Professional Documents
Culture Documents
PRS - Theory Differential Protection Complete - ENU
PRS - Theory Differential Protection Complete - ENU
> Introduction
> Differential protection principle
> Field of application
> Principles of transformer differential protection
> Connection example transformer differential relays
> Tripping characteristic
> Inrush detection (2nd harmonic/CWA)
> Overexcitation detection (3rd/5th harmonic)
> Zero sequence elimination
> Disadvantages and limits of transformer differential protection
> Protection testing principle
© OMICRON Page 4
Agenda
> Introduction
> Differential protection principle
> Field of application
> Principles of transformer differential protection
> Connection example transformer differential relays
> Tripping characteristic
> Inrush detection (2nd harmonic/CWA)
> Overexcitation detection (3rd/5th harmonic)
> Zero sequence elimination
> Disadvantages and limits of transformer differential protection
> Protection testing principle
© OMICRON Page 5
Introduction
Why is overcurrent or
distance protection not
sufficient to protect
Which types of fault transformers?
can occur at
transformers?
What does a
transformer
Why do we have to differential protection
protect against relay do?
transformer fault
currents?
© OMICRON Page 6
Why do we have to protect against transformer fault
currents?
© OMICRON Page 7
Which types of fault can occur at transformers?
Types of fault
© OMICRON Page 8
Types of electrical fault (examples)
1 2 3
© OMICRON Page 9
Types of non-electrical faults (example)
Buchholz relay Contact thermometer
a b
a
5
Gas warning contact
b Trip contact
Temperature high
a (Warning contact)
Temperature highest
b
(Trip contact)
© OMICRON Page 10
Why is overcurrent or distance protection not
sufficient to protect transformers?
Example of time grading with overcurrent protection I> stage:
t
1.2 s
800 ms
!
! 400 ms
A B C
Overcurrent relay
© OMICRON Page 11
Why is overcurrent or distance protection not
sufficient to protect transformers?
Example of current grading with overcurrent protection I>> stage:
t
1.2 s (I>)
400 ms (I>>)
A
! B
Overcurrent relay
© OMICRON Page 12
Why is overcurrent or distance protection not
sufficient to protect transformers?
Theoretical consideration of distance protection with a transformer:
Vsc
Vsc = 0
Isc
The impedance
is no longer
proportional to
110 kV 20 kV the distance!
Zsc
Vsc
Zsc =
Isc
distance 100%
© OMICRON Page 13
What does a transformer differential protection relay
do?
criterion
operating faulty
condition condition
ΔI
Definition:
The differential protection relay operates, if the
differential current exceeds a predetermined value.
© OMICRON Page 14
Agenda
> Introduction
> Differential protection principle
> Field of application
> Principles of transformer differential protection
> Connection example transformer differential relays
> Tripping characteristic
> Inrush detection (2nd harmonic/CWA)
> Overexcitation detection (3rd/5th harmonic)
> Zero sequence elimination
> Disadvantages and limits of transformer differential protection
> Protection testing principle
© OMICRON Page 15
Differential protection principle (physical background)
The current differential principle is based on Kirchhoff’s Law, i.e. the sum of
the currents flowing into a conducting network is zero.
Iside 1 Iside 2
Protected
Object Iside 1 + Iside 2 = 0
1A 0° 1A 180°
in general: ∑I
i=1
side i =0
Protected
Object
n
Idiff = ∑I
i=1
side i
© OMICRON Page 16
Differential protection principle (fault direction)
87 87
Iside 1 + Iside 2 ≠ 0 Iside 1 + Iside 2 = 0
→ Trip → no Trip
© OMICRON Page 17
Differential protection principle (summary)
800 ms
0s
400 ms
A u B C
87
v
Overcurrent relay
© OMICRON Page 18
Agenda
> Introduction
> Differential protection principle
> Field of application
> Principles of transformer differential protection
> Connection example transformer differential relays
> Tripping characteristic
> Inrush detection (2nd harmonic/CWA)
> Overexcitation detection (3rd/5th harmonic)
> Zero sequence elimination
> Disadvantages and limits of transformer differential protection
> Protection testing principle
© OMICRON Page 19
Field of application of differential protection (overview)
Transformer
A B A Line B
87 87
Motor Generator
A A
M G
87 87
Busbar
87
© OMICRON Page 20
Field of application (protection concept for transformer)
A B
50/51
87
main protection
backup protection
© OMICRON Page 21
Agenda
> Introduction
> Differential protection principle
> Field of application
> Principles of transformer differential protection
> Connection example transformer differential relays
> Tripping characteristic
> Inrush detection (2nd harmonic/CWA)
> Overexcitation detection (3rd/5th harmonic)
> Zero sequence elimination
> Disadvantages and limits of transformer differential protection
> Protection testing principle
© OMICRON Page 22
Power transformer (transmission behavior)
Load current flowing through the transformer:
Yyn0-transformer
Sr = 160 MVA
231 kV / 118.5 kV
400/1 800/1
ΔI
IC
HV
LV
IB
IA HV
+ IA LV ∆I ≠ 0 !
IC
LV
HV
IB
© OMICRON Page 23
More in detail (calculation of the transformer parameters)
Calculation of the primary and the secondary rated current of
the transformer:
Sr 160 MVA
IHV,prim
= = = 399.9 A ≈ 400 A
3 ⋅ Vr 3 ⋅ 231 kV
Sr 160 MVA
ILV,prim
= = = 779.5 A ≈ 780 A
3 ⋅ Vr 3 ⋅ 118.5 kV
IHV,prim 400A
IHV,sec = = = 1A
IHV CT, prim
IHV CT, sec
( 400A
1A)
ILV,prim 780A
ILV,sec = = = 0.975A
ILV CT, prim
ILV CT, sec
(
800A
1A)
© OMICRON Page 24
Transformer differential protection (reference winding)
Differential current calculated to reference winding: HV side
Yyn0-transformer
Sr = 160 MVA
1 231 kV / 118.5 kV 2
© OMICRON Page 25
Agenda
> Introduction
> Differential protection principle
> Field of application
> Principles of transformer differential protection
> Connection example transformer differential relays
> Tripping characteristic
> Inrush detection (2nd harmonic/CWA)
> Overexcitation detection (3rd/5th harmonic)
> Zero sequence elimination
> Disadvantages and limits of transformer differential protection
> Protection testing principle
© OMICRON Page 26
Connection of a transformer differential relay
87
87
87
OR
Trip
signal
Differential relay
© OMICRON Page 27
Connection example of a transformer differential relay
(with phasor diagrams)
Im Im
IC HV IB LV
IA HV
Re IA LV Re
IB HV IC LV
v HV side u LV side v
A I u = power transformer
A HV IA LV
B
v = current transformers (ct)
IB HV IB LV
C I IC LV
C HV
Im Im
IC HV IB LV
IA HV
Re
IA LV Re
IB HV IC LV
© OMICRON Page 28
Agenda
> Introduction
> Differential protection principle
> Field of application
> Principles of transformer differential protection
> Connection example transformer differential relays
> Tripping characteristic
> Inrush detection (2nd harmonic/CWA)
> Overexcitation detection (3rd/5th harmonic)
> Zero sequence elimination
> Disadvantages and limits of transformer differential protection
> Protection testing principle
© OMICRON Page 29
Tripping characteristic in general (differential current)
calculation of the differential current
IF I Load I Load
87 87
© OMICRON Page 30
Tripping characteristic in general (bias current)
calculation of the bias current
IF I Load I Load
87 87
the bias current is the sum of currents flowing through the protected object
© OMICRON Page 31
Tripping characteristic in general
|x + y|
|y|
|x|
|x| + |y| ≥ |x + y|
1
→ Ibias ≥ Idiff
ideal characteristic external faults Ibias
or load currents
fault inside the protected object: 4 fault outside the protected object: 5
2
tap changer
Idiff >> 3
ct errors
4
x sum
curve 1+2+3
Tripping
w 5
Idiff >
z u
Ibias
{
© OMICRON Page 33
Tripping characteristic in general (bias current)
Manufacturer Method
Siemens, SEL I =
bias ( IP + IS ) / K1
AEG I
bias
= (IP - IS ) / K1
GE Multilin I
bias ( IP + IS ⋅ K 2) / K1
=
ABB I = I ⋅ I ⋅ cos (α )
bias P S
ZIV I =
bias ( IP + IS - IDiff ) / K1
© OMICRON Page 34
Agenda
> Introduction
> Differential protection principle
> Field of application
> Principles of transformer differential protection
> Connection example transformer differential relays
> Tripping characteristic
> Inrush detection (2nd harmonic/CWA)
> Overexcitation detection (3rd/5th harmonic)
> Zero sequence elimination
> Disadvantages and limits of transformer differential protection
> Protection testing principle
© OMICRON Page 35
Inrush (physical background)
The physical phenomenon of an inrush current occurs when a transformer
gets energized (CB close):
Iinrush
∆I ≠ 0
0A
!
A B
87
protected area
© OMICRON Page 36
Inrush (measured inrush current)
Example of a measured inrush current (three phase):
© OMICRON Page 37
Inrush detection (methods)
© OMICRON Page 38
Inrush restraint (2nd harmonic)
Frequency analysis of an inrush current:
© OMICRON Page 39
Inrush restraint (2nd harmonic/measurement logic)
Iinrush
Iinrush
Iinrush
2nd Harmon.
2nd Harmon.
2nd Harmon.
Trip signal
AND
u v
blocked
87
Differential relay
© OMICRON Page 40
Inrush restraint (2nd harmonic/measurement logic)
Idiff
inrush restraint
deactivated
Idiff>>
Idiff>
Ibias
© OMICRON Page 41
Inrush restraint (2nd harmonic/cross blocking)
Iinrush
Iinrush
Iinrush
2nd Harmon.
2nd Harmon.
2nd Harmon.
Trip signal
OR
blocked
87
Differential relay
© OMICRON Page 42
Inrush restraint (gap detection)
The occurrence of the significant gaps in the current waveform is typical for
inrush currents.
© OMICRON Page 43
Agenda
> Introduction
> Differential protection principle
> Field of application
> Principles of transformer differential protection
> Connection example transformer differential relays
> Tripping characteristic
> Inrush detection (2nd harmonic/CWA)
> Overexcitation detection (3rd/5th harmonic)
> Zero sequence elimination
> Disadvantages and limits of transformer differential protection
> Protection testing principle
© OMICRON Page 44
Overexcitation (physical background)
∆I ≠ 0
ILV
IHV
HV LV
!
A side side B
© OMICRON Page 45
Overexcitation (Frequency analysis of the current)
t [ms]
t [ms]
t [ms]
© OMICRON Page 46
Overexcitation (3rd/5th harmonic)
Frequence analysis of the current:
© OMICRON Page 47
Agenda
> Introduction
> Differential protection principle
> Field of application
> Principles of transformer differential protection
> Connection example transformer differential relays
> Tripping characteristic
> Inrush detection (2nd harmonic/CWA)
> Overexcitation detection (3rd/5th harmonic)
> Zero sequence elimination
> Disadvantages and limits of transformer differential protection
> Protection testing principle
© OMICRON Page 48
Zero sequence elimination (physical background)
external phase-to-ground fault:
A
?
HV side
∆I ≠ 0
LV side
IF
!B
IF
© OMICRON Page 49
Zero sequence elimination (physical background)
? HV side LV side IF
>>>
1
>>>
currents measured by phase CTs:
-2 -3
1
IHV = +1 I0 = (IA +IB +IC ) ILV = 0
3
+1 0
2 3 5 -2 -3 -5
Ibias = IHV + ILV = 1 + 0 =
1 Idiff = IHV +ILV = +1 + 0 = +1
unselective trip
u 1 0 1 +1 0 +1
© OMICRON Page 50
Zero sequence elimination (methods)
© OMICRON Page 51
Zero sequence elimination (mathematical solution)
? HV side LV side IF
>>>
1 2 3
>>>
currents measured by phase CTs:
1 -3
-2 I0 = (IA +IB +IC )
3
IHV = +1 ILV = 0
1
+1 I0 = ( -3+0+0 ) = −1 0
3
-2 0 -2 -3 -1 -2
′ = IHV -IHV 0
IHV = +1 - 0 = +1 ′ = ILV -ILV 0
ILV = 0 − -1 = +1
+1 0 +1 0 -1 +1
© OMICRON Page 52
Zero sequence elimination (numerical relays / measurement)
∆I = 0
HV LV
Y d5
A
B
C
u ILV
3I0
87
© OMICRON Page 53
Zero sequence elimination (star point CT)
© OMICRON Page 54
Zero sequence elimination (interposing transformer)
HV side LV side
A A
B B
C C
87
= transformer
YD Interposing Transformer
© OMICRON Page 55
Agenda
> Introduction
> Differential protection principle
> Field of application
> Principles of transformer differential protection
> Connection example transformer differential relays
> Tripping characteristic
> Inrush detection (2nd harmonic/CWA)
> Overexcitation detection (3rd/5th harmonic)
> Zero sequence elimination
> Disadvantages and limits of transformer differential protection
> Protection testing principle
© OMICRON Page 56
Disadvantages and limits of transformer differential
protection
no backup protection:
∆I = 0
IF IF IF
A B
87
© OMICRON Page 57
Agenda
> Introduction
> Differential protection principle
> Field of application
> Principles of transformer differential protection
> Connection example transformer differential relays
> Tripping characteristic
> Inrush detection (2nd harmonic/CWA)
> Overexcitation detection (3rd/5th harmonic)
> Zero sequence elimination
> Disadvantages and limits of transformer differential protection
> Protection testing principle
© OMICRON Page 58
Protective functions and test modules
© OMICRON Page 59
Front View of the CMC 356
© OMICRON Page 60
Wiring scheme of the CMC (Differential)
HV LV
A side side B
Standard:
outputs
binary „Trip“ signal HV side
1
inputs
2
I
Test currents I
HV side
Test currents
LV side
1
2
© OMICRON Page 61
© OMICRON Page 62