Barmer to Salaya Pipeline Project

Project Numbering and Formatting System

COMMENT SHEET

CONTRACTOR/VENDOR NAME: PLL2

CONTRACT / P.O. NUMBER :

Doc Title : GA, RCC & Steel Details for Closed Drain Drum Pit
BSPL-1712-PLL2-CV-DWG-0009-01 Rev A1
Doc No : Revision : A1

Incoming Transmittal Number: PLL2-CEIL-T-0372 Date : 09.11 .09

Return Transmittal Number : CEIL- PLL2 –T-0149 Date : 17/11/09

COMMENT COORDINATOR : Ashok Mathur Review Issue Date : 17.11.2009

CLOSED OUT
SECTION, PARA & CLOSED OUT DATE BY
ITEM PAGE NO. / DWG. COMMENTS BY CEIL RESPONSE BY CEIL
LOCATION VENDORS /
CONTRACTOR

1) The size of the pit as shown on 1)Noted & not


Piping GAD No: BSPL-1712-PLL2- agreed. It is
PI-DWG-0006-01 does not match matching with
with the size on this drawing. the Piping GAD.
2) The overall length of the drum 2)As per Latest
including insulation=4400mm. This Piping GAD final
leaves only 800 mm between the length of the Pit
wall and the head of the tank. 800- is kept as
170=530 mm. It is considered 6500mm.
necessary to increase the length of
the pit to 7000 mm. 3)As discussed
3) The height of the roof shall be raised with CEIL Eave
BSPL-1712-PLL2-CV- height shall not
to provide 3.0 M clear at the eaves
DWG-0009-01 level of the rafter beam. To be increased.
minimize the entry of rain water let Only rafter with
the rafter extend beyond the column sheeting will be
lines by say 500 mm each side. Also extended by
extend the sheeting by 1.0 m beyond 500mm.
column line in direction of the length
of the pit by extending the purlins. 4) Noted &
4) Please provide rafter bracing in shed Incorporated.
roof Plan and check slenderness of
the columns about minor axis. 5)Already
5) Please provide design calculation for submitted.
our records.

Document / Drawing Comments Sheet


Page 1 of 2
Review does not constitute acceptance of design details, calculations, test methods or
materials developed or selected by Contractor / Vendors, nor does it relieve Contractor /
Vendors from full Compliance with contractual or other obligations.
1. No Comments Submit Final
2. Incorporate Comments & Submit Final
3. Not Acceptable Revise & Resubmit
4. No Comment Required.
5. Issued for Information Only

Name: Ashok Mathur


Signature:………………………………
.

Document / Drawing Comments Sheet


Page 2 of 2