Filtration of Automatic Filter

Fuels and Lubricants Type 6.62/6.62.1


Highly-efficient self-cleaning without pressure loss

The fully automatic back-flushing filter The filter contains an inner housing ● Fully automatic self-cleaning opera-
6.62 is primarily used for the filtration with individual filter chambers to ac- tion
of fuels and lubricants. Incorporated commodate the filter candles. ● Operational safety from robust con-
into the lower section is a heating During the filtration process one cham- struction and precise automatic
chamber for connection of heat tracing. ber is always held in reserve, cleaned back-flushing system
This range of BOLL filters is unique in and pressurised, whilst the other filter ● Precisely defined filtration fineness
the method by which filtered-out resi- chamber is simultaneously providing via precision-made mesh
dues are completely removed from the the filtration function.
filter and thus from the liquid flow sys- ● Optimal cleaning of the filter mesh
tem. from compressed-air-assisted back-
Special features flushing
Highly efficient self-cleaning is
achieved with the assistance of filter- ● Efficient operation at line pressures ● Filter designed to meet the require-
as low as 1 bar ments of Maritime Classification So-
stored compressed air. Using this inde-
cieties (GL, LRS, NV, BV, ABS,
pendent medium as an energy source ● Low flushing losses, thus no higher
USSR-Reg., USCG etc.) for ships
for back-flushing ensures uninterrupted pump capacity necessary
operating with unmanned machin-
operation without pressure loss in the
● Compact, space-saving design ery spaces.
liquid flow system.

3 2
1
5 4

5/2

5/2

5 4
1
3 2

Heating chamber

Back-flushing position Filtration position


Precisely defined filtration of fuels and lubricants

Filtration The clean filter candle acting as a the liquid and flushed out of the filter
standby is automatically swung into through the sludge discharge valve.
The liquid to be cleaned enters the the operating position. Activation of
individual filter candle chambers the clean filter candle causes the After a brief post-blowing period the
through the top inlet flange and flows differential pressure to immediately sludge discharge valve and the air
through the filter candles from the fall. inlet valve are closed automatically.
outside inwards. At the same time, the empty cham-
Back-flushing then starts automati- ber is filled with a controlled volume
Back-flushing cally. The sludge discharge valve is of clean filtered liquid via a pilot bore
opened and the pressure in the and the chamber is automatically air
As the quantity of filtered-out solids chamber released. The compressed vented. The filter candle now cleaned
retained on the filter mesh increases, air stored in the air reservoir is then is ready to be put back into operation
this causes a rise in the pressure ‘explosively’ released via the inlet when required.
differential across the candles which, valve. The resulting reversed flow of
at a predetermined value, initiates clean liquid presses liquid on the
self-cleaning of the filter chamber. clean side of the candles at high
On activation of back-flushing, the velocity through the filter mesh of the
pneumatic actuator rotates the filter candles.
body and swings the filter candle to
The solids which have accumulated
be cleaned into the back-flushing
on the filter mesh are entrained by
position.

Electronic control
type 2100
The standard features of the back-
flushing filter include an electronic
control cabinet type 2100.
All important control and monitoring
functions are contained in the elec-
tronic control type 2100.

● Only three keys for operation


● 5-place,7-segment display
● Display of the back-flushing opera-
tion
● Indication of the number of back-
flushing operations
● Display of faults
● CPU board with non-volatile E-
Prom and program memory
● Input-/output board in the control
box
Technical Data Back-flushing Filters
with Bypass for ma-
rine Applications
Booster System (t max 150° C) According to the regulations of the
classification societies, fuel filters
Filter fineness Flow rate m3/h must be equipped with a changeover
micron Type 6.62 (size 40) Type 6.60 (size 50) mechanism and a bypass filter.

50 5.5 15

34 5.5 15

25 2.2 6

Supply System (t max 100° C)


Filter fineness Flow rate m3/h
micron Type 6.62 (size 40) Type 6.60 (size 50)

50 2.5 7.5

34 2.5 7.5

25 1.0 3.0

10 1.0 1.0

Back-flushing filter type 6.62.1 (DN 40)


Installation Diagram Supply System
We recommend the automatic filter
type 6.60 or 6.60.1 and 6.61 or
6.61.1 for higher flow rates
Diesel oil HFO
Day tank Day tank

Type 6.62
Duplex filter
Mixing tank

FM

Supply pumps Flow meter


Overflow tank
Back-flushing filter type 6.60.1 (DN 50)

VC Certified Quality to
Viscosity
DIN-ISO 9001
control unit Final pre-heater Booster pumps
This quality management system,
on which we place particularly strong
emphasis, guarantees QUAL
T ER I