Professional Documents
Culture Documents
PART 1 – GENERAL
1.1 Description
1.2 Standards
1. PS
2. PEC 2009 (Part 1 and 2)
3. IEC
4. NEMA
5. UL
6. ANSI
1. PS
2. IEC
3. NEMA
4. UL
1.3 Submittals
c. One line diagram showing electrical ratings, overcurrent protection device ratings,
cable lugs, metering displays, identification nameplate.
d. Wiring diagrams.
e. Installation instructions.
a. Field inspection and testing shall occur after installation is complete, feeders are
terminated, and the room is secure. Testing shall be conducted not more than 4
weeks before equipment is energized.
1.5 Identification
a. Provide an identification nameplate for each switchboard, each main, and each
feeder overcurrent protection device.
a. Prepare a short circuit and coordination study based on the actual overcurrent
protection devices proposed for use. Provide overcurrent protective devices of
suitable type and rating to meet or exceed the available short circuit currents
indicated in the short circuit study. The study shall be prepared by a locally
registered electrical engineer.
b. The study shall be submitted with the distribution equipment submittal and shall
indicate where device substitutions are being made in order to achieve adequate
interrupting capacity ratings for each piece of equipment.
c. The study shall include recommended settings of adjustable overcurrent and ground
fault settings.
d. The study shall indicate the current limiting effect of fuses and series rated current
limiting circuit breakers. Submit evidence of UL series ratings of overcurrent
protection devices.
PART 2 – PRODUCTS
2.2 General
a. The Low Voltage Switchboard shall be certified & TESTED by the manufacturer.
b. Low voltage switchboards shall be of the ratings and configurations shown on the
Drawings.
c. Low voltage switchboards and overcurrent protection devices shall have a minimum
short circuit rating as specified herein or greater where indicated on the Drawings.
1. Low voltage switchboards are identified with the prefix LVSG as shown
on the Drawings.
2. Maximum allowable physical dimensions: 800 mm wide by 1000 mm
deep per section.
3. Low voltage switchboards: Main bus shall withstand a prospective fault
level as indicated in the drawings at 400 volts, 3 phase (RMS
Symmetrical) for 1 second in accordance with the test procedures laid
down in the relevant NEMA/ANSI or IEC Standards.
2.3 Construction
a. Low voltage switchboards shall be NEMA 4 free standing metal enclosed, tamper
proof, front and rear accessible, with individually mounted main and feeder
overcurrent protection devices of the number, rating, and arrangement as shown on
the Drawings. Vertical sections shall be aligned front and rear.
c. The Low Voltage Switchboard shall have a full height and depth fire retardant and
non-hygroscopic barriers, from top to bottom and from front to rear to contain faults
and to minimize the passage of ionized gases between vertical Sections.
d. Low voltage switchboards shall be provided with adequate lifting means and be
capable of being rolled or moved into position and bolted directly to the floor without
the use of floor sills.
e. Steel surfaces shall be chemically cleaned and treated, providing a bond between
paint and metal surfaces to prevent the entrance of moisture and formation of rust
under the paint finish. Finish shall be ANSI-61 grey enamel paint.
f. Space for future devices shall include all necessary bus, overcurrent protection
device supports and mounting, and connections.
i. Cables shall be supported within the Switchboard so that stress is not imposed on
termination.
a. Bus bars shall be arranged throughout A-B-C left to right, top to bottom, and front to rear.
Bus bars shall be permanently labeled by phase. Bus joints shall be bolted with high
tensile steel bolts with spring loaded Belleville type washers.
b. Bus bars shall be 98% conductivity silver plated copper sized at not more than 1000
amperes per square inch. Bus bars shall be of the ampere rating (continuous) shown on
the Drawings.
c. Horizontal bus shall be full size, tapered bus is not permitted. Provide bolt holes drilled
and tapped for future extension at the end of bus bars including neutral and ground bus
so that the addition of a future section would require only the installation of standard
bolted splice plates.
Air Circuit Breakers (ACB), shall be individually mounted manufactured and tested in
accordance with applicable IEC/NEMA/ANSI standards.
a. ACB shall be 4-pole or 3-pole and having fault interrupting rating of 80 kA at 400 volt,
60 HZ. ACB shall be UL listed for continues operation at 100% rated load and
electrically operated, draw-out type and shall operate as follows:
2.A set of shutters shall be provided for automatic shielding of stationary main
contacts in the breaker in the isolated position. Each set shall be capable of
being individually operated and padlock closed.
3. Bus bar shutters shall be painted “Red” and shall be clearly labeled
“Busbars” in large white letters. Circuit shutters shall be painted “Yellow” and
clearly “circuit” in large white letters.
f. Ground fault protection shall be provided on all service disconnect switches rated 1000
amperes or more as required by the local electrical code. The ground fault protection
shall consist of the following:
2. Ground Fault Sensor: The ground fault sensor shall continuously sense the
output of the current monitor. Should the sensor detect a ground current in
excess of the pick-up setting for a duration exceeding the time delay, the sensor
shall shunt-trip the appropriate device. The sensor shall have an adjustable pick-
up of 100 to 1200 amperes and an adjustable time delay from 0 to 60 cycles.
3. Test Panels: Each ground fault sensor shall be provided with a test panel which
shall completely test the ground fault system. The test panel shall indicate that a
ground fault was sensed or test the system with or without tripping the switch or
circuit breaker. The test panel shall be installed in the front of the switchboard
adjacent to the device being protected.
4. Shunt-Trip: Each device with ground fault protection shall be provided with a
shunt-trip which shall automatically open the device when signaled by the sensor.
5. Provide fuse protected control power transformer from the switchboard line side
for the ground fault system. Ground fault and shunt-trip device shall be capable
of operation at 55% of rated voltage.
6. Set each ground fault sensor pick up setting at 25 percent of the rating of over-
current device with a 6-cycle time delay unless specifically indicated otherwise in
the accepted short circuit and coordination study.
2. No access shall be possible to ACB in the “open”, “test”, and “isolated” positions.
4. Main contact arching contacts shall be rated and protected to the fault current level
of the circuit breaker.
5. Circuit breakers shall have at least nine auxiliary contacts in any combination of
normally open, normally closed and changeover.
6. Auxiliary contacts shall be self-cleaning; silver-plated and shall be available for 500
volts AC and 110 volts DC.
8. Circuit breakers shall have manual local and remote operating facilities.
a. Provide an electronic digital true RMS sensing metering display for each main
switchboard main circuit breaker. The display shall indicate voltage (each phase to
each phase and each phase to neutral, amps (each phase), watts, vars, power
factor, frequency, watt demand, and watt hours. Display shall be positioned not
lower than 1.2 meters or higher than 1.8 meters above the finished floor. Each
metering display shall be compatible for accepting or sending output/input signals
from the Building Management System.
b. Provide a remote terminal unit (RTU) in each Switchboard. All digital and analog
input/output signal wiring to all solid-state protection and metering devices at circuit
breakers shall be terminated at the RTU. The terminals at RTU shall be labeled for
field connections to the BMS system.
c. Metering and circuits shall be supplied and installed in accordance with ANSI Cl2.4,
Cl2.10, ANSI C39.1, and ANSI C57.13 and the following requirements. In addition to
the items listed below, the terminals for connection of portable check metering shall
be provided. These terminals shall be clearly labeled and cross referenced to the
circuits to which they are connected.
h. Potential Transformer
i. Current Transformer
1. Shall comply fully with the requirements of ANSI57.13 and shall be of adequate
burden and class for the duty.
2. Shall have 5 amperes secondary.
3. Shall withstand safely the mechanical and thermal stresses of its associated
ACB.
4. The polarity of windings shall be marked with approved labels.
5. Current transformers shall be connected to equipment via test links.
6. Accuracy shall be as listed in table B of ANSI C37.20
a. Push Buttons
1. Shall be oil tight pattern, heavy duty, and rated at a minimum of 10 amps
inductive.
2. Consist of an actuating button assembly coupled to an interchangeable contact
assembly of sufficient poles to suit the application.
3. Color codes shall be:
b. Indication Lights
1. Shall be of the domed glass or plastic lens type employing connected neon lamps
rated at 6 watts. The indication must be clearly visible from the sides or front at a
distance of 15 meters in a normally illuminated room.
2. Indication lights shall have black bezels.
3. The bodies shall be ventilated to ensure efficient heat dissipation. Connection to
lights shall be by screw to clamp terminals. Soldered termination is unacceptable.
4. Color Codes shall be:
i. De-energized - Green
ii. Energized - Red
iii. Abnormal condition - Amber
iv. Other functions - Blue or White
c. Relays
2. Auxiliary Relays
4. Time Switches
1. Conductors running within the bus bar chambers shall be double insulated.
2. All control wiring shall be color coded and marked at both ends, indicating the
device or equipment, including specific terminal number to which the remote
end of the wire is attached.
9. The terminal blocks shall be adequately rated for the duty and shall have 20%
spare capacity for future use.
10. Terminal blocks of the insertion or tunnel type shall incorporate captive pinching
screws and saw-toothed clamping plates with an inherent locking feature.
1. The heaters shall be suitable for operation on 230V 60H Z AC supply with
thermostat control and manual local ‘ON/OFF’ switch.
b. Where indicated “space for future” or “space” shall mean to include bus, devices
supports and connections.
c. The individually mounted device shall be isolated in its own compartment and shall
be positioned vertically with operating handles extending through the hinged front
cover.
d. Feeder Breaker shall have ground fault protection on rated 1000 amperes or more
as required by the local electrical code. The ground fault protection shall consist of
the following:
PART 3 – EXECUTION
3.1 General
a. Install low voltage switchboards when the area is free and clear of dust and debris.
Protect low voltage switchboards from dust and moisture. Do not utilize switchboard
for temporary lighting and power services.
a. Vacuum back boxes clean of debris after installation and wiring of feeder cables.
b. Repair and touch up paint damaged surfaces.
a. Inspect for physical damage, proper alignment, anchorage and grounding. Check
proper installation and tightness of connection of busbars, circuit breakers as well as
feeder terminations.
3.4 Interfacing
a. Provide all the necessary relays and wires in conduit for the interfacing of LVSG with
Genset Control Panel, Capacitor Bank and for BMS provision.
END OF SECTION