EXTERIOR INTERIOR

SELECTED ALUMINIUM PROFILE FABRICATION SILICONE SEALANT APPLIED TO FIXING


TO MANUFACTURERS DETAILS HEADS. AS PER MANUFACTURERS'
DETAILS
VERTICAL MEMBRANE TERMINATION
HEIGHT CALCULATED BY STEPS 1-3 SILICONE SEALANT OVER CLOSED CELL
COMPLETED BY ARCHITECT (SEE BELOW) BACKING ROD BETWEEN WATERSTOP
ANGLE AND SUBSILL
STOP ENDS TO SUBSILL SEALED WITH
ALUMINIUM WATERSTOP ANGLE FOR
SILICONE SEALANT AS PER MANUFACTURERS
WATERPROOFING MEMBRANE VERTICAL
DETAILS
TERMINATION. ANGLE TO CONTINUE AROUND
10mm MIN TO AS4654.2-2012 GAP BETWEEN OPENING AND RETURN AT BOTH ENDS AND BE
THRESHOLD SUBSILL AND EXTERNAL TILE. SEALED TO JAMB FLASHING OR SARKING
WHERE GREATER THAN 10mm PROTECTIVE WITH SILICONE SEALANT
COVER TILE TO BE PROVIDED TO VERTICAL
FACE OF THRESHOLD. FALL

PROFILE
TERMINATION
ALUMINIUM COVER PLATES WITH MECHANICAL

DEPTH
MIN 1:100
70 M M

HEIGHT
FIXINGS MUST NOT BE USED TO PREVENT
VOIDING OF THE MEMBRANE SYSTEM
FINISHED

REBATE DEPTH
SET DOWN
FLOOR

HOB DEPTH
BUILT UP
SCREED
DEPTH
SELECTED TILES ON REBATE WIDTH
UNDERTILE WATER PROOFING
SELECTED ENGINEERED TIMBER OR TILE
PRIMARY BASE WATERPROOFING MEMBRANE TO FLOORING TO FINISH AGAINST ALUMINUM
LINE UP VERTICAL FACE OF SETDOWN AND WATERSTOP ANGLE
UP ALUMINIUM WATERSTOP ANGLE
PACKING TO LEVEL SUBSILL WITH
MEMBRANE PROTECTOR 'SNAKE SKIN'
MEMBRANE TO CONTINUE ACROSS BALCONY
POLYTHENE DAMP COURSE POLYCOURSE OR
AND INTO ROOF WASTE OUTLET
SIMILAR. CARE TO PROTECT MEMBRANE OF
PACKERS BY USE OF DPC
PRIMER APPLIED TO ALL MEMBRANED AREAS
WITH OVERCAPS AS PER MANUFACTURERS DYNA BOLT
DETAILS
CEMENTATIOUS NON-SHRINK GROUT FORMED
SCREED TO FALL WITH FALL, FINISH TO HOB TO SUPPORT AND LEVEL SUBSILL
BE NO FLATTER THAN 1:100 AS PER 10mm FOAM FILLER PACKING TO SCREED
CLAUSE 2.5.2 OF AS4654.2-2012 EDGE FOR THERMAL MOVEMENT
PRIMARY WATERPROOFING MEMBRANE TO
RUN UP VERTICAL FACE OF SLAB
SETDOWN AND UP ALUMINIUM ANGLE
STEP 3 STEP 2 STEP 1
WATERPROOFING MEMBRANES FOR EXTERNAL ABOVE STRUCTURAL DESIGN ACTIONS PART 2 : WIND LOADS FOR HOUSING AS4055-2012
GROUND USE, DESIGN & INSTALLATION WIND ACTIONS - TABLE 2.2 WIND CLASSIFICATION FROM WIND REGION & SITE
TO BE IN ACCORDANCE WITH TABLE A1, - AS/NZS 1170.2-2011 SYDNEY CONDITIONS
AS4654.2-2012 TYPICALLY 46M/S. ENSURE TO CONFIRM - SYDNEY = WIND REGION A
- WIND SPEED, ULTIMATE LIMIT STATE AGAINST PROJECT WIND STUDY - SYDNEY = TERRAIN CATERGORY, TYPICALLY TC3, CONFIRM PER
=70mm FROM STEPS 1. + 2. + 3. PROJECT
- TOPOGRAPHIC CLASS TYPICALLY T3- T4, CONFIRM PER PROJECT

TO BE COMPLETED BY ARCHITECT AND TO BE COMPLETED BY ARCHITECT AND


INCORPORATED INTO DOCUMENTATION INCORPORATED INTO DOCUMENTATION

ALUMINIUM FABRICATION PROFILE SELECTION WATERPROOFING PRODUCT SELECTION


PROFILE / MANUFACTURER SELECTION PRODUCT MANUFACTURER CONTACT

REBATE WIDTH

REBATE DEPTH / SETDOWN

FORMED HOB HEIGHT

FORMED HOB WIDTH

WATERSTOP ANGLE HEIGHT

Project: Title: Project #: Scale: Drawn by:


PARKVIEW STANDARD STEPPED RECESSED 742 1 : 5 @A4 AK
DETAILS THRESHOLD BALCONY Drawing No: Rev: Approved by:

0102 F IN PARKVIEW CONSTRUCTIONS PTY LTD


ABN 41078064963

FINAL ©COPY RIGHT PARKVIEW CONSTRUCTIONS


ALL RIGHTS ARE RESERVED. NO PART OF THIS PUBLICATION MAY BE REPRODUCED OR TRANSMITTED IN ANY
REV NO. REV DESCRIPTION DATE FORM OR BY ANY MEANS, WITHOUT THE EXPRESSED PERMISSION OF PARKVIEW CONSTRUCTIONS, UNLESS
SPECIFICALLY ALLOWED FOR BY THE TERMS OF A CONTRACTUAL AGREEMENT WITH PARKVIEW
A Revision 1 July 2017 CONSTRUCTIONS. PARKVIEW CONSTRUCTIONS GRANTS THE PRINCIPAL AND/OR CONSULTANT AN
B Revision 2 Sept 2017 IRREVOCABLE LICENCE TO USE THIS DOCUMENT FOR THE PROVEN WITH THE PRINCIPAL AND/
ORCONSULTANT TO ENSURE THAT THIS DOCUMENT IS USED ONLY FOR THE PORPOSE OF THE PROJECT.
C Revision 3 Dec 2017
D Final Mar 2018
E Final July 2019
F Final Issue 09/10/2019