Sd = 164.00 MPa
St = 175.71 MPa
Design Thickness :
td = 4.9 x D x ( H - 0.3 ) x G / ( Sd x E ) + CA
td = 4.9 x 6 x ( 9.564 - 0.3 ) x 0.978 / ( 164 x 0.85) + 3
td = 4.91 mm
Test Thickness :
Head incl.
Course Height of Head incl.
Internal td incl. higher of t
from course in Internal pressure tt Material
pressure in CA td & tt provided
Bottom mm in m
mm
1 1500 9563.9 9.56 4.91 1.82 4.91 10.00 IS 2062 Gr B
2 1500 8063.9 8.06 4.60 1.53 4.60 10.00 IS 2062 Gr B
3 1500 6563.9 6.56 4.29 1.23 4.29 8.00 IS 2062 Gr B
4 1500 5063.9 5.06 3.98 0.94 3.98 8.00 IS 2062 Gr B
5 1500 3563.9 3.56 3.67 0.64 3.67 8.00 IS 2062 Gr B
6 500 2063.9 2.06 3.36 0.35 3.36 8.00 IS 2062 Gr B
7 0 1563.9 1.56 3.26 0.25 3.26 0.00
8 0 1563.9 1.56 3.26 0.25 3.26 0.00
9 0 1563.9 1.56 3.26 0.25 3.26 0.00
10 0 1563.9 1.56 3.26 0.25 3.26 0.00
11 0 1563.9 1.56 3.26 0.25 3.26 0.00
12 1563.9 1.56 3.26 0.25 3.26
8000
Provide Curb Angle 80 x 80 x 8 thk --- ALL AROUND THE TANK (Cl. No. 5.1.5.9 e API 650)
Weight/mtr 9.4848 Kg
Select the Code IS 875 : Part III
Design Wind Pressure ( Pz ) = 0.6 x Vz^ 2/9.81 ( As per 5.4 IS 875 : Part 3 )
0.6 x 60.73^2 / 9.81
225.54 kg/m^2
Modulus of elasticity at room temp = Er 199000 MPa ( Cl. M.6 Appendix M API 650
Modulus of elasticity at design temp = Ed 199000 MPa )
Uncorroded condition
H1 = 9.47 t x ( t / D)^1.5 x (190 / V )^2 ( Cl. 5.9.7.1 & M.6 API 650)
9.47 x 8 x (8 / 6 )^1.5 x ( 190 / 394.75 )^2
27.02 m
Corroded condition
H1 = 9.47 t x ( t / D)^1.5 x (190 / V )^2 ( Cl. 5.9.7.1 & M.6 API 650)
9.47 x 5 x (5 / 6 )^1.5 x ( 190 / 394.75 )^2
8.34 m
Calculation of transposed width of the shell ( Cl. 5.9.7.2 API - 650 )
Provide Wind Girdet at 4.000 m from curb angle Transposed width = 4.0000 m
Provide Wind Girdet at 0.00 m from curb angle Transposed width = 0.00 m
Provide Wind Girdet at 0.00 m from curb angle Transposed width = 0.00 m
Provide Wind Girdet at 0.00 m from curb angle Transposed width = 0.00 m
Weight calculation for Tank Shell
Minimum Thickness of the roof plate = 5.0(3/16 inch)+1.5mm ( Cl. 5.10.2.2 API 650 )
6.50 mm
80 x 80 x 8 m m
35
= 82. th = 6.5 mm (corroded)
Wh
theta = 15 deg.
m
m
8 R2 = 11591.11 mm
.4
3
7
=
c
W
tc = 5 mm (corroded)
Rc = 3000 mm
Min Shell Thickness for Shell for external load : (Cl. V.8.1.3- API 650)
N= 5.888
N= 6
Required moment of inertia ( I req ) = 37.5 Q D^3 / E ( N^2 - 1 ) ( V.8.2.2.5 API 650 )
= 23.14 cm^4
65 1 0 thk
145.26
6 thk
4.5 thk shell ( cor ) 2 0
It. Mkd. x , cm y , cm
1 0 0
2 6.5 0.6
3 0.45 14.53
Section M=Axd
Size cm x cm Area cm^2 d in cm Iaa cm^4 Igg cm^4
marked cm^3
1 0x0 0.00 0.00 0.00 0.00 0.00
2 0.6 x 6.5 3.90 3.25 12.68 41.19 13.73
3 14.53 x 0.45 6.54 6.73 43.96 295.62 0.11
10.44 56.63 336.81 13.84
Weight
Web size 65 mm x 6 mm thk 58.41 kg
Toe size 0 mm x 0 mm thk 0.00 kg
Total for each 58.41 kg
q x m^2
Wind load on various surfaces q (psf) q (kg/m^2) m Multi.
(kg/m^2)
W ind load on projected area of cylindrical surfaces 18 psf 87.88 kg/m^2 1.000 87.88
Wind load on projected area of conical surfaces 30 psf 146.47 kg/m^2 1.000 146.47
Wind force on the shell = 6.5 x 87.88 x 8 ( 0.5 m extra for ladder )
4569.95 kg
Wind Moment about the base Mw = Wind of shell + Wind on roof ( upward )
( 4569.95 x 8 / 2 ) + 4141.42 x ( 6 / 2 )
30704.09 kg-m
0.6 Mw + Mpi > MDL / 1.5 & Mw + 0.4 Mpi > ( MDL + MF ) / 2
Tank is Unstable against wind. Provide anchor bolts.( Cl. 5.11.2 API 650 )
Hence Safe
Hence Safe
Test Condition
+ve Value of Net Uplift indicates that Anchor Bolts are required.
Hence Safe
Hence Safe
Seismic Analysis ( Appendix E API 650 Addendum 3 Sept 2003 )
Overturning Moment due to Seismic applied to the Bottom of Shell shall be determined by
Seismic Zone Factor ( Z ) = as per spec 0.16 ( Table E-2 API 650 )
Importance Factor ( I ) = As per Spec 2 ( E.3.1 Appendix E API 650 )
Lateral earthquake force coefficient ( C1 ) = 0.6 ( E.3.1 Appendix E API 650 )
Constants
D= 6.00 m H= 9.564 m
D/H= 0.63
( k ) Factor obtained for the ratio D / H = 0.58 ( Figure E-4 API 650 )
Natural period of the first sloshing mode ( T ) = 1.81 k ( D )^0.5 ( E.3.3.2 API 650 )
= 2.571
Moment at Base
M= Zl [ C1 Ws Xs + C1 Wr Ht + C1 W1 X1 + C2 W2 X2 ]
C1 Ws Xs = 231094.60 19534.03
C1 Wr Ht = 130938.66 5237.55
C1 W1 X1 = 5633470.18 428387.3254
C2 W2 X2 = 2084227.78 87170.29
Total = 8079731.22 540329.19 N
Weight of tank shell and portion of the fixed roof supported by shell ( Wt )
Now,
Formula 1
Maximum Allowable Compressive Stress ( Fa ) = 83 t / 2.5 D + 7.5 ( G H )^0.5 ( E.5.3 API 650 )
= 83 x 7 / 2.5 x 6 + 7.5 ( 0.978 x 8 )^0.5
= 59.71 MPa
Hence O.K.
Minimum Anchorage
Hence Safe
Hence Safe
Uplift due to Seismic & Internal Pressure ( As per API 650 Table 3-21 a)
Hence Safe
Hence Safe
AS PER AISI T-192 VOL II PART VII- ANCHOR BOLT CHAIR
* marked are based on DRG REF STANDARD DRAWING STD.TK.GEN.7314
B
Q = 40 mm = 1.575 inches
a* = 175 mm = 6.890 inches j
b* = 150 mm = 5.906 inches
c* = 32 mm = 1.260 inches a g 175
Hole dia.d* = 52 mm = 2.047 inches
e* = 70 mm = 2.756 inches
pcd* = 6180 mm = 243.307 inches f
radius,R = 3003 mm = 118.228 inches
e min = 60.601 mm = 2.386 inches b
f=B-d/2 = 44 mm = 1.732 inches
f min = 29.175 mm = 1.149 inches radius
B* = 70 mm = 2.756 inches c
g* = 110 mm = 4.331 inches k
A* = 268 mm = 10.551 inches t
j* = 16 mm = 0.630 inches A
k = 95 mm = 3.740 inches e
m = 10 mm = 0.394 inches m w
t = 20 mm = 0.787 inches Shell thk + Pad thk Q
w = 10 mm = 0.394 inches pcd
P= design load in N =
36898.80 N= 3761.35 KG ( wind + Test Pressure ) appx
32684.19 N= 3331.72 KG ( wind + Operating pressure ) appx
106416.62 N= 10847.77 KG ( Seismic condition+ Intr pressure ) appx
10847.77 KG ( Maximum of above load ) appx
Minimum cross sectional area of bolt = 375.83 mm^2 ( Corroded )
Yield strength of bolt = 482.80 N/mm^2
Max. Load (P) =1.5 x Bolt load = 159624.9 N 35.873 kips
VERTICAL PLATE :
Min thk = 16.00 mm
0.04 ( h - c) = 0.37 in
= 9.44 mm
j k => P / 25
j k = 2.3560
P / 25 = 1.4349
As per the standard practice, we design bleeder vent for 1.15 times its pump in / out rate capacity
Add 15% extra to cater for tank drainage in case of pump out condition….Hence
REQUIRED AIR CAPACITY FOR THERMAL EFFECT,Q2 = 50.60 m³/ hr Ref:-Table 2-B OF API2000
CAPACITY DUE TO CO2 FILTER SYSTEM, Q5 = 0.00 m³/ hr
TOTAL REQUIRED AIR BREATHING CAPACITY, Q in = Q1+Q2+Q5
= 72.22 m³/ hr
B) OUT BREATHING (PRESSURE RELIEF)
4. SPECIALS :
1 Stress relieving of tank outside of foundation - REQURED for Cleanout door - 1 Nos
Required for Compression Girder
2 Painting & sand blasting TO SA 2 1/2 FINISH
External surface System 7 of spec
= Shell 150.8 m^2
= Stairway+P. Form = 9.6 m^2
=' Cone roof plate 29.7 m^2
= Nozzle , appx = 8.0 m^2
= Floating Roof plates 0.0 m^2
=Hand Rail 0.46 per m run 8.7 m^2
=Wind girder 0.00 47.88 47.9 m^2
bottom 29.7 m^2
TOTAL => 284.3 m^2
16.0 mtr long
4 CIVIL REQUIREMENT Not by tank vendor as per note 6 of data sheet rev B1
5 FIRE FIGHTING REQD, TO BE CONSIDERED SEPERATLY ( Foam and Cooling water system )
6 CATHODIC PROTECTION IF TO BE CONSIDERED SEPERATLY
7 PLEASE CONSIDER NOZZLE PIPE ( EXTRA STRONG) AND FLANGES AS PER SPECIFICATION
8 INSTRUMENTS AND CONTROLS SHALL BE TO p & I AND DATA SHEET EXTRA
( Level Instruments, temp instruments, vent etc..)