Troubleshooting
G3500 Engines
Media Number -SENR6413-08 Publication Date -01/06/2008 Date Updated -05/06/2008

i02336401

MID 014 - CID 0301 - FMI 05 Ignition Transformer Primary #1


open circuit
SMCS - 1561-038

Conditions Which Generate This Code:

The primary circuit of the transformer is diagnosed with an open circuit.

System Response:

The warning output is activated. The diagnostic code may be viewed on the Digital Diagnostic Tool
(DDT) or on the Caterpillar Electronic Technician (ET).

One of the following conditions is the source of the diagnostic code:

z A broken circuit driver's wire for the transformer

z A broken return wire for the transformer

z An open circuit within the primary winding of the transformer

z An internal failure of the control module for the Electronic Ignition System (EIS)

Test Step 1. Perform the following diagnostic procedure: Ignition Transformers Primary Circuit

Results:

z OK - STOP