Professional Documents
Culture Documents
2. Press push button C Setup and hold it down for approx. 3 seconds.
➥ Display goes to main menu and indicates: ▶ Display...
Select parameter 3. Select parameter either:
→ click via the menu to parameter, or
→ via direct display: press and enter ID M0088.
➥ Display indicates: Trip torque CLOSE
CLOSE or OPEN 4. Select via Up ▲ Down ▼:
→ ▶ Trip torque CLOSE
→ ▶ Trip torque OPEN
➥ The black triangle ▶ indicates the current selection.
5. Press Ok.
➥ Display shows the set value.
➥ The bottom row indicates: Edit Esc
6. Press Edit.
➥ Display indicates:
- Specialist (4) → continue with step 7
- in bottom row Up ▲ Down ▼ Esc → continue with step 11
Log on user 7. Use Up ▲ Down ▼ to select user:
Information: Required user level: Specialist (4) or higher
➥ The symbols have the following meanings:
- black triangle: ▶ = current setting
- white triangle: ▷ = selection (not saved yet)
8. Press Ok.
➥ Display indicates: Password 0***
9. Enter password (→ enter password).
➥ Display shows the set value.
➥ The bottom row indicates: Edit Esc
2
Torque switching: set
● Status indication S0007 Fault = Torque fault OPEN or Torque fault CLOSE
The fault has to be acknowledged before the operation can be resumed. The
acknowledgement is made:
1. either by an operation command in the opposite direction.
- For Torque fault OPEN : Operation command in direction OPEN
- For Torque fault CLOSE : Operation command in direction CLOSE
2. or, in case the torque applied is lower than the preset tripping torque:
- via the push button RESET in selector switch position Local control
(LOCAL).
3
Limit switching: set
4
Limit switching: set
5
6
7