G3516 Generator Set CSZ00001-UP(SEBP3374 - 29) - Document Structure Page 1 of 2

Shutdown SIS

Previous Screen

Product: GENERATOR SET


Model: G3516 GENERATOR SET CSZ
Configuration: G3516 Generator Set CSZ00001-UP

Troubleshooting
G3500 Engines
Media Number -SENR6413-08 Publication Date -01/06/2008 Date Updated -05/06/2008

i01921749

MID 014 - CID 0168 - FMI 02 System Voltage


intermittent/erratic
SMCS - 1408-038

Conditions Which Generate This Code:

The engine is running and one of the following conditions has occurred:

z The control module for the Electronic Ignition System (EIS) has detected engine rpm during a
normal powerup sequence.

z There is a noisy component in a secondary circuit of the ignition system.

System Response:

The shutdown output is activated. The code may be viewed on the Digital Diagnostic Tool (DDT) or on
the Caterpillar Electronic Technician (ET).

The engine is shut down.

Test Step 1. Perform the following diagnostic procedure: Electrical Power Supply

Results:

z OK - STOP

z Not OK -

Repair: Perform the following diagnostic procedure: Troubleshooting, "Ignition Transformers


Secondary Circuit and Spark Plugs".

STOP