TUBE WELL NUMBER - II BLOCK- RAMNAGAR-I J.L-123, UNDER DIGHA SUB DIVISION
OF TAMLUCK DIVISION
PURBO MEDENIPURE
WEST BENGAL.
WORK ASSIGNED BY
WORK EXECUTED BY
MAITY CONSTRUCTION
KANPUR, BALISAHI, RAMNAGAR
DISTRICT- PURBA MEDENIPURE,
PIN- 721423
BY
AQUA
(Action for Quality Underground Water Approach)
A bore hole has been drilled at Biswanathpur P.W.S.S Tube Well Number-II Block Ramnagar-I
under Digha Sub Division of Tamluck Division P.H.E Dte, Purbo Medenipure, West Bengal. up to
the depth of 230 m by direct rig rotary method
Diameter of the bore hole was 8 inches at the time of log.
Tube well has been electrically logged on 09.10.2023 up to the depth of 226 m adopting multi electrode
system of logging which enables determination of true resistivity of the formation encountered at time of
logging .
Spontaneous Potential (S.P) ; Long Normal (L.N) 1.6 m & Short Normal (S .N) 0.4 m resistivity data has
been plotted in mm graph sheet with depth . Four electrodes two for emitting current and two for potential
measurement constitute the system .
Recommendations are made on the basis of effective porosity , yield , quality of water , for construction of
production well . The tube well in question will be successful and yield good amount of water with good
quality , provided all steps of well construction are maintained .
Biswanathpur P.W.S.S Block Ramnagar-I under Digha Sub Division of Tamluck Division P.H.E Dte 2
170 to 190 High LN,SN&SP Sand saturated with water
SAND ZONES :-
As per electrical log parameters there are four clear sand zones have been identified as under.
70 to 80 m Zone A , 114 to 132 m Zone B, 140 to 153 m Zone C , 170 to 190 m Zone D
On the basis of electrical log parameters Zone A, B and C in between 114 to 129 m , 147 to 153 and
171 to 177 m are recommended for placement of strainer.
From the behavior of log characteristics as recorded in the bore hole and as per the drilled out samples, it
may be infer that the quality of water in the identified granular zones will be free from salinity.
TDS – Good.
RECOMMENDATIONS :-
1. Strainers are recommended for placement in Zone A, B and C in between between 114 to 129
m , 147 to 153 and 171 to 177 m
2. Expected Yield - Moderate .
3. Quality :- Free from salinity & TDS will be within acceptable limit.
(Debashis Dhar)
M.Sc.Tech Applied Geophysics,
Indian School of Mines, Dhanbad
Biswanathpur P.W.S.S Block Ramnagar-I under Digha Sub Division of Tamluck Division P.H.E Dte 3
40
Electrical Log at Biswanathpur P.W.S.S Tube Well Number-II Block Ramnagar-I under Digha Sub Division of
35 Tamluck Division P.H.E Dte
30 Date -09.10.2023
S.N L.N
25
Resistivity in ohm m
20
15
10
5
0
0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230
60
0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230
Depth from Ground level in M
S.P
50
Spontanious Potential in M.V