You are on page 1of 9

S.

No Parameter Name Tag Nomenclature Units Design Data


1 CHILLER Make / Model CHILLER MAKE
2 CHILLER Type CHILLER TYPE Screw / Centrifugal
Air Cooled / Water Cooled
3 CHILLER Cooling Capacity CHILLER TR TR
4 CHILLER Design Condition CHILLER TEMP DegC
CHILLER dT DegC
CHW RANGE DegC
COW RANGE DegC
5 REFRIGERANT
6 Starter Type DOL / Star-Delta / VFD
7 Compressor Motor Capacity CHILLER KW DESIGN kW
8 Motor Meta Data
9 Compressor Qty
10 Design Approach Temp Evaporator degC
11 Condenser degC
Operating Setpoint
Design delta Temp
Design Chilled water Inlet & Outlet Temp
Design Cooling water Inlet & Outlet Temp
Asset
S.No. Category Asset Type INPUT SENSOR PARAMETERS REQUIRED Source

Flow Flow Meter


Inlet Pressure Control Panel
Chilled Water Inlet temperature Control Panel
Outlet Pressure Control Panel
Outlet Temperature Control Panel
Flow Flow Meter
Inlet Pressure Control Panel
Condenser water Inlet temperature Control Panel
Outlet Pressure Control Panel
Outlet Temperature Control Panel
1 CHILLER Type 1 Evaporator Refrigerant Pressure Control Panel
Refrigerant Temperature Control Panel
Condenser Refrigerant Pressure Control Panel
Refrigerant Temperature Control Panel
Refrigerant Compressor Discharge Temp Control Panel
Compressor Suction Temperature Control Panel
Ambient Temperature Dry Bulb Temperature Control Panel
Wet Bulb Temperature Control Panel
Energy Meter Energy kWh Control Panel
Power kW Control Panel
3 Phase V, I, PF, kW Control Panel

Vibration Vibration DE and NDE Vibration + Temp


Temperature Skin Temperature Vibration + Temp
Tag Nomenclature Type Min Value / Low State Max Value / High State Normal Operating Range

EVA FLOW Integer 0 as per Meta Data as per Meta Data


EVA IP Integer 0 as per Meta Data
EVA IT Integer 0 as per Meta Data
EVA OP Integer 0 as per Meta Data
EVA OT Integer as per Meta Data as per Meta Data
COND FLOW Integer 0 as per Meta Data
COND IP Integer 0 as per Meta Data
COND IT Integer 0 as per Meta Data
COND OP Integer 0 as per Meta Data
COND OT Integer as per Meta Data as per Meta Data
EVA P Integer as per Meta Data
EVA T Integer as per Meta Data
COND P Integer as per Meta Data
COND T Integer as per Meta Data
COMP DT Integer as per Meta Data as per Meta Data
COMP ST Integer as per Meta Data as per Meta Data
DB Temp Integer as per Meta Data
WB Temp Integer as per Meta Data
CHI kWh Integer 0 as per Meta Data
CHI kW Integer 0 as per Meta Data
CHI V, CHO Amp, CHI PF, CHI kW (R,Y,B) Integer 0 as per Meta Data

MOTOR ND X,Y,Z and MOTOR NDE X,Y,Z Integer


MOTOR Temp Integer
Remarks

Detailing to be done for CBM insights


S.No Calculated Parameters / KPI Type Tag Nomenclature

1 CHILLER Evaporator Temperature Difference CALC PARAM CHW DT

2 CHILLER Condensor Temperature Difference CALC PARAM COW DT

3 CHILLER Load CALC PARAM CHILLER TR

4 CHILLER Performance KPI CHILLER kW/TR

5 Evaporator Approach KPI EVAP APP

6 Condenser Approach KPI COND APP

7 CHILLER Performance Comparison KPI

8 CHILLER Motor Loading KPI CHILLER KW%

9 Electrical Signature Analysis (CHILLER Motor) KPI CHILLER MOTOR ESA

10 Chiller COP KPI CHILLER COP


11 Chiller kW KPI CHILLER kW
12 Condensor Water Flow Rate KPI COND FLOW
13 Evaporator Water Flow Rate KPI EVA FOW
14 Cooling Tower Approach KPI CT APP

15 Cooling Tower Effectiveness KPI CT EFFE

KPIs chart
Performance
kW
COP

Chiller Capacity (TR)


Compressor
Pressure
Temperature

Condensor
Condensor water temperature
Condensor Approach
Condensor Water Flow Rate
Condensor Water Delta T

Evaporator
Evaporator Approach
Chilled Water Delta T
Evaporator Water Flow Rate
Chilled Water Temperature

Cooling Tower
Cooling Tower Approach
Cooling Tower Effectiveness

Overall Health Index


Compressor
Evaporator
Condensor
Chiller
Parameters Used Formula Used
CHW IN TEMP
CHW IN TEMP - CHW OUT TEMP
CHW OUT TEMP
COW IN TEMP
COW OUT TEMP - COW IN TEMP
COW OUT TEMP
CHILLER FLOW
CHILLER FLOW X CHW DT / 3.024
CHW DT
CHILLER KW TOT
CHILLER KW TOT / CHILLER TR
CHILLER TR
CHW OUT TEMP
CHW OUT TEMP - EVAP TEMP
EVAP TEMP
COW OUT TEMP
COND TEMP - COW OUT TEMP
COND TEMP
CHILLER KW/TR
CHILLER KW/TR / DESIGN KW/TR
DESIGN KW/TR
CHILLER KW TOT
CHILLER KW TOT / CHILLER DESIGN KW
CHILLER DESIGN KW

CHILLER Motor Voltage &


Current to calculate respective
imbalances

CHILLER kW/TR 3.516/(ikW/TR)


Chi kW
COND FLOW
EVA FOW
COND IT COND IT - WET BULB T
WET BULB T
COND IT (COND OT-COND IR)/((COND OT-COND IT)+(COND IT - WET BULB T))
COND OT
WET BULB T
Remarks

CHILLER FLOW in CMH, CHW DT in degC

Not Applicable for motors with VFD

You might also like