You are on page 1of 2

APPLICATION

Voltage dips during start-up of large


compressor motors
by Bernhard Cronjé; - DRPA Consulting

Th

Voltage, current and speed measurements


showed that during start-up of the neighboring
compressor, the voltage drop on the bus was
excessive and that the motor was running up
too fast. Further measurements and supply
system modeling revealed that it was caused
by the combination of a high tap setting on
the neighboring compressors auto starting
transformer and certain abnormal supply
system configurations.

Background

A mine was experiencing problems with Fig. 2: Korndorffer starter arrangement.


Fig. 1: Normal supply configuration for compressor
damage to the impellors and pinions of sub station.
two 4,8 MW compressors (type A). It was
noticed that the levels of vibration on the
compressor increased progressively each
time the neighboring 4,5 MW compressor
(type B) was started. This led to the suspicion
that the machines were being damaged
by deceleration and acceleration torques
resulting from excessive voltage drops during
the start-up of the type B compressor. The
manufacturers of the type A compressors
specified maximum allowable voltage drop
of 10%. DRPA were requested to conduct a
voltage dip investigation and to evaluate
the severity of the dips under various system
conditions.

The single line diagram in Fig. 1 shows


the normal supply configuration for the
compressor sub station. Under normal Fig. 3: 11 kV bus voltage during compressor type B start-up.
operating conditions the compressor sub
station is supplied with power from two
88/11 kV 20 MVA transformers operating in full speed, the “star” contactor is opened 20 ms intervals were produced. Another
parallel via two 11 kV overhead line (OHL) effectively converting the auto transformer recorder was set up on the motor coupling to
feeders. starter into a primary reactance starter. Next record the speed during start-up. The results
the “run” contactor is closed to bridge the are shown in Fig. 3, Fig. 4 and Fig. 5.
The type B compressor drive is an 11 kV,
reactance and apply full voltage to the
4,5 MW, BBC synchronous motor and is The average measured voltage drop was
motor.
equipped with an auto transformer starter 6,7%. During this start-up the supply network
panel. It is also known as a Korndorffer starter Measurements conducted was not in its normal configuration. The bus
and it reduces the stator voltage during start- section to the third transformer was also
Two high speed power quality recorders
up. It also has the effect of reducing the start- closed resulting in three 20 MVA supply
were used to make current and voltage
up current by the same ratio as the voltage measurements simultaneously on the type transformers being in parallel. The average
reduction. A simplified diagram of the motor A and B compressor feeders. The recorders start-up current of 1174 A or 4,4 p.u. of rated
and starter is shown in Fig. 2. were set up to measure and record the full load current (270 A) was higher than
To start the motor, the “star ” and “start” current and voltage for the duration of the expected. The motor run-up time of 9 to 10
contactors are closed applying the reduced start-up at high resolution (sampling rate s was also slightly faster than the expected
voltage to the motor. The run contactor >25 kHz). RMS voltage and current values 12 s for this machine. (The manufacturers,
is open. When the motor has reached were calculated and graphs with data at ABB Switzerland quoted 12 s for 83%

energize - December 2006 - Page 38


APPLICATION
higher than the maximum allowable
voltage drop of 10% specified for the type
A compressors.

Starter auto transformer inspection and


tests

The high start-up currents prompted further


investigation into the tap settings of the
auto transformer. The transformer taps
are internal boltable links and cannot be
inspected without draining some of the
oil, disconnecting power cables and then
opening the top cover. By injecting 525 V
on the supply of the auto transformer and
measuring the voltage on the motor side it
Fig. 4: RMS current of compressor type B during start-up. was established that the transformer was on
its maximum tap of 90%. A recommendation
was made to change to the 82% tap in order
to reduce the magnitude of the voltage dip
during start-up.

Supply system modeling

An accurate model of the system was


constructed in ETAP. The start-up of the
motor was then modeled with various
supply configurations. It was found that
with the existing tap settings, the voltage
drop was excessive (i.e. >10%) under
certain conditions e.g. with only one or two
supply transformers in circuit or if one of the
overhead lines trip.

Simulation results for one, two and three


supply transformers gave voltage drops
Fig. 5: Motor speed of compressor type B during start-up. during start-up of 12%, 10% and 7%
respectively. The simulated bus voltage
during start-up with three supply transformers
is shown in Fig. 6.

The simulated value of 7% correlated well with


the measured value of 6,7%. It is therefore
important to monitor the supply configuration
and to ensure that the compressors are not
started when fault levels are too low.

Conclusions

The correct application of starter circuits


on large medium voltage motors is critical
to avoid power quality problems that can
result in costly damage to other equipment.
Accurate measurement of voltage, current
and speed during start-up can reveal a lot
about the motor and the starter circuit.
Fig. 6: Simulated 11 kV bus voltage during start-up of type B compressor.
The ETAP model accurately reproduced the
measurement results and it could be seen
that it is very important to model various
supply and equipment configurations as
starting voltage). These measurement results On a second occasion the voltage dip
only certain combinations may result in
corresponded to that of a DOL starter or a measurements were repeated and this time
problems.
very high tap on the starting transformer. a voltage drop of 10,7% was recorded.
The oscillations observed are due to the This time the supply network was in its Contact Bernhard Cronje,
non-sinusoidal MMF of the machine and are normal configuration i.e. two 20 MVA supply DRPA Consulting, Tel (011) 202-8734,
considered normal. transformers in parallel. The volt drop was b.cronje@drasa.co.za 

energize - December 2006 - Page 39

You might also like