PROJECT - JALANDHAR RAILWAY STATION

PACKAGE - DRINKING WATER SYSTEM


SUMMARY OF COST
S.No. DESCRIPTION AMOUNT IN RUPEES
1) CHAPTER-1 : REVERSE OSMOSIS BASED PLANT

TOTAL AMOUNT IN RUPEES 0

EXCLUSIONS

1) Civil works shall not form any part of this bill including foundations, core cuts and any other kind of cutouts in any structural component etc.

2) Statutory deposits or fee for any approval or liasoning.

RATES
1) The quoted rates are exclusive of all taxes and duties.
2) The rates shall be prepared in conjuction and with reference to the contents of S.C.C., Specification & Drawings.

3) The rates quoted shall also include for providing any temporary work or preparatory work required to execute the particular items of work.

4) The unit prices stated hereunder shall be deemed to include, but not be limited to the following :
a. Site management and supervision, labour and all costs in connection therewith, including the cost of overtime as necessary.
b. The supply, fabrication and supervision during installation of all goods and all costs in connection therewith.
c. Delivery as appropriate.
Paint, tools, equipment and all cost in connection therewith site facilities and all other costs from items that are necessary to execute the
d. Work.
e. Waste of Material.
f. Mobilization costs, overhead costs and profit.
g. Major civil works shall not form any part of this contract including foundations.

The rates for each item of work included in the schedule of quantities shall unless expressed stated otherwise, include cost of all equipment,
5) ancilliary equipment, fixing material, accessories, tools, plants, transport, labour and incidentals required for the completion of the work as
called for in the item and as per Specification and drawings.

NOTES
All the items of work under this contract shall be executed strictly in accordance with the description of the item in the schedule of
1) quantities relevant drawings and specifications read in conjunction with appropriate Indian Standard Specifications, Special conditions of
contract.

This bill is to be read in conjunction with all other project documents and deviations if any shall be brought into the notice of the consultant
2) in prior.

All the items of work given in this schedule of quantities shall be executed strictly in accordance with National Building codes 2016 and
3) requirements of the Indian standards read in conjunction with the relevant drawings, specifications and the appropriate Indian Standards.

The contractor shall visit the site and shall satisfy himself as to conditions under which the work is to be performed. No extra claim as a
4) consequence of ignorance or on grounds of insufficient description will be allowed at a later date.

No Alteration whatsoever is to be made to the text or quantities of this schedule of quantities unless alteraion is authorised in writing by
5) client. Any such alterations, notes or additions shall, unless authorised in writing be disregarded when tender documents are considered.

6) Any error in totalling in the amount column and in carrying forward totals shall be corrected.

Any error in description or in quantity or omission of items from the contract schedule shall not vitiate this contract but shall be corrected
7) and deemed to be a variation required by the owner.

1
PROJECT - JALANDHAR RAILWAY STATION
PACKAGE - DRINKING WATER SYSTEM
DETAILED ESTIMATE
S. NO. DESCRIPTION UNIT QUANTITY UNIT RATE AMOUNT
1 CHAPTER-1 : REVERSE OSMOSIS BASED PLANT

Supply, Installation, Testing & Commisioning of Reverse


Osmosis unit of following capacity to treat the raw water
having TDS 1200 ppm and reducing TDS to 100ppm and
hardness less than 50 ppm or as per WHO standards. The
operating voltage to 230 volt AC +/- 10%. Potable water system
1.1 components shall comply with Safe Drinking Water Act
Amendments, the 1988 Lead Contamination Control Act and
shall be to ANSI/NSF 61 Section 9. Contractor shall require to
submit test report post installtion of RO plant and cost shall be
inclusive of 15 days training to engineer incharge.

1. Pre and Post treatment Dosing System (each consisting of


one HDPE tank of 200 litres capacity with a positive
displacement diphragm dosing speed & stroke control pump
(1W + 1S) having variable flowrate of 0-6 lph. The motor shall
be suitable for operation at 240 V/Single phase/50 Hz. Supply.
The pump shall be supplied complete with necessary agitator,
polypropylene piping, valves, strainers, low level switch(Range
0-600mm) and injection fittings.):
a) Biocide dosing system for pre and Hypochlorite and soda ash
post dosing and dosage rate 2-3 mg/l.
b) Anti scalant dosing system for dosing downstream of MGF
and ACF and dosage rate 5 mg/l.
c) Acid dosing system in inlet of RO membrane and dosage rate
2 mg/l.
d) SMBS dosing system for dechlorination at the inlet of RO
membrane and dosage rate 5-10 mg/l.
e) PH Correction Dosing system(NaOH) for maintaining the ph
to drinking water standard. Dosage required will be 2 mg/l.

2. Filtration System:

a)Activated Carbon Filter with initial charge of


pebbles, anthracite, media , connecting with multiport valve
(for controlling all operations for rinsing, backwashing, service
etc under automated system linked with differential pressure
transmitter and differential guage), glycerine filled pressure
gauge at inlet, outlet and back wash (each with isolation cock),
complete as required including wiring and anunciation
complete as required with SS 304 piping(paid separately)
complete as required and all other accessories required to
make the system complete as per the specifications.
b) Water softener with brine tank (200 litre HDPE).
c) CIP System.
d) Raw water feed Pump.

2
3. Reverse Osmosis System:

a) High Pressure Pump(1W+1S): Vertical


centrifugal Pump with low pressure switch for smooth
operation, dry run protection of adequate capacity and head
with SS AISI 304 stage casing, AISI SS 304 impellors, SS Suction
chamber, SS 304 Pump shaft, steel base plate, carbon
mechanical shaft seal and suction and discharge casing as per
IEC standards, connected to TEFC Ventilated induction motor of
2 pole, 2900 RPM, suitable for 400/440 Volts, 3 phase, 50 Hz
A.C. supply with glycerin filled pressure gauge , vibration
elimination pads, dry run protection etc. complete with base
and frame, nuts and bolts. The pump should be rated at the
premium efficiency rating of IE. The pump inclosure to be
minimum IP 54 rated and insulation class to be F.
b) Reverse Osmosis Block comprising of micron filter and
membrane encased inside pressure vessels. the membrane to
be thin film composite in spiral wound construction. Membrane
material to be TFC Polyamide. RO Housing to FRP material with
pressure rating of 250 psi.
c) Ultraviolet Unit of required flow rate.

1.1.1 Capacity: 1000 LPH Set 1