... 0.058 𝐵𝑡𝑢/𝑓𝑡2−ℎ𝑟−°F

Design Conditions:

Outside Temperature …………………………………. 96.8 °F


Republic of the Philippines
CAMARINES SUR POLYTECHNIC COLLEGES
Nabua, Camarines Sur
COLLEGE OF ENGINEERING AND ARCHITECTURE

Inside Design Temperature …………………………… 75 °F

Daily Range …………………………………………... 19.8 °F (see table 1.1)

Table 1.1

DAILY RANGE TEMPRATURE (2022)

MANILA, Philippines Weather History (2022)

Month Maximum (°F) Date and Time Minimum (°F) Time


January 89.6 (27 Jan, 14:00) 68 (18 Jan, 02:00)
February 91.4 (24 Feb, 14:00) 71.6 (5 Feb, 08:00)
March 95 (31 Mar, 14:00) 73.1 (1 Mar, 05:00)
April 95 (28 Apr, 14:00) 71.6 (3 Apr, 02:00)
May 96.8 (8 May, 14:00) 77 (6 May, 14:00)
June 95 (10 Jun, 14:00) 75.2 (23 Jun, 02:00)
July 93.2 (3 Jul, 14:00) 75.2 (6 Jul, 02:00)
August 93.2 (26 Aug, 14:00) 75.2 (4 Aug, 23:00)
September 93.2 (6 Sep, 14:00) 75.2 (26 Sep, 03:00)
October 96.8 (10 Oct, 14:00) 75.2 (26 Oct, 05:00)
November 93.2 (14 Nov, 14:00) 73.4 (28 Nov, 02:00)
December 91.4 (3 Dec, 14:00) 73.4 (28 Dec, 02:00 )

Daily Range = 96.8 °F – 77 °F = 19.8 °F


Republic of the Philippines
CAMARINES SUR POLYTECHNIC COLLEGES
Nabua, Camarines Sur
COLLEGE OF ENGINEERING AND ARCHITECTURE

ROOM 1
A. Solar Gain – Glass

➢ To find the Area of the glass, A ( 𝒇𝒕𝟐)

Southeast---------------------- 12 ft2
Southwest--------------------- 20 ft2

➢ To find the Heat Transfer Coefficient, U (𝑩𝒕𝒖 / 𝒇𝒕𝟐−𝒉𝒓−°𝐅)

Btu
U = 0.94 2
ft −hr−℉
➢ To find the Temperature Difference (°F)

(ASHRAE GRP 158; Table 3.18, page 3.31) (see table 1.3)
ΔT of W1 at Southeast: 14 °F
ΔT of W4 at Southwest: 57 °F

➢ To find the Solar Heat Gain- Glass (Q)

𝑄glass = 𝐴glass 𝑥 𝑈glass 𝑥 𝛥T

Btu
For SE: 12 x 0.94 2
x 14 ℉
ft −hr−℉
Btu
Q = 157.92
hr
Btu
For SW: 20 x 0.94 2
x 57 ℉
ft −hr −℉
Btu
Q = 1071.6
hr
B. SOLAR AND TRANSMISSION GAIN (Walls and Roof)

➢ To find the Area of the Wall, A ( 𝒇𝒕𝟐)


Southeast ---------------7.57𝑓𝑡 𝑥 12 𝑓𝑡 = 90.84𝑓𝑡2 (Area of SE wall) –12𝑓𝑡2 (𝐴𝑟𝑒𝑎 𝑜𝑓 𝑤𝑎𝑙𝑙 𝑊1)
= 78.84 𝑓𝑡2
Southwest---------------14𝑓𝑡 𝑥 12 𝑓𝑡 = 168 𝑓𝑡2 (Area of SE wall) – 20 𝑓𝑡2 (Area of wall W4)
= 148 𝑓𝑡2
Republic of the Philippines
CAMARINES SUR POLYTECHNIC COLLEGES
Nabua, Camarines Sur
COLLEGE OF ENGINEERING AND ARCHITECTURE

Interpolation of the Concrete Hollow blocks (CHB)

X Y

4 0.71

6 0.91

8 1.11
Republic of the Philippines
CAMARINES SUR POLYTECHNIC COLLEGES
Nabua, Camarines Sur
COLLEGE OF ENGINEERING AND ARCHITECTURE

SI MATERIAL RESISTANCE

1 Outside air @ 7.5 mph 0.25

2 Cement 5/8” plaster 0.39

3 CHB (6”) 0.91

4 5/8” plaster 0.39

5 Inside air (still air) 0.68

TOTAL RESISTANCE 2.62

Uwall = 1/RT = 1/2.62


Uwall = 0.38 BTU/HR-𝐹𝑇2 − °F

➢ To find Solar Heat gain of Walls:

𝑄wall = 𝐴wall 𝑥 𝑈wall 𝑥 𝛥T

2 Btu
Qw ( SE)=78.84 ft x 0.38 2
x 30 ℉=898.776
f t −hr−℉
2 Btu
Qw ( S w )=148 ft x 0.38 2
x 24.5 ℉=1377.88
f t −hr−℉

C. Roof Ceiling:

𝑄roof = 𝐴roof 𝑥 𝑈roof 𝑥 𝛥T


Area of roof = 105.98 ft2
Republic of the Philippines
CAMARINES SUR POLYTECHNIC COLLEGES
Nabua, Camarines Sur
COLLEGE OF ENGINEERING AND ARCHITECTURE

➢ To find U of Roof/Ceiling

SI MATERIAL RESISTANCE

1 Outside air (@7.5 mph wind) 0.25

2 GI sheet roofing (corrugated) 0.00

3 No insulation 0.00

4 Still air 0.92

5 Plywood 0.31

6 Inside air 0.91

TOTAL RESISTANCE 2.4


Republic of the Philippines
CAMARINES SUR POLYTECHNIC COLLEGES
Nabua, Camarines Sur
COLLEGE OF ENGINEERING AND ARCHITECTURE

∑ R=2.4
1 1
U roof = = =u=0.4167
∑R 24

➢ To find ΔTR: for roof:

(Load estimate: table 20, page 1-63)

ΔT of Roof = 28 + 10°F (correction to equivalent temperature) = 38 °F

𝑄roof = 105.98 𝑓𝑡2 𝑥 0.4167 𝑥 38℉ = 1678.15 𝐵𝑡𝑢 / ℎ

Transmission gain:

D. All glass, 𝑄 = 𝐴glass 𝑥 𝑈glass 𝑥 𝛥𝑇

= 29.7895 𝑥 0.94 𝑥 21.8 = 610.446434 𝐵𝑡𝑢/ℎ

Total area of partition = (7.57 x 12) + (14 x 12) = 258.84

E. Partition, 𝑄 = 𝐴p 𝑥 𝑈p 𝑥 𝛥T

➢ To find Area of partition: Total area of P – Area of Doors

258.84 – 16 ft2 (Area of Door 1) = 242.84 ft2

To find U partition: (ASHRAE table 3.1A)


Republic of the Philippines
CAMARINES SUR POLYTECHNIC COLLEGES
Nabua, Camarines Sur
COLLEGE OF ENGINEERING AND ARCHITECTURE

SI MATERIAL RESISTANCE

1 Outside air @ 7.5 mph 0.25

2 Cement 5/8” plaster 0.39

3 CHB (6”) 0.91

4 5/8” plaster 0.39

5 Inside air (still air) 0.68

TOTAL RESISTANCE 2.62

U = 1/∑ 𝑅 = 1 / 2.23 = 0.4484

➢ To find 𝜟𝑻p

21.8 – 5 = 16.8 °F

➢ To find Qpartition

𝑄 = 𝐴p 𝑥 𝑈p 𝑥 𝛥T
Republic of the Philippines
CAMARINES SUR POLYTECHNIC COLLEGES
Nabua, Camarines Sur
COLLEGE OF ENGINEERING AND ARCHITECTURE

= 242.84 x 0.4484 x 16.8 ℉

Btu
¿ 1829.34
hr

F. Ceiling: 𝑄𝑐𝑒𝑖𝑙𝑖𝑛𝑔 = 𝐴 𝑥 𝑈 𝑥 𝛥𝑇

Btu
= 105.98 ft x 0.4167 x 38 = 1678.1509
hr

G. Floor: 𝑄𝑓𝑙𝑜𝑜𝑟 = 𝐴f 𝑥 𝑈f 𝑥 𝛥𝑇

(Ashrae, Table 3.1A, Thermal properties of typical building & insulating materials)

Btu
= 105.98 x 0.05 x 16.8 = 65.1
hr

Total solar and Transmission gain,

Qst =Qsolar + Qtransmission

Qst = 3317.64 + 2798.9111 𝐵𝑡𝑢/ℎ𝑟

Internal Heat

A. People (Sensible Heat)

(ASHRAE, Table 48- Heat Gain from people)

Qs =Sens. H.G x No. of persons

Qs = 230 𝐵𝑡𝑢 ℎ𝑟 x 2 persons = 460 𝐵𝑡𝑢/ hr.

(Latent Heat)

Qs = Lat. H.G x No. of persons

Qs = 120 𝐵𝑡𝑢 ℎ𝑟 x 2 persons = 240 𝐵𝑡𝑢/ hr.

B. Lighting
Republic of the Philippines
CAMARINES SUR POLYTECHNIC COLLEGES
Nabua, Camarines Sur
COLLEGE OF ENGINEERING AND ARCHITECTURE

Qlighting = A x input x 3.41

1 watt
Q lighting=105.98 x 2
x 3.4 1 = 361.3918 Btu
ft hr

C. Equipments

Qequipments = Total watts of items/equipment x 3.41

EQUIPMENTS Wattage
Laptop 70 watts
Incandescent Lamp 30 watts
Cellphone 3 watts
TOTAL: 103 watts

Qequipments = 103 Watts x 3.41 = 351.23 𝐵𝑡𝑢 / ℎr.

Total Internal Heat:

Qinternal = 460 + 240 + 264.275 + 351.23 𝐵𝑡𝑢 / ℎ𝑟.

Qinternal = 1315.505 𝐵𝑡𝑢 / hr.

Qst + Qinternal =6116.5511+1315.505 =7432.0561 𝐵𝑡𝑢 / ℎ𝑟

➢ Add factor of .15: =7432.0561 x 0.15 = 1114.8084

7432.0561 + 1114.8084 =8546.8645 𝐵𝑡𝑢 / ℎ𝑟

Ventilation & Infiltration CFM = CFM/Person x No. of persons

(ASHRAE, Table 6.1, Minimum Ventilation rates in Breathing zone)

CFM = 5 x 2 =10

CFM =CFM/𝑓𝑡2 x Area of room

CFM = 0.06 x 105.98 = 6.35

CFM = 10 + 6.35 = 16.35


Republic of the Philippines
CAMARINES SUR POLYTECHNIC COLLEGES
Nabua, Camarines Sur
COLLEGE OF ENGINEERING AND ARCHITECTURE

Outside Air (By passed air)

Q = 1.08 x 0.12 x CFM x (OAT – RAT)

Q= 1.08 x 0.12 x 14.65 x 21.8 °F

Q = 41.390352 𝐵𝑡𝑢/hr.

Outside Air (Sensible Heat Gain)

Qs =1.08 x CFM x (OAT – RAT) x 0.88

Qs = 1.08 x 14.65 x 21.8 x 0.88

Qs =303.529248 𝐵𝑡𝑢/hr.

Outside Air (Latent Heat Gain)

QL = 0.68 x CFM x 𝐺𝑟/𝑙𝑏 x 0.88

QL = 0.68 x 14.65 x 70 x 0.88

QL = 613.6592 𝐵𝑡𝑢/hr.

Total Ventilation and Infiltration

Qvi =958.578792 𝐵𝑡𝑢/ hr.

Grand Sub-Total Heat, 𝐵𝑡𝑢 ℎ𝑟

Q= Qst + Qinternal + Qventilation

Q= 8950.19 + 958.578792 𝐵𝑡𝑢/ hr.

Qsubtotal = 9908.769 𝐵𝑡𝑢/ hr.

Safety Factor (5%)

SF = 9908.769 x 0.05

SF = 495.44

Grand Total Heat Gain


Republic of the Philippines
CAMARINES SUR POLYTECHNIC COLLEGES
Nabua, Camarines Sur
COLLEGE OF ENGINEERING AND ARCHITECTURE

Qt = SF + Qsubtotal

Qt =495.44 + 9908.769 𝐵𝑡𝑢/ hr.

Qt =10,404.209 𝐵𝑡𝑢/ hr.

Tonnage, TR

Tonnage = Grand Total heat gain / 12000

Tonnage = 10,404.209/ 12000

Tonnage = 0.86