D := 10m f := 5m h := 30m d := 100km Vn := 500kV − 12 F

ε := 8.85⋅ 10 ⋅
m
bundle
−7H
µ 0 := 4 ⋅ π ⋅ 10
n := 3 e := 40cm m
d ext
Cabo Grosbeak dext := 2.516cm rext := rext = 0.01258 m
2
3
Dmg := D⋅ ( 2 ⋅ D) ⋅ D Dmg = 12.599 m

Capacitância MVA := 1000kW


−6
µS := 10 ⋅S MW := MVA
3
2 MVAr := MVA
req := e ⋅ rext req = 12.626 cm

oC := K
2⋅ π ⋅ ε nF
C := C = 12.08
ln
Dmg  km
exp −
1
req   = 0.7788
   4

Total 100 km
µS
ω := 2⋅ π ⋅ 60Hz Y := C⋅ ω Y = 4.554
km
2
Yt := Y⋅ d Yt = 455.417 µS B := Yt⋅ Vn B = 113.854 MVAr

Indutância
3
e ⋅ rext⋅ exp − 
2 1
reqz := reqz = 11.617 cm

4 
µ0 Ω
⋅ ln
Dmg  mH
L :=  L = 0.937 X := L⋅ ω X = 0.3533
2⋅ π  reqz  km km

Resistência a 75oC obtida da tabela de fabricante


Ω −1 Ω
Rac75 := 0.1075 α := 0.00403oC Rac20 := Rac75⋅  1 + α ⋅ ( 20⋅ oC − 75⋅ oC)  Rac20 = 0.0837
km km
Ω Ω
Rcc20 := 0.0896 Rcc75 := Rcc20⋅  1 + α ⋅ ( 75⋅ oC − 20⋅ oC)  Rcc75 = 0.1095
km km
Para 3 condutores por fase

Rac75 Ω
R := R = 0.0358
n km

Exercício 3

item a)
D := 10m e := 40cm
3
Dmg := D⋅ ( 2 ⋅ D) ⋅ D Dmg = 12.599 m

X = 0.353
km
Ω µ0
⋅ ln
X Dmg  Dmg
X := 0.3984 L := L=  reqz := reqz = 6.391 cm
km ω 2⋅ π  reqz   L⋅ 2 ⋅ π 
exp 
 µ0 
2
reqz
reqz = e⋅ rext⋅ exp − 
1
rext := rext = 1.311 cm dext := 2 ⋅ rext dext = 2.622 cm
 4 e⋅ exp −
1

 4 rmg := rext⋅ exp − 
1
rmg = 0.01021 m
 4 
Consultando a tabela o cabo com rmg 0.1021 m é o Grosbeak

item b)

Capacitância

req := e⋅ rext req = 7.242 cm

2⋅ π ⋅ ε nF
C := C = 10.779
ln
Dmg  km

 req 

Item c)

Total 100 km

d := 100km

Ct := C ⋅ d Ct = 1.078 µF

Total 300 km
d := 300km

Ct := C ⋅ d Ct = 3.234 µF
Item d) Impedância capacitiva

ω := 2⋅ π ⋅ 60Hz d := 100km

Xrt := j ⋅ X⋅ d Xrt = 39.84i Ω

1 3
Yt = j ⋅ ω⋅ C⋅ d Xct := Xct = −2.461i × 10 Ω
j ⋅ ω⋅ C ⋅ d

ω := 2⋅ π ⋅ 60Hz d := 100km

Xrt := j ⋅ X⋅ d Xrt = 39.84i Ω

1 3
Yt = j ⋅ ω⋅ C⋅ d Xct := Xct = −2.461i × 10 Ω
j ⋅ ω⋅ C ⋅ d