Elevator Inspection and Thorough examination report/check list

TUV Southwest, Inspection DEPT.www.tuvsw.com

Doc.No : Procedure. No : Standard Ref :


Owner/Customer

Owner Id Project/Location

Registration NO Name Of Equipment

Chassis No Model Of Equipment

Year Of Manufacture Name Of Manufacture

Description Of Equipment

Periodic Record:-
Type Of Examination Initial / Periodic/ Major Last Examination Date
Date Of Examination Next Examination Due
Test Details :-
Type of Driving Machine No of Floor Served Rated Capacity/No of persons Test Load Applied

Type of Use Type of Door Suspension Rope Dia / Falls Rated Speed/Actual speed

PA-Satisfactory ; CO- Comments (Finding), RE-Recommendation ; FL-Not Satisfactory ; NA-Not Applicable


MACHINE PULLEY / PULLEY SPACE RESULT 43 Overload device function
1 Instruction manual circuit diagram and test certificates/reports 44 Stopping accuracy of the car, ± 10 mm, Ref: 5.12.1.1.4
2 Access to the machine room/Controller cabinet 45 Horizontal clearance bet. landing door and car door sill, ≤ 35 mm, Ref: 5.3.4
3 Socket outlet condition 46 Clearance between car door sill & well wall
Lighting Intensity in working areas (at least 200 lux & 50 lux to move between
4 47 Unusual noise or vibration
working areas), ref: 5.2.1.4
5 Effective ventilation 48 Operation during emergency fire operation
6 Main switch function, identifiable & lockable CAR TOP & HOIST WAY RESULT
7 Inspection control condition 49 Car top inspection control
8 Controller component label & protection 50 Emergency stopping device function
9 Machine unit & brake operation. 51 Lighting (shaft, car top) & socket outlet
10 Machine traction, sheave & pulley grooves condition 52 Lighting at least 50 lux, Ref: 5.2.1.4

11 Final limit safety switches function. 53 Fall protection guards & warning sign
Over-speed governor specification & function (TR at least 115 % of the RS &
12 54 Headroom clearance when the counterweight rests on its fully compressed buffer
(1.25.V+0.25/V) for RS > 1.0 m/sec), ref: 5.6.2.2.1.1
13 Over-speed governor electric safety device function 55 Refuge Dim: Upright(0.40x0.50x0.20)m & Crouching(0.50x0.70x1.0)m, Ref: Table 3
14 Safety gear operation & safety device function 56 Mechanical car blocking device & electric safety device (For MRL)
15 Ascending car speed governor function 57 Governor rope condition &termination
16 Protection for unintended car movement 58 Compensating rope/chain condition & termination
17 Slippage test 59 Car & counterweight roller/guide condition
18 Balancing check 60 Car top deflector pulley condition & protection guard
19 Communication device 61 Trailing cables condition
20 Manual emergency operation (brake release) 62 Emergency trap door & electric safety devices

21 Emergency operation detailed instruction 63 LANDING DOOR ASSEMBLY & LANDING AREA

Effective mechanical landing door locking element, engaged at least 7 mm


22 Emergency landing device function (battery operated) 64
mechanical/electrical, Ref: 5.3.9.1
23 Suspension rope condition & terminations 65 Landing door unlocking device
24 Protection guards on rotating parts 66 Landing door electric safety device
25 Electrical wiring & earth bonding condition 67 Apron, sill & guide condition
Dimension & Clearances. Ref: 5.2.6.3.2; Clear H at working areas ≥ 2.10 m; Clear
26 68 Operational clearances
H at working movement ≥ 1.80 m
27 Warning signs, notices & markings 69 Landing door self-closing mechanism
28 Equipment not related to elevator 70 Lighting at landing areas, ≥ 50 lux, Ref: 5.3.7.1
29 Fire prevention means provided 71 Hall Panel buttons & indicators
30 Pressure relief valve test (Hydraulic drive) PIT RESULT
31 Manual relief valve test (Hydraulic drive) 72 Safe access to pit
32 Re-leveling check (Hydraulic drive) 73 Lighting & socket outlet

CAR RESULT 74 Emergency stopping device function


33 Car control operating devices function 75 Free from water ground leak
Partition screen between the elevators with common shaft, 2.5 m above the floor
34 Label indicating rated load/number of person. 76
of the lowest landing, Ref: 5.2.5.5.2.1
35 Car lighting & Emergency lighting 77 Counterweight screen guard
36 Car lighting ≥ 100 lux @ 1 m above floor level, Ref: 5.4.10 78 Car & counterweight buffer condition
37 Car adequate ventilation 79 Car & counter safety switch, if any
38 Emergency alarm 80 Car & counterweight run-bys
39 Car communication device 81 Tensioning pulley condition & electric safety device
40 Car door reversal device function 82 Bottom clearance & refuge space
Refuge Dim: Upright(0.40x0.50x0.20)m ; Crouching(0.50x0.70x1.0)m &
41 Car door locking & electric safety device 83
Laying(0.70x1.00x0.50)m, Ref: Table 4
42 Car apron, ceiling, panel & sill condition 84 Anti rebound condition

Is the Equipment safe to operate? YES/NO Name & Signature of Company Appointed
Inspector :

Equipment Group Id : Other Equipment Used

ELE/01, REV-07
Doc.No :

Critical Findings

Recommendation (if Any)

Comments (Finding) Target Date

ELE/01, REV-07