G3516 Generator Set CSZ00001-UP(SEBP3374 - 29) - Document Structure Page 1 of 2

Shutdown SIS

Previous Screen

Product: GENERATOR SET


Model: G3516 GENERATOR SET CSZ
Configuration: G3516 Generator Set CSZ00001-UP

Troubleshooting
G3500 Engines
Media Number -SENR6413-08 Publication Date -01/06/2008 Date Updated -05/06/2008

i02336403

MID 014 - CID 0301 - FMI 12 Ignition Transformer Primary #1


short to return
SMCS - 1561-038

Conditions Which Generate This Code:

The primary circuit of the transformer is diagnosed with a short circuit to the return for the transformer.

System Response:

The warning output is activated. The diagnostic code may be viewed on the Digital Diagnostic Tool
(DDT) or on the Caterpillar Electronic Technician (ET).

The cylinder will misfire.

One of the following conditions is the source of the diagnostic code:

z A short circuit in the wiring from the control module for the Electronic Ignition System (EIS) to
the transformer

z A short circuit within the primary winding of the transformer

z An internal failure of the control module for the Electronic Ignition System (EIS)

Test Step 1. Perform the following diagnostic procedure: Ignition Transformers Primary Circuit

Results:

z OK - STOP

Copyright 1993 - 2009 Caterpillar Inc. Mon Sep 21 13:16:35 UTC+0700 2009
All Rights Reserved.

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/s... 21/09/2009
G3516 Generator Set CSZ00001-UP(SEBP3374 - 29) - Document Structure Page 2 of 2

Private Network For SIS Licensees.

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/s... 21/09/2009

You might also like