01

EngineeringTools

MiCOM S30
Central Protection and Control Unit

MiCOM S30 is the up-to-date and cost-effective


Schneider Electric solution for substation control
and monitoring.
Besides local and remote monitoring and operation
MiCOM S30 provides communication, time
synchronization and access to intelligent protection and
control devices (IEDs). Factory built, pre-engineered
templates and an exhaustive support of a wide range
of MiCOM protection and control devices ensure
a quick and a reliable engineering and reduced
commissioning time.

Application
MiCOM S30, the central protection and control unit, enables acquisition
and logging of information and measured values, the automatic archiving of
disturbance fault records and status indication for a maximum of 127 IEDs
linked with the standardized serial communication interface according to IEC
60870-5-103.

For combined protection and control devices and bay units for control
and monitoring additional switchgear operation and status indications are
provided.

Overview, device and bay screens are generated by the integrated


configuration tool. Optionally a log archive is available. Additionally MiCOM
S30 is responsible for the time synchronization of the IEDs connected.
Customer benefits
The disturbance fault data and daily logs can be downloaded locally or
• User-friendly
• High efficient configuration remotely (via a modem link) from MiCOM S30 by the operating program
• Easy to install MiCOM S1 and can be viewed menu controlled. The full range of features
• Integration into enterprise networks of the operating program is also provided by the direct access mode for
via Web server the IEDs linked.
• Optimized management
The integrated Web server enables remote download (via Intranet or
• Open communication
modem) of disturbance fault data and daily logs from MiCOM S30 as well
• Highly reliable
as the operation of switchgear devices by a Web browser .
02
EngineeringTools MiCOM S30

Using Schneider Electric latest Web-based • Display of status, information and measured
technology e-terra control, MiCOM S30 can be values
integrated in a network-based distributed system • Switchgear position indications and switching
via an IEC 60870-5-101 / 104 communication link. commands
e-terra control’s full graphics user interface • Overview screens for all IEDs connected
simplifies the interaction with MiCOM S30 and • Protection screens for status and information of
provides consistency across all Schneider Electric each protection device connected
applications. • Substation overview for switchgear position
indications
Design • Bay screens for control and monitoring
MiCOM S30 central protection and control unit switchgear devices, according to the predefined
is built on a basic 19” rack system (6 U, 84 E) or a bay types
wall-mounted unit with up to four communication • Local interface for the operating program
interfaces to the IEDs via star couplers or RS 485 MiCOM S1
interface modules. • Features of the operating program MiCOM S1
The basic unit comprises a central processing unit ◦◦ Download of the daily logs
with a graphic and an Ethernet controller, a 12.1” ◦◦ Generation of an actual daily log (up-to-date
TFT color display, an alphanumeric keyboard, a daily log)
hard disk, a floppy drive and a CD-ROM drive as ◦◦ Download of fault disturbance data
well as a communication module. ◦◦ Direct access to each IED connected
A modem (19”, 2 U, 84 E) and a Web server are • List of sequence of events (SOE)
integrated as well. • Error list
• Log archive (one log per day)
Standard features • Automatic transfer of the fault disturbance data
MiCOM S30 is equipped with a multiplicity of from IEDs to hard disk
efficient standard functionalities. • Storage of fault disturbance data in
• Model 1: at maximum 64 IEDs or Schneider Electric format. COMTRADE file
Model 2: at maximum 127 IEDs format is available via MiCOM S1.
• Integrated configuration tool including the • Reset of the alarms at the local control panel
automatic generation of the screens for the IEDs
03
EngineeringTools MiCOM S30

• Complete range of functions available upon The screens are created menu-assisted by the
direct access to the IED (setting, operation, user with the integrated configuration tool and
measured values, status information, operating the process data to be displayed can be selected
recordings, event recordings) according to the application. Subsequently
• Time synchronization of the IEDs by the devices may be added by the configuration tool.
internal clock
The configuration tool provides a database of all
• Integrated self-monitoring
devices available for MiCOM S30.
• Up- and download of the configuration data via
FTP access These are a variety of Schneider Electric
• Provided via modem or internet protection devices, Schneider Electric combined
◦◦ Remote download of the daily logs protection and control devices, Schneider Electric
◦◦ Generation of an actual daily log bay units for control and monitoring as well as
◦◦ Remote download of fault disturbance data the standard protection devices as defined in IEC
• Nominal auxiliary supply voltage 115 / 230 V AC 60870-5-103.
The database provides predefined templates and
Options bay screens for each of these IEDs, whereas the
MiCOM S30 is extended by a variety of efficient bay screens correspond to the bay types of the
functions. control devices. The database can be updated by
• Time synchronization of the IEDs by reloading.
◦◦ GPS Navigating through MiCOM S30 via the local
◦◦ DCF77 control panel, with each screen selected (overview
◦◦ SCADA interface (IEC 60870-5-101/104) display, device of bay screen) a virtual keyboard
◦◦ NTP (Net Time Protocol) is shown at the bottom of the screen. The
• SCADA communication for information, functions available at the screen are assigned
• measured values and control to the function keys F1 ... F10. Thus apart from
• e-terra control as full graphic user interface stepping through the screens, the selection of
• Nominal auxiliary supply voltage: an IED or resetting of an alarm, commands for
60 V DC, 110 V DC, 220 V DC protection and/or control devices (e.g. automatic
reclosing enable/disable) or control commands
Functions
for switchgear devices like circuit-breakers or
Status and information from the IEDs and for the disconnectors can be given.
entire system are displayed on the integrated
Information from the IEDs are stored in a ring buffer
local display.
and displayed on the relevant screens.
The navigation through the screens is via 10 These information events are filed as a daily log at
function keys (F1 … F10) of the integrated midnight on MiCOM S30’s hard disk. The ring buffer
membrane keyboard. can be viewed in the list of events on the local display.
04
EngineeringTools MiCOM S30

Disturbance fault data or long-term recordings being An actual daily log can be triggered from here.
recorded by the IEDs are transferred to the hard disk
After the file transfer to the PC running the browser
as well. For the analysis of the fault data the external
the data may be analyzed (e.g. by the fault record
viewer of the operating program MiCOM S1 can be
viewer, a text viewer, a spreadsheet program or the
used.
operationg program MiCOM S1)
Via the local serial interface the disturbance fault
The link to control centers (e.g. SCADA) is provided
data are transferred from MiCOM S30 hard disk to a
by two optional serial communication interfaces
PC running the operating program MiCOM S1.
according to the international standard for Telecontrol
Furthermore IEDs selected for direct access can
IEC 60870-5-101 as well as a communication
be set from a central access point by the operating
interface according to IEC 60870-5-104. Information
program.
from the IEDs and the commands from the control
Using a modem link a PC running the operating center are based on templates. A application specific
program communicates with MiCOM S30 via the setting is supported by the configuration tool.
telephone network and the same functions are
For the integration into a network-based distributed
available remotely as locally provided.
system MiCOM S30 can be linked via a
The PC with the operating program MiCOM S1 IEC 60870-5-101 communication line to e-terracontrol.
provides the function “Write daily log in a file
(updating)” via the local interface or remotely (via e-terracontrol provides the following key features:
modem). The daily logs generated on request and • Offering Web server functions
the daily logs generated automatically at midnight
• Full graphics local HMI
can be transferred via the local interface or remotely
(via modem) to the PC and viewed by an editor. For • Sequence of events
the analysis in a spreadsheet program, the daily logs • Event and alarm logging
are available in an appropriate file format. • Historian data functions with trending
The Web server of MiCOM S30 can be integrated • Printing facilities
into to a LAN or WAN using the Ethernet interface or For the time synchronization of the IEDs the internal
may be addressed via the optional modem using a clock of MiCOM S30 is used. Optionally time
Dial-up connection. synchronization is available with an integrated GPS /
Accessing via TCP/IP protocol, the ‘homepage’ of DCF77 time signal receiver or the Net Time Protocol
MiCOM S30 (HTML Web site) can be started by (NTP).
a Web browser. Users with access privileges will LEDs at the front side of MiCOM S30 indicate the
not require custom software to access data - the status of power supply and the hard disk access.
Microsoft® Internet Explorer will suffice. Additionally at the 19” rack unit the status of
Disturbance fault data as well as the archived daily logs temperature and of the keyboard are indicated.
stored in MiCOM S30 can be accessed via that page.
05
EngineeringTools MiCOM S30

Additional LEDs display the operating status like • Nominal consumption where VA = 220 V DC max.
system warning and system fault, the direct access 230 W (basic unit)
and local operation of the PC to an IED, the modem
access as well as the status of the internal power • Storage energy time at nominal load:
supply. 60 V DC, 110 V DC, 220
The fault and warning signal are signaled via two V DC, 230 V AC: 20 ms,
output relays. Internal voltage failure and fan failure 115 V AC: 17 ms
are permanently assigned to the fault and warning
relay. Additional signals can be assigned to the fault • Classification according to IEC 60870-2-1:
and warning signal by the configuration tool. Nominal voltages DC: 60 / 110 / 220 V DC
DC voltage tolerances: DC3 (-20 % to +15 %)
Moreover, detailed signals are displayed in the list of
events and corresponding screens. Ripple: VR3 (≤ 5 %)
DC grounding conditions: E+, E-, EC
MiCOM S30 can by widely accommodated to almost
any substation configuration while using different • Nominal voltages AC: 115 / 230 V AC
models: System frequency range: 50 Hz, 60 Hz
Voltage tolerances: AC2 (-10 % to +10 %)
• Model 1: 2 communication interfaces
System frequency tolerances: F3 (± 2 %)
• Model 2: 4 communication interfaces Total harmonic distortion: H2 (< 10 %)
Up to 32 IEDs can be operated at each interfaces
either by a RS 485 bus or by optical fibers. Interfaces
The optical fiber link is via star-couplers (type CK Displays
102/112/122) and the power-supply module
(CZ 912). • Status and operation displays: LEDs on front
panel (only 19’’ rack) and on PC plug-in boards
Different types star couplers allow the mixture of
plastic and glass optical fibers. • Display (only 19’’ rack)
12.1” TFT color
Technical data 800 x 600 pixels
Design
Local interface
• Basic unit: 19” rack (6U) / wall mounted unit
• DIN 41652 connector, type D-Sub, 9-pin
• Modem as ad-on unit: 19” rack (2U)
Communication interfaces
• Installation position: horizontal
• Protocol according IEC 60870-5-103
Degree of protection
• M2 threaded terminal ends for wire cross sections
• Per EN 60529 or IEC 60529 Front panel: IP 54 to 1.5 mm2
Case sides and terminals: IP 20
Ethernet interface
Weight
• Protocol according IEC 60870-5-104
• 19” Basic unit (dependent on configuration):
up to 24 kg • HTTP, FTP protocol
wall mounted unit: 10 kg • Plug RJ-45, 10/100 Mbit
Add-on unit: up to 2 kg
Telecontrol interface
Creepage distances and clearances
• Protocol according IEC 60870-5-101
• Per IEC 60664-1
• Pollution degree : 3 • DIN 41652 connector, type D-Sub, 9-pin, isolated
working voltage: 250V DC
overvoltage category : III
Aerial interface

Power supply • BNC

• Per IEC 60664-1 Power supply


• Nominal auxiliary voltage VA,nom: • AC / DC auxiliary voltage:
60 V DC, -20 %...+15 % Inlet connector for non-heating apparatus with
110 V DC, -20 %...+15 % pre-assembled cable (3 m)
220 V DC, -20 % to +15 %
115 / 230 V AC, -10 % to +10 % • DC auxiliary voltage by external power inverter
06
EngineeringTools MiCOM S30

Interface for external keyboard • Insulation voltage test:


IEC 60870-2-1,
• 5-pin per DIN 41524 2,5 kV

Mass storage • Vibration test:


IEC 60255-21-1,
• hard disk drive (≥10 GB) Class 1
• 3.5” floppy disk drive • Shock response and withstand test:
• CD-ROM disk drive IEC 60255-21-2,
Class 1
Tests • Seismic test:
• 1 MHz burst disturbance test: IEC 60255-21-3,
IEC 61000-4-12, Class III Class 1

• Immunity to electrostatic discharge: Environmental conditions


IEC 61000-4-3,
Level 3 • Operating temperature:
-5°C to +55°C
• Electrical fast transient or burst requirements: (23°F to +131°F)
IEC 61000-4-4,
Level 4 • Storage temperature:
-25°C to +55°C
• Surge immunity test: (-13°F to +131°F)
IEC 61000-4-5,
Class 4 • Transport temperature:
-25°C to +70°C
• Power frequency magnetic field immunity: (-13°F to +158°F)
IEC 61000-4-8,
Level 5 • Ambient humidity range:
≤ 75 %
relative humidity (annual mean), condensation not
permitted

MiCOM S30: The up-to-date solution for substation control and monitoring

Easy to configure, remote access and operation via Web server,

Standardized communication interfaces


07
EngineeringTools MiCOM S30

Ordering information
Variants Order No.
MiCOM S30 S30-
19" base unit, 6 H, with integrated HMI and modem rack (2 H) 1 0
19" base unit, 6 H, without HMI, with modem rack (2 H) 2 0
Base unit, wall mounted, without HMI, with modem rack (2 H) 3 0
Standard Components
For up to 64 protection- and/or control devices
1)
with IEC 60870-5-103 protocol via integrated RS485 interfaces
Integrated Web Server for remote access/control via modem or
2)
Ethernet interface; FTP server
Integrated harddisk, CD-ROM disk drive, floppy disk drive
Modem rack 2H mit analog modem (standard),
3)
With local interface and power supply switch
Standard 19'' base unit
4 binary inputs
Base unit, wall mounted
2 binary inputs
Additional devices (IEC 60870-5-103) to be connected
Without 0
1)
maximal 127 devices 1 1
2 1
Telecontrol
without 0 0
4)
per IEC 60870-5-104 0 1
4) 5)
per IEC 60870-5-101 1 0
4) 5) 4)
per IEC 60870-5-101 and per IEC 60870-5-104 1 1
4) 5)
2 x per IEC 60870-5-101 2 0
4) 5) 4)
2 x per IEC 60870-5-101 and per IEC 60870-5-104 2 1
Others x x
Link to HMI or SCADA
e-terra control *)
Modems
Analog modem (standard) 1
ISDN modem 2
GSM modem 3 *)
GRPS modem 4 *)
Leased line 5 *)
Time synchronization
Internal computer clock 1
DCF ( 5 m antenna cable) 1 2
2 2
GPS with outdoor antenna, lightning protection and cable 1 3
2 3
NTP (via Ethernet and TCP/IP) 4
9)
per IEC 60870-5-101 5
per IEC 60870-5-104 9) 6
Nominal auxiliary voltage VA,nom :
115 / 230 V~ 50/60 Hz 0
24 V– 1 *)
6)
60 V– 2
6)
110 V– 3
6)
220 V– 4
Additional options
Engineering of telecontrol *)
Version according project specification and order num ber / A ... Z 7) -501
Language
English
German -801
Russian -805
Accessories
Optical fibers *)
Indoor antenna DCF77 (> 5 m antenna cable) *)
Outdoor antenna with lightning protection (DCF77) *)
Manual (printed version) order in plaintext
Engineering of an user-specific bay type 8) *)
1) Coupling modules, star couplers, optical fibers will need to be ordered separately (for details please see ‘Accessories’).
For star couplers CK 102, CK 112 and CK 122, mixed-coupler connection is possible.
2) For the integration into a LAN. the necessary parameters have to be specified to the supplier with the order.
3) Modem with AC-supply. For other versions of power supply separate accessories are available.
4) With defined volume of project data. Physical interface: RS232 / V.24
5) Via an IEC 60870-5-101 telecontrol line eterra control (operator terminal) can be connected.
6) For DC an inverter for separate assembling is delivered as 19” mounting rack 3 U, 370 mm depth
7) Single devices within an order are numbered consecutively with A ... Z.
8) According specification
9) Only available together with telecontrol interfaces
*) On request
EngineeringTools MiCOM S30 08

IEDs supported by MiCOM S30


• MiCOM devices
C232
C434
P122C
P130C
P139, P439, P432
P430C
P433, P435, P437
P543
P631, P632, P633, P634
• Devices with a communication interface
according IEC 60870-5-103 compatibility level 2
• Third party products with communication
interface according IEC 60870-5-103, like
voltage regulator, regulator for Petersen coil

© 2010 Schneider Electric - All rights reserved

Schneider Electric
35, rue Joseph Monier As standards, specifications and designs change from time to time, please ask for confirmation
CS 30323 of the information given in this publication.
92506 Rueil-Malmaison Cedex, France
Tel: +33 (0) 1 41 29 70 00 This document has been printed
on ecological paper
RCS Nanterre 954 503 439
Capital social 896 313 776 € Publishing: Schneider Electric
www.schneider-electric.com Design: Schneider Electric
Printing:

EnergyAutomation-DS-S30-0547-EN 10-2010