G3516 Generator Set CSZ00001-UP(SEBP3374 - 29) - Document Structure Page 1 of 1

Shutdown SIS

Previous Screen

Product: GENERATOR SET


Model: G3516 GENERATOR SET CSZ
Configuration: G3516 Generator Set CSZ00001-UP

Troubleshooting
G3500 Engines
Media Number -SENR6413-08 Publication Date -01/06/2008 Date Updated -05/06/2008

i02336846

MID 014 - CID 0317 - FMI 08 Load Sensor (MAPS) signal


abnormal
SMCS - 1439-038

Conditions Which Generate This Code:

The duty cycle or the frequency for the manifold absolute pressure sensor (MAPS) is outside of the
normal range.

System Response:

The warning output is activated. The diagnostic code may be viewed on the Digital Diagnostic Tool
(DDT) or on the Caterpillar Electronic Technician (ET).

Under normal conditions, protection from detonation is enabled only when the manifold pressure is
greater than 60 kPa (8.7 psi). When a 317-08 code is activated, protection from detonation is always
enabled.

Emissions may be affected.

Test Step 1. Perform the following diagnostic procedure: Inlet Manifold Pressure Sensor

Results:

z OK - STOP

Copyright 1993 - 2009 Caterpillar Inc. Mon Sep 21 13:20:59 UTC+0700 2009