G3516 Generator Set CSZ00001-UP(SEBP3374 - 29) - Document Structure Page 1 of 2

Shutdown SIS

Previous Screen

Product: GENERATOR SET


Model: G3516 GENERATOR SET CSZ
Configuration: G3516 Generator Set CSZ00001-UP

Troubleshooting
G3500 Engines
Media Number -SENR6413-08 Publication Date -01/06/2008 Date Updated -05/06/2008

i01995071

Poor Fuel Consumption


SMCS - 1250-035

Probable Causes
z Fuel leak

z Incorrect ignition timing

z Incorrect air/fuel ratio

Recommended Repairs
Fuel Leak

Inspect the fuel system for leaks.

Ignition Timing

Note: Data from a fuel analysis is required for this procedure.

Use an electronic service tool to check for the correct desired ignition timing.

Adjust the ignition timing according to the recommended timing in the Engine Performance, "Fuel
Usage Guide".

Air/Fuel Ratio

An air/fuel mixture that is too lean will increase fuel consumption. A change in the fuel energy content
will change the air/fuel ratio. Obtain a fuel analysis.

The fuel supply pressure must be adequate and stable.

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/s... 21/09/2009
G3516 Generator Set CSZ00001-UP(SEBP3374 - 29) - Document Structure Page 2 of 2

Strike the gas pressure regulator with a soft hammer. If the engine speed changes, inspect the internal
parts of the gas pressure regulator for wear. Inspect the gas pressure regulator's diaphragm for leaks.
Make sure that the valve moves freely. The valve must seat correctly.

Verify that the exhaust emissions are correct.

Copyright 1993 - 2009 Caterpillar Inc. Mon Sep 21 12:58:40 UTC+0700 2009
All Rights Reserved.