You are on page 1of 1

Density 992

Water flow rate through CT 225 m3/hr


SP. Heat of water 1 k.Cal/kg °C
Inlet water temperature 37
Outlet water temperature 32
Ambient WBT 29
Cooling tower capacity (TR) = (flow rate x density x sp.heat x diff. temp)/3024

369.0476 TR
20% Excess 442.8571 TR

You might also like