1 2 3 4 5 6

NOTES : CLIENT :

1. ALL DIMENSIONS SHOWN HERE ARE


IN MILLIMETERS. ALL LEVELS ARE IN
METERS.
(DO NOT SCALE FROM THE DRAWING).

2. TO BE COORDINATED WITH ARC AND


MEP TRADES.
CPPA
3. STRUCTURAL CONCRETE :
- GRADE A substructure
Compressive Strength on Cylinder (28 Days) : PROJECT MANAGEMENT CONSULTANT:
40 MPa
Triple blend cement Moderately sulphate
resisting cement Type II conforming to ASTM
Protection Board C150 or cement Type CEM I 42.5N conforming
A to BS EN 197-1, with C3A content ranging from A
5% to 8% in combination with silica fume (5% to
HDPE Waterproofing Membrane 10% of cementitious weight) and fly ash (25% to
RAFT (As per Project's Specifications) 35% of cementitious weight)
Fillet 40x40
- GRADE B superstructure
SLAB ON GRADE Fillet 40x40 Compressive Strength on cylinder (28 Days) :
WELL COMPACTED FILL 40 MPa
Joint Blinding Ordinary Portland cement Type I conforming to DESIGNED BY:
PERIPHERAL WALL ASTM C150 or cement Type CEM 42.5N
conforming to BS EN 197-1 shall be used with
Silica fume (5% to 10% of cementitious weight)
RAFT and fly ash (25% to 35% of cementitious weight)

HDPE WATERPROOFING Cement SAND/SCREED - GRADE C- Slab-on-Grade : Internal slabs


(or as per manufacturer's on grade.
MEMBRANE Compressive Strength on cylinder (28 Days) :
Engineered Fill recommendations)
25 MPa
(TYP.) Ordinary Portland cement Type I conforming to
ASTM C150 or cement Type CEM 42.5N
conforming to BS EN 197-1 CSC
WATERSTOP - GRADE D- Blinding and plain concrete
Compressive Strength on Cylinder on cylinder
(28 Days) : 15 MPa.
Sulphate resisting cement Type V conforming to
WELL COMPACTED FILL W03 ASTM C150 or cement Type CEM I 42.5N/SR3
conforming to BS EN 197-1 with C3A lower
SLAB ON GRAGE than 3%.
BLINDING 4. REINFORCEMENT STEEL :
Joint YIELD STRENGTH OF STEEL SHALL BE CONSTRUCTION SUPERVISION CONSULTANT
ENGINEERED FILL MINIMUM
420 MPa (60000 Psi) ACCORDING TO ASTM MAIN CONTRACTOR :
STANDARD A615 , SBC 304, and ACI 318
HDPE WATERPROOFING
MEMBRANE 5. CONCRETE COVER :
- RAFT : 75 mm
B - COLUMN : 40 mm B
- BEAM : 40 mm
- WALL : 30 mm
- SLAB : 30 mm

6. FOUNDATION DESIGN IS AS
GEOTECHNICAL
ENGINEERED FILL REPORT SAFCO FOR Z1-Z3-SHARMA
DISTRICT-DESIG CONSULTANCY SERVICES SUBCONTRACTOR :
RAFT PROJECT– NEOM, SHARMA, TABUK
EXISTING SOIL
AREA-K.S.A, DATED 13 OCTOBER, 2022.

BLINDING

LEGEND : REFERENCE DRAWING :


1. Z1Z3-MACC-SV-CON-SHD-ST-SSC-020005
2. Z1Z3-MACC-SV-CON-SHD-ST-SSC-020010
DECORATIVE COLUMN 3. Z1Z3-MACC-SV-CON-SHD-ST-SSC-020101
4. Z1Z3-MACC-SV-CON-SHD-ST-SSC-020102
5. Z1Z3-MACC-SV-CON-SHD-ST-SSC-020103
C.. : COLUMN 6. Z1Z3-MACC-SV-CON-SHD-ST-SSC-020104
DC.. : DECORATIVE COLUMN 7. Z1Z3-MACC-SV-CON-SHD-ST-SSC-020105
W.. : WALL 8. Z1Z3-MACC-SV-CON-SHD-ST-SSC-020106
PW.. : PERIPHERAL WALL 9. Z1Z3-MACC-SV-CON-SHD-ST-SSC-020107
CJ : CONSTRUCTION JOINT
T.O.R : TOP OF RAFT
SV S.S.L
N.G.L
: STRUCTURAL SLAB LEVEL
: NATURAL GROUND LEVEL FOR FD DRAWING REFER TO :
L 1. S20066-0604D-FD-SC-SV-00-101-1
2. S20066-0604D-FD-SC-SV-00-102-1
WELL COMPACTED FILL C45 3. S20066-0604D-FD-SC-SV-00-103-0
C 4. S20066-0604D-FD-SC-SV-00-104-0 C
COLUMN SLAB ON GRAGE DC12 WELL COMPACTED FILL 5. S20066-0604D-FD-SC-SV-00-105-1
6. S20066-0604D-FD-SC-SV-00-201-0
7. S20066-0604D-FD-SC-SV-00-202-0
SLAB ON GRADE Joint SLAB ON GRAGE 8. S20066-0604D-FD-SC-SV-00-301-1
9. S20066-0604D-FD-SC-SV-00-302-1
Joint Joint Joint 10. S20066-0604D-FD-SC-SV-00-303-0

HDPE WATERPROOFING
MEMBRANE PERIPHERAL WALL

HDPE WATERPROOFING
MEMBRANE
WELL COMPACTED FILL

HDPE WATERPROOFING ENGINEERED FILL


MEMBRANE
RAFT WATERSTOP
BLINDING ENGINEERED FILL
RAFT RAFT

BLINDING
ENGINEERED FILL
BLINDING

00 FIRST ISSUE 15-Jun-2023

REV. DESCRIPTION DATE


NO.

As Built
D D

5022 00 020 SV 011 0_00


PROJECT CODE PHASE TRADE BUILDING DOC. NUMBER REVISION

CIVIL/LS ARCHITECT STRUCTURAL

- - -

SV ELECTRICAL MECHANICAL ICT


N
WELL COMPACTED FILL - - -

DRAWN BY CHECKED BY APPROVED BY


SLAB ON GRAGE
J.P. J.K. J.K.
Joint
WELL COMPACTED FILL
SITE KEY PLAN : PROJECT TITLE :
PERIPHERAL WALL HDPE WATERPROOFING
Z3 - PROJECT

R 16M
CORRIDO
MEMBRANE

UTILITIES
CJ BLINDING TABUK-KSA
HDPE WATERPROOFING RAFT
MEMBRANE
BUILDING NUMBER & NAME :
ENGINEERED FILL
SV
SON'S VILLA
ENGINEERED FILL WATERSTOP
RAFT BUILDING KEY PLAN : DRAWING TITLE :
SELF EXPANDING N

N
E
N
WATER STOP

E
SW

SE
S

E BLINDING FOUNDATIONS E
FORMWORK
MECH. SHAFT

SECTIONS
PLUMBING SHAFT

SCALE - SHEET SIZE DATE CAD FILE

1/25 A0 15-Jun-2023 Z3-MACC-SV-CON-ABL-ST-SSC-020011-00

DAR DOCUMENT NUMBER :

Z3 MACC SV CON ABL ST SSC 020011 00


PROJECT ORGANIZATION BUILDING STAGE DWG.TYPE DISCIPLINE SUB-DISC. SHEET NUMBER REVISION