Vertical Circulation
3.1.1. Staircases
Within the average interval seconds, this population requires a very high car size.
Therefore, we provide zoning system for this building.
The lift system can be designed with two zones.
The first zone has been selected from ground 1st floor to 9th floor. The second zone has to be from 9th
to 15th floor.
For first 8 floors;
Assume lift speed as 2m/s.
For upper floors, the total population = 7 x 203 = 1421
The population handled in 5 mins as 12% = 1421 x 12% = 171
people Interval can be 34 seconds with capacity of lifts as 24.
The corresponding round trip time with 2m/s lifts = 122 seconds
Floor to floor height is 3.6 m.
Hence, No. of lifts = 122/34 = 3.6
Therefore, A total of 4 lifts can be
provided.
The inside size of the lift (From figure 5.3) = 2100 mm x 1650 mm
The shaft size required = 2550 x 2400 mm
The width of the lobby = 1.5 D = 1.5 x 1650 = 2475 mm