Professional Documents
Culture Documents
And
Electric Energy Management
Eng H Chingosho
PhD (cand), B.Eng (Hons), MSc (Ren-Eng), MZweIE (ZIE), E.C.Z (ZIM), CEM ®,
AEE (USA).
• Alternating Current
– Electron flow changes direction
– Frequency – 50 times per second = 50 Hz
AC
• The usual waveform of alternating current in most electric power
circuits is a sine wave, whose positive half-period corresponds with
positive direction of the current and vice versa.
Basic Electrical Terms & Formulas
Basic Electrical Terms & Formulas
V=IxR
For a fixed resistance, doubling V results in a doubling of I
Basic Electrical Terms & Formulas
Basic Electrical Terms & Formulas
Basic Electrical Terms & Formulas
Basic Electrical Terms & Formulas
Basic Electrical Terms & Formulas
Ohms Law for Power
• Why 3 phase:
– Lower mass of the conductors
– Permit more flexibility in the choice of voltages
– Can be used for single phase load
– 3 phase equipment smaller in size, lighter
– Higher efficiency than single phase
3 Phase delta connection
3 Phase delta connection
3 Phase Wye (Y) connection
3 Phase Wye (Y) connection
3 Phase power (Y = Δ)
• Total Power = V I …….
• For balanced load phase impedances have equal currents
• Power per phase Pp = Vp * Ip * Cos Ø
• Total real power P = 3 * (Vp * Ip * Cos Ø) = 3 * (Vline * √3 Iline/3 * Cos
Ø)
• Three‐phase system
Pa = 1.732 x V x I x Cos phi
• Where Cos phi = power factor
Electric Rates
• Utility Rate Structure Incentives
– Demand Reductions
– Time of day rate or real time pricing
– Seasonal rate
– Power Factor (Cos phi) Correction
– Primary vs. secondary metering
– Rebates and Rate riders (electric heat, etc)
• Potential approaches
– High efficiency equipment
– Scheduling uses off‐peak
– Demand limiting (demand response)
– Duty cycling
Load profile
Facility Electric Load Factor
• Load Factor = 𝐴𝑐𝑡𝑢𝑎𝑙 𝑘𝑊ℎ 𝑈𝑠𝑒𝑑Τ𝑃𝑒𝑎𝑘 𝑘𝑊 ×𝑇𝑖𝑚𝑒
Note: Higher load Factor will reduce unit kWh costs (more kWh per kW i.e. kW‐ fixed costs,
kWh variable costs.)
Example of Demand Control Savings
• A production facility has four large machines with a demand of 200
kW each. The machines could be controlled by a computer which
would limit the total demand to 400 kW at any one time. This
company limits the use of the machines by operational policy which
states that no more than two machines should be turned on at any
given time. This room is separately metered from the rest of the
facility.
• One morning at 8:00 am, a new employee turned on the two idle
machines. At 8:30 am the plant foreman noticed that too many
machines were running and quickly shut down the extra two
machines. Assuming a demand rate of $7.02/kW and an energy rate
of $0.043/kWh determine the cost to the facility of this mistake.
Immediate Cost of Mistake
• The immediate cost on the month's electric bill has two components.
Assuming a demand rate of $7.02/kW and an energy rate of
$0.043/kWh, the immediate cost is calculated as:
kVA = √3 x kV x I
• Note that ground leads must be run in the same cable or raceway as
the power leads
Typical Facility Electrical Distribution System
Voltage Imbalance
• Problems can occur because of voltage imbalance between the three
phases. This can be a serious problem in motors, and is discussed in
the motor section.
• Percent voltage imbalance is found as the ratio of the largest phase
voltage difference from average, divided by the average voltage.
• For example, if we have 220, 215 and 210 volts, the voltage imbalance
is 5/215 = .023, or 2.3 percent.
Upgrade Neutrals
• Many neutrals were not designed to carry any significant amount of
current, and are simply too small.
• Unbalanced loads, harmonics, and especially triplen harmonics cause
neutral current to increase—can be up to 1.73 to 3.0 times the phase
current.
• Solution is to:
• Add neutrals—run a separate neutral for each single phase load.
• Oversize the neutral, or run parallel neutrals to several large loads.
• A facility has a 100 kW electric resistance oven for drying parts. What
is the power factor (Cos φ) of the oven?
Problem 5
• Determine the power available for work for a facility operating a ball
mill powered by an inductive 3 phase electrical motor that is rated at
550 kVA given that the facility has a power factor (Cos φ) of 80%.
Recommend the reactive power to be supplied by the capacitor bank
to achieve unit power factor.
• Given that the facility then decides to just improve the power factor
to 95% .Determine the corrective capacitance in kVAR needed to
achieve this decision.