4 hydraulic calculations
= 14.14 m
32
We start counts ( Q and P) for sprinklers :
2- P2 = P1 + Pf (1- 2)
. ( ) .
F ( 1-2) = ( ) . ( ) .
= 0.16 psi\ft
= ( 0.16) x (14.8)=2.36
Q2= Q1 x 𝑝2\𝑝1
= 20 x 15.12\12.76
= 21.77 gpm
33
We find the value of (C & D) through the tables following the NFPA:
3- P3 = P2 + Pf (2- 3)
. ( . ) .
F ( 2-3) = ( ) . ( ) .
= 0.64 psi\ft
= ( 0.64) x (10.91)=6.98psi
Q3=( Q1+Q2) x 2
= 83.54 gpm
NOTE :
Q3 = Q2 & Q4 = Q1
P3 = P2 & P4 = P1
34
4- P6 = P3 + Pf (3- 6 )
. ( ) .
F ( 3-6) = ( ) . ( . ) .
= 0.317 psi\ft
= ( 0.317) x (20.2)=6.4psi
Q6= Q5 x 𝑝6\𝑝5
= 83 x 28.4\22
= 94.3 gpm
5- P11 = P6 + Pf (6- 2)
. ( . ) .
F ( 6-11) = ( ) . ( ) .
= 0.311 psi\ft
= ( 0.311) x (22.2)=6.9psi
Q11= Q6 x 𝑝11\𝑝16
= 175.19gpm
35
6- P12 = P11 + Pf (11- 12)
. ( . ) .
F ( 11-12) = ( ) . ( . ) .
= 0.1 psi\ft
= ( 0.1) x (104.8)=10.48
= 175.19 gpm
. ( . ) .
F ( 12-13) = ( ) . ( ) .
= 0.043 psi\ft
= 175.19gpm
36
8- P14 = P13 + Pf (13- 14)
. ( . ) .
F ( 13-14) = ( ) . ( ) .
= 0.0106 psi\ft
= 175.19gpm
. ( . ) .
F ( 14-15) = ( ) . ( ) .
= 0.0106 psi\ft
= ( 3m x 3.28 ) ft + 59 ft =68.84 ft
= 175.19gpm
37
10- P16 = P15 + Pf (15- 16)
. ( . ) .
F ( 15-16) = ( ) . ( ) .
= 0.01 psi\ft
= 175.19gpm
. ( . ) .
F ( 16-17) = ( ) . ( ) .
= 0.01 psi\ft
= ( 15 m x 3.28 ) ft + 32 ft =81.21 ft
38
Q17= Q16 x 𝑝17\𝑝16
= 175.19gpm
p =
.
= = 1.26 m
.
Q = Qtot x 1.5
1- Suction =4 in
2- Discharge =4in
39
In the end, we find that the value of each of (Q &P) are required to
pump:
= 177.3 X 40 X 0.003785
= 26.8 m2
Where …
Length tank = 3 m
Height tank = 3 m
Where…
NOTE : The value of the nfpa (30-60) and Height of the tank between
(3-5) .
40
1.5 Pump design room
-We used the room at the pumps and three pumps are :
1- Jockey pump .
2- diesel pump .
3- electrical pump .
1- OS&Y(gate valve).
2- flexible connection.
3- reduce.
2- flexible connection.
3- Pressure gauge.
4- check valve.
-We put a test between the pump room and tin line.
41
1.6 Selection of the pump
2- P = 68.26 psi
Now :
42