Neutral Voltage Protection - 59GN - 95% Stator Earth Fault Protection
Neutral Voltage Protection - 59GN - 95% Stator Earth Fault Protection
[wp_ad_camp_1]
Neutral Voltage Protection -59GN is also called 95% stator earth fault protection. The
above relay setting protects the generator/alternator’s bus duct, the low-voltage winding
of the step-up transformer associated with the generator and other interconnection with
the stator winding.
https://www.electrical4u.net/alternator/neutral-voltage-protection-59gn-95-stator-earth-fault-protection/ 1/2
9/11/23, 5:43 PM Neutral Voltage Protection -59GN- 95% stator Earth fault protection | Electrical4u
Note: If the earth-fault nearer to the neutral point of the generator will not give sufficient
neutral point voltage to activate the neutral point voltage (95 %) relay 59GN. Therefore
we use 100% stator protection relays which means the stator’s 95% of the winding is
protected by neutral point voltage and the remaining 5% is protected by another relay is
called 27TN. Exactly, (59GN + 27TN)