G3516 Generator Set CSZ00001-UP(SEBP3374 - 29) - Document Structure Page 1 of 1

Shutdown SIS

Previous Screen

Product: GENERATOR SET


Model: G3516 GENERATOR SET CSZ
Configuration: G3516 Generator Set CSZ00001-UP

Troubleshooting
G3500 Engines
Media Number -SENR6413-08 Publication Date -01/06/2008 Date Updated -05/06/2008

i02336396

MID 014 - CID 0300 - FMI 03 Primary Return short to +batt


SMCS - 1408-038

Conditions Which Generate This Code:

A return for an ignition transformer is shorted to the +Battery side.

System Response:

The warning output is activated. The diagnostic code may be viewed on the Digital Diagnostic Tool
(DDT) or on the Caterpillar Electronic Technician (ET).

Engine performance is affected. Engine operation may continue, or the engine may shut down due to
lugging.

Test Step 1. Perform the following diagnostic procedure: Ignition Transformers Primary Circuit

Results:

z OK - STOP