Wavin SiTech+ is a mineral reinforced polypropylene (PP) soil Quality of living is an important consideration in building
and waste system. The system offers increased robustness, design. A reduction of noise in water discharge systems
low-noise properties and improved ease of installation. improves end-experience in both living and working
environments. Wavin SiTech+ meets the latest construction
Its flexible connectivity and push-fit system makes SiTech+ requirements and fulfills customers’ demand for increased
a complete plug and play solution for waste water discharge comfort and quality.
in buildings.
Easy to install
Better handling during installation due to the grip features. Ribbed fittings provide enhanced
grip for easy installation in complex environments. SiTech+ is perfect for any project, from
small renovations to large-scale construction jobs.
3
1.2. Field of application 1.3. Special fittings
Wavin SiTech+ meets system requirements for soil & waste The Wavin SiTech+ portfolio includes specialized fittings for
discharge systems (EN 1451-1), including noise reduction easier and more efficient installation and use, particularly in
and fire resistance (EN 13501-1). The emitted noise level of areas where space is limited.
SiTech+ is measured by the Stuttgart Fraunhofer Physical
Constructions Institute (DIN EN 14366). Shower branches provide an easy connection of both the
toilet and shower to the down pipe.
Wavin SiTech+ is the ideal solution for installation in multi-
storey building and those that are particularly sensitive to Swept branches, as compared to sharp angle fittings, allow
noise like apartment buildings, hotels, offices, hospitals, water to run more smoothly while reducing overall noise
elderly homes and libraries. levels, improve the ventilation and increase the flow rate.
Wavin SiTech+ can be used for water discharge at tempera The new design of access pipes makes inspection easier.
tures up to 90°C, with peaks of to 95°C for short periods.
It can also be used at low temperatures up to -20°C. This
durability makes it an ideal solution for extreme-temperature
drainage areas such as kitchens, laundromats and industrial
waste environments.
DN/OD
32 mm
40 mm
50 mm
75 mm
90 mm
110 mm
125 mm
160 mm
4
2. Technical datasheet
SiTech+
Range Applications
Wavin SiTech+ offers a complete range of pipes and fittings Wavin SiTech+ is the ideal solution for both residential and
in PP-MD, from 32 mm to 160 mm. non-residential buildings, where customer put more attention
to low-noise properties (hotels, offices, hospitals). Thanks to
Diameter Thickness Socket Length Class
the mineral filled, the system can be even be installed till -20°C
DN/OD mm mm
air temperature.
32 1,8-2,2 43 S16
40 1,8-2,2 45 S16 Certifications
50 1,8-2,2 47 S16
Wavin SiTech+ meets all standards set for soil & waste
75 2,6-3,1 53 S14
discharge systems (EN 1451-1), application EN12056-2,
90 3,1-3,7 57 S14
fire behavior EN13501, and noise protection according to
110 3,4-4,0 64 S16
the Italian Standard D.P.C.M. 05.12.1997. The low noise
125 3,9-4,5 71 S16
performance has been measured at the Fraunhofer Institute in
160 4,9-5,6 76 S16 Stuttgart, according to the EN 14366. Company meets quality
requirements according to ISO 9001, and environmental
Technical Specifications requirements according to ISO 14001.
Working Temperature |
90°C continuous temperature; 95°C peak temperature. Impact resistant
Conformity certification |
PIIP (n°1866 - 1867 - 1868)
DIBT (n° Z-42.1-539)
ITB (n° AT-15-7703).
5
3. Acoustics
6
Fig. 3: FRAUNHOFER Test set up for determination of
the installation sound level in the laboratory.
Pipe
system characteristics
Building
design
Shaft
characteristics
Suspended
ceiling criteria
tructural characteristics of the building
S
Flow
parameters
Installation
requirements
Insulation requirements
7
3.2.1. Wavin SoundCheck tool
With noise regulations continuously being updated, calculating noise levels to ensure your design meets requirements can be a
complex exercise. Wavin’s online SoundCheck Tool is designed to relieve some of that stress.
Unique to Wavin, the SoundCheck Tool simulates system acoustics in a final installation and calculates noise levels based on
individual parameters. In just four clearly defined and intuitive steps, you can get the answers you need to see if your design meets
regulations.
8
3.3. Optimal noise reduction
DIN 4109 (public minimum legal requirement) Volumetric flow rate Meets standard
specification 30 dB(A) 2 l/s 4 l/s
VDI 4100 sound insulation level II / III Volumetric flow rate Meets standard
specification 27 / 24 dB(A) 2 l/s 4 l/s
Wavin Low Noise bracket installation offering sound performance as low as 21 dB(A)* behind the wall according to DIN4109
21 dB(A)
Wavin No Noise bracket installation offering sound performance as low as 13 dB(A)* behind the wall according to DIN 4109
13 dB(A)
* DIN4109 behind the wall with 2,0 l/s Fraunhofer Testreport 62/2019 an 9/2020
9
3.4. About sound The doubling of acoustic power corresponds to an
increase of 3 dB.
Sound is a sensation felt, a perception of what takes place
around us, caused by various compression waves which Every 10 dB increase is perceived by the human ear
cross the eardrum and are captured and transformed by the as twice as loud (10 cars are perceived as twice as loud
brain; it is composed of different frequencies. The acuteness as 1 car).
or intensity of the perception depends on the frequency and
range. 60 dB + 50 dB + 40 dB = 60.5 dB
The highest dB is in a sum the most important
Sound is a wave that is:
Elastic
(it needs a medium to be propagated)
Longitudinal
(perturbation takes place parallel to
the direction of propagation).
1 car = 60 dB
To exist it requires:
A
source (vibrating body)
An
elastic propagation medium (air, water, etc.)
Sound is measured with a phonometer, an instrument which Noise can be described as unwanted sound. In relation to
filters noise and measures intensity at its different frequen- sound, noise is not necessarily random.
cies. It is expressed in decibels.
The decibel is the logarithm of the ratio between the measu- Acoustic noise can be anything from quiet but annoying to
red sound pressure and a reference sound pressure, multip- loud and harmful causing permanent irreversible hearing
lied by ten. damage.
dB = 10 log (P/Pa)
10
Based on the World Health Organization (WHO) guidelines, For instance sleep disturbance: measurable effects of noise
European countries have maximized the noise level (in hou- on sleep begin at sound levels of about 30 dB. However, the
ses, apartments, hospitals, elderly homes, hotels, etc.) during more intense the background noise, the more disturbing is its
the night to: effect on sleep. Sensitive groups mainly include the elderly,
shift workers, people with physical or mental disorders and
LA max night = 30 to 35 dB(A). other individuals who have difficulty sleeping.
Community noise (also called environmental noise, residential Table 1 presents the WHO guideline values arranged accor-
noise or domestic noise) is defined as noise emitted from all ding to specific environments and critical health effects. The
sources except noise at the industrial workplace. guideline values consider all identified adverse health effects
11
for the specific environment. An adverse effect of noise refers Bathroom Bedroom
to any temporary or long-term impairment of physical, psy-
chological or social functioning that is associated with noise
exposure. Specific noise limits have been set for each health
effect, using the lowest noise level that produces an adverse
health effect (i.e. the critical health effect).
<= 30 dB (A)
It is not enough to characterize the noise environment in terms
of noise measures or indices based only on energy sum- points of noise
mation (e.g., LAeq), because different critical health effects propagation
require different descriptions.
12
3.6. Acoustic design Apartment A Apartment B
Noise-sensitive
areas should be kept away, as far as
possible, from sources of noise.
Non-sensitive
areas should, wherever possible, be used
as “buffer zones”.
Noise-sensitive
areas should not be positioned in the
direct vicinity of bathrooms, toilets or stairwells.
Apartment A Apartment B
Potential
sources of noise should be “bundled together”
in the same area.
The comparison between the two examples of layout shown Kitchen Bath
above demonstrates how the acoustically advantageous lay-
out in the second example contributes to a clear reduction
In designing piping, moreover, we need to avoid positioning Room dividing wall Installation in own living room wall
waste pipes in the partition walls between apartments. Special
noise-reduction measures also need to be adopted when
fixing drain pipes to the partition walls between apartments. The comparison of the floor plans above demonstrates how
Protect the pipes from the propagation of intrinsic noise. good acoustic design in the lower building example can
significantly reduce the noise levels to which areas requiring
noise protection are exposed.
Fig. 6: E
xamples of good acoustic practice in building design.
13
3.6.2. Acoustic plumbing design
Wavin SiTech+ shows optimal noise performance. However, When planning pipe installation, waste water discharge pipes
when installing high-performance sound-insulating waste should not be allowed to run inside the walls separating living
water piping systems it is still necessary to consider how areas. The attachment of waste water discharge pipes to
effectively the system can be sound-isolated. This applies to partition walls in living areas should only be carried out under
the waste water discharge system as a whole, including its application of special noise protection measures. DIN 4109
points of contact with the building structure (pipe brackets requires that single-skin walls to which, or in which, water
and clamps, the running wof pipework through walls and installations or equipment (i.e. waste water pipes) are to be
ceilings, mortar droppings between pipes and wall surfaces, attached must have an area-related mass of at least 220 kg/
etc.). sq.m. Walls having an area-related mass of less than 220 kg/
sq.m may only be used where prior testing has demonstrated
that the walls exhibit acceptable properties with respect to the
transmission of noise.
14
4. Installation
and jointing
Wavin has designed its low-noise systems to reduce noise
emissions in concealed and visible installations. However,
to ensure the system is leak-tight and to achieve a high level
of soundproofing it is strongly recommended to follow the
instructions given below.
Fixing
15
4.2. General bracketing rules
Use sound absorbing brackets, dimensionally compatible to To change the bracket from sliding to fixed, a distance washer
the pipe diameter. Screw-pipe brackets with rubber inserts is removed from the bracket before installation. The sliding
are recommended, which are fixed to the wall by screws and and fixed brackets can both be completely tightened until
plastic plugs. the bracket ears touch the distance washers. The distance
washers make sure that in any situation, the clamping force
Sliding Bracket on the pipe is perfect. This results in minimal structure borne
By using sliding brackets, the pipe can still expand and con- sound transmission.
tract due to temperature changes after the screws are tigh-
tened. This make sure longitudinal movement is still possible The distance washers also prevent over-tightening of the
once installed. brackets, which could otherwise result in a reduction of sound
performance.
Fixed bracket Sliding bracket Changing from sliding to fixed: Remove the distance washer.
* removed distance washer * distance washer in place
16
4.2.2. Bracket Arrangement
Vertical pipes:
To prevent the vertical stack sliding down, each pipe section between floors must be secured by
one fixed bracket at the spigot-end.
All remaining pipe brackets at subject pipe must be sliding brackets.
The table 2 prescribing the maximum distance between brackets is to be respected.
Horizontal pipes:
Every horizontally installed pipe length ≥ 2 meters should always be fixed with one fixed bracket at the spigot-end.
All remaining pipe brackets at one pipe must be sliding brackets.
The table 2 prescribing the maximum distance between brackets - is to be respected .
Notes:
For all changes of direction - e.g. a bend at the bottom of a down pipe - 1 bracket directly before and after the change
of direction.
In case multiple fittings are assembled, additional bracket(s) before/after this assembly might be required to ensure:
- A downward slope in flow direction is in place (in case of horizontal pipes).
- The center of the assembly cannot be excessively displaced (in case of vertical pipes).
Ensure the materials are installed tension-free by properly aligning the brackets.
To achieve a high level of sound proofing, generally pipe brackets should not be installed in impact areas
(e.g. diameter reductions and changes of directions in the system).
Pipe brackets to be fixed to building materials with high specific area weight.
In multiple storey buildings (from 3 storeys and more) the stack pipes of 110mm must be secured by additional fixing
(stack pipe support) to prevent sliding. In this case we advise using the Wavin SiTech+ socketed short length with a fixed
bracket.
17
Max distance between brackets
Nominal outer
diameter DN/OD horizontal vertical
(mm) (mm)
50 750 1250
75 1125 1875
90 1350 2000
110 1500 2000
125 1625 2000
160 2000 2000
200 2000 2000
Sliding bracket
Fixed bracket
18
4.2.3. Max length of threaded rod
In the development of Wavin SiTech+ the product has fulfilled Regarding internal pressure it is important to know what the
all testing procedures to ensure high quality. Wavin SiTech+ impact can be in case maximum lengths are exceeded. In
pipes and fittings comply to system tests as specified in case the system gets clogged or otherwise is filled with water,
EN1451-1. Wavin SiTech+ is approved via Type Testing an internal pressure builds up, the resulting forces cause the
(internal) as well as independently tested by accredited testing rods to bend and the joints might be pushed apart till leakage
facilities. occurs.
System requirements for leak tightness are prescribed in The maximum pressure that can occur when the system gets
standards. Wavin SiTech+ is meeting leak-tightness require- clogged is determined by the vertical distance between the
ments as set in the following standards: horizontal line and the lowest sanitary application to which
this horizontal line is connected. In most cases, this distance
EN ISO 1451-1 : leak-tight for 15 minutes with angular is =< 1 meter.
deflection of 2° at 0.5 bar.
Therefore, the maximum lengths of the threaded rods in
EN ISO 13257 : leak-tight for 15 minutes at 0.5 bar when Tables 3a and 3b are such that they can withstand bending
filled after Temperature Cycle Test (1.500 cycles). moments due to 0.1 bar internal pressure.
These requirements do not take into account fixation to a In the following cases, a heavier fixation needs to be applied
wall or ceiling. A proper installation is key to leak-tightness. – especially at changes of direction where resulting forces
A poor installation cannot be compensated by a perfect cause treaded rods to bend – to ensure the system remains
system. Threaded rods are commonly used for suspension leak-tight.
and fixing pipe brackets. It is important to keep in mind that
threaded rods are designed to be used in tension and not to The distance between bracket and wall / ceiling exceeds
withstand bending moments. the maximum lengths as given in the table.
For this reason, threaded rods to be used in SiTech+ installa- The maximum pressure in the system can exceed 0.1 bar
tions have predefined maximum lengths. If the strength class in case of clogging.
is unknown, the maximum length can be retrieved from Table
3a and 3b. These tables were created, based on strength There is a wish to hydrotest the installed system at a
class 4.6. pressure > 0.1 bar.
19
K
DR
Horizontal
Maximum (DR) distance to the ceiling and maximum length (K) of threaded rod or threaded pipe
DR K DR K DR K DR K DR K
DN/OD50 120 85 195 160 315 280 1535 1500 1535 1500
DN/OD75 110 60 170 120 260 210 1300 1250 1550 1500
DN/OD90 105 50 150 95 225 170 1055 1000 1555 1500
DN/OD110 105 40 145 80 205 140 915 850 1565 1500
DN/OD125 100 30 135 60 180 105 725 650 1570 1500
DN/OD160 135 45 175 85 590 500 1590 1500
DN/OD200 150 40 175 70 510 400 1360 1250
Note: for M12 threaded rods, 1/2” and 1” threaded pipes, adapter pieces are needed to connect to brackets.
20
K
DW
Vertical
Maximum (DW) distance to the wall and maximum length (K) of threaded rod or threaded pipe
DW K DW K DW K DW K DW K
Note: for M12 threaded rods, 1/2” and 1” threaded pipes, adapter pieces are needed to connect to brackets.
If the distance from the wall to the pipe is bigger than you can solve with a single threaded rod according to the table 3a and 3b
with the general fixing distances, or in case the internal pressure might exceed 0,1 bar then there are multiple options to increase
the distance.
It is important to know what the impact can be in case maximum lengths are exceeded. In case the system gets clogged, an internal
pressure builds up, the resulting forces cause the rods to bend and the joints might be pushed apart till leakage occurs. In these
cases the following options could be considered:
1. An option could be to consider suspended bracketing for socket support. Bracket assemblies are available for suspended
sanitary and drainage installations in a building.
2. Another option is to use a ‘wall bracket’ to extend the distance between wall and pipe.
3. A third option could be to mount the pipe brackets to a mounting rail, that is installed parallel to the complete installation of
the pipe.
4. A fourth option could be securing the connection via a LKS clamp. The joints at changes of flow direction need to be secured
to prevent them from detaching. The Wavin LKS clamp guarantees this for internal pressures of up to 2 bar.
21
4.3. Low noise installation – bracketing types 4.3.1. Low noise bracketing – single bracket – 21 dB(A)
Low noise installation is all about minimizing the transfer of The low noise installation makes use of a single “Wavin low
sound (vibration) to connecting rooms. Two types of sound noise bracket” that can be used as a sliding and a fixed brac-
can be distinguished; airborne and structure borne sound. ket. The pipe bracket can be changed from sliding to fixed,
Airborne sound is reduced by the mass of the SiTech+ pipe, by removing the distance washer. See 4.2.1. “changing from
and structure borne sound is reduced by low noise bracke- sliding to fixed”
ting. For more information about noise reduction, please refer
to chapter acoustics.
22
4.3.2. No-noise bracketing – double bracket – 13 dB(A)
The no-noise type installation makes use of the same “Wavin low noise bracket”, only difference in this installation is the stacked
installation of the fixed bracket. The sliding bracket is the same as in the Low noise installation (see paragraph 4.2.1.). Each Wavin
low noise bracket contains a rubber inlay that has foam sidewalls. The stacked installation offers further acoustic decoupling, for
increased noise performance. The stacked installation consists of a sliding bracket that is mounted to the wall (not exceeding the
treaded rod distances in table 3) and a fixed bracket that is mounted to the pipe. In final installed form, the fixed bracket is carried
by the sliding bracket.
In the no-noise installation, the distance washers make sure that in any situation, the clamping force on the pipe is perfect. This
results in minimal structure borne sound transmission. The distance washers also prevent over-tightening of the brackets, which
could otherwise result in a reduction of sound performance.
23
4.4. Floor and ceilings crossings
Shower branch
24
Pressure surges may occur in any part of systems located
downstream of pumps and pump stations. All fittings should
therefore be secured using LKS clamps. Ensure that the
fixings used are able to withstand such pressure surges. The
system must be able to transfer dynamic loads to the sup-
porting structure.
25
Alternatively, the use of one extended 45° bend and one nor-
mal 45° bend is recommended. The waste water pipes should
likewise be dimensioned and installed in such a way that
allows air to circulate freely around the water being drained.
Pipe clamps designed to comply with noise-prevention requi-
rements must be fitted with a suitable rubber insert. In the
case of bricked-up pipes, note that these must be secured to
the underlying structure and not to the new brickwork. Wall
and ceiling penetrations must be flexible.
25
cm
26
Repairs using repair couplers
If a pipe section needs to be replaced 3. Install the free half of the coupler 6. Install as close as possible to the
or a branch needs to be added to the onto the existing pipe and slide two pipe ends wall plates for the
pipe system, please follow the the repair coupler completely over fixed-point brackets and mount
following procedure. the existing pipe. the threaded rod and back part
of the brackets. When fixating
1. Cut out the part which needs to be the repair couplers with tensile
replaced. When inserting a branch resistant clamps this step can be
at a later stage, please secure that skipped.
the level of the branch is located
at the right height. The Z1 value is 7. Install a tensile resistant clamp on
mentioned for each branch in the each repair coupler to ensure no
product overview. movement.
27
Repairs using a long socket and repair coupler
8. Finalise the installation of the 1. When inserting a branch at a later When replacing a piece of pipe,
fixed-point brackets or install a stage, please secure that the secure that the total length of the
tensile resistant clamp on each level of the branch is located at new socketed pipe (L) equals the
repair coupler to ensure no the right height. The Z1 value is length of the part cut out minus
movement. mentioned for each Branch in the the length of the spigot of the
product overview. branch (Q) minus 20 mm.
Fixed point
bracket
Tensile resistant
clamp
28
4. Install a short piece of temporary pipe halfway onto 7. Push the socketed of the branch or pipe on
the repair coupler to secure a correct positioning of to the long socket.
the rubber seal.
29
11. Slide the repair coupler over the 12. Finalise the installation of the fixed-point
spigot end of the branch or to the bracket or install a tensile resistant clamp on
marking on the pipe. the repair socket to ensure no movement.
Tensile
resistant
clamp
Fixed point
bracket
Fixed point
bracket
Tensile
resistant
clamp
30
5. Fire protection
Fire behavior of construction materials, e.g. piping systems and isolation materials, have been defined in fire classification classes
as per DIN 4102-1. Construction materials are classified as combustible and non-combustible materials. According to EN 13501-1,
PP, and thus Wavin SiTech+ is listed as Class C-s2, d0 according to EN13501-1.
Non-combustible A1 A1 - -
A2 A2 s1 d0
Non-readily ignitable B1 B s1 d0
(low flame spread) C s1 d0
A2 s2/s3 d0
B s2/s3 d0
C s2/s3 d0
A2 s1 d1/d2
B s1 d1/d1
C s1 d1/d2
A2 s3 d2
B s3 d2
C s3 d2
Readily ignitable B3 F - -
Table 4: Fire behavior classification according to DIN 4102-1 and DIN EN 13501-1.
In line with European standardization, the fire classification Fire resistance Fire resistance
classes as per DIN 4102-1 are translated into the European classification duration in minutes
DIN EN 13501. The accreditation is based on the standar
dized Singl-burning-Item-Test (SBI) in conformity with DIN F30 ≥ 30 = fire retardant
EN 13823. F60 ≥ 60 = high fire retardant
F90 ≥ 90 = fire resistant
5.2. Fire resistance classification F120 ≥ 120 = high fire resistant
F180 ≥ 180 = extreme fire resistant
The fire resistance classification provides the fire resistance
duration of a specific construction material.
31
Possible additions to these fire resistance classes, e.g. z.B. 5.4. Assembly instructions
F90 A or F90 AB, can be explained as follows:
When the system is applied to a fire-resistant vertical (wall)
A made of non-combustible materials or horizontal installation (floor) which separated a fire-risk
B made of combustible materials area, only one Fire Protection collar is required. If the system
AB in principle made of non-combustible materials is applied to a fire resistant vertical (wall) or horizontal (floor)
installation which separated two fire-risk areas, use a Fire
5.3. Wavin fire protection concept Protection collar on both sides.
For
wall and ceiling crossings
Suitable
for pipes with or without sockets and fittings
Also
suitable for angled passages (up to 45 degrees)
Approved
for ceiling installation
Fire
classification F90
32
Closing and sealing against fumes and gas General recommendations
If there are any gaps between the pipe and the wall, seal these
using putty or intumescent strips according to the thickness, (1) Positioning of the collars:
to prevent the passage of fumes in the event of a fire. On both sides of a wall; on one side under/in a ceiling.
150 mm
Acoustic insulation mat
NB: the fire protection collar can only prevent the passage of
fire if it is properly installed
BM-R90 collar
Precautions
In the case of contact of the intumescent material with the
eyes, wash delicately with soap and water. Keep out of the
reach of children.
Installation manual Wavin Fig. 17: Straight installation with / without sleeve / socket.
fire protection collar BM-R90
Wavin BM-R90 is a new fire protection sleeve designed for (2) Wall & ceiling types:
use with Wavin domestic waste water removal piping systems At least 10 cm thick solid concrete, aerated concrete and
according to DIN 4102-11. It is suitable for use on piping with sand-lime brick walls as well as light dividing walls (stud
external diameters of up to 200 mm and is able to provide a walls: both sides clad with 12.5 mm plasterboard) and solid
secure seal for use in all conceivable installation situations: concrete and aerated concrete ceilings at least 15 cm thick.
Right-angled
wall and ceiling penetration (3) Structural acoustic insulation:
Lightly-constructed
partition walls The acoustic insulation mat provided must be wrapped
Angled
wall and ceiling penetration to 45˚ around the pipe where it passes through the wall or ceiling.
For
sealing over pipe collars (to 45˚)
For
installation under ceilings and in front of walls (4) Joint sealing between pipe and wall/ceiling:
Installation
flush with ceiling surface To be packed to the full thickness of the wall or ceiling using
mineral materials such as concrete, cement or plaster.
BM-R90 installation instruction
The BM-R90 fire collar provides fire resistant sealing for wall
and ceiling installation of SiTech+ and other selected Wavin
soil and waste systems.
33
Components Types of installation
The fire collars are made from powder coated sheet steel I. Ceiling installation
with a push-in fastening and tab fixings with an integrated
intumescent material for reliable closure in the event of fire. Minimum requirements of the ceiling: min. 150 mm thick
Also included: concrete ceiling.
Insulation
mat Flush ceiling installation
Fixing
kit Wrap insulating mat around the pipe.
Identification
label Open the collar and position it around the pipe, whilst hooking
in the push-in fastening. Bend or angle the collar mounting
tabs. Then install the collar flush with the ceiling. Fill the
Selection table remaining ceiling gap with cement or concrete (see general
recommendations (4)).
Wavin d s straight straight angled
SiTech+ mm mm installation installation installation 1)
pipes with collar with sleeve or
DN/OD socket ≤ 45º mm
gap around the edge
32 32 2,.0 32 40 50
40 40 2.0 40 50 63
50 50 2.1 50 63 75
150 mm
75 75 2.6 75 90 110
Acoustic insulation mat
90 90 3.1 90 110 125
¹) The shape of the sleeve must be turned oval by pushing Fig. 20: S
traight installation without sleeve / socket
on both sides. In that way the shape of the collar can be up to 160 mm.
adapted when leading-through the pipes (see also figure
below)
II. Installation under the ceiling
Table 6: B
M-R90 selection table for various types of
Wavin SiTech+ pipe installation. Straight ceiling installation
Wrap insulating mat around the pipe. Open the collar and
position it around the pipe, whilst hooking in the push-in
fastening. Fill the remaining gap with cement or concrete (see
general recommendations (4)). Hold the collar firmly against
the ceiling and mark the positions of the mounting holes.
34
gap around the edge
gap around the edge
150 mm
Acoustic insulation mat
Acoustic insulation mat
BM-R90 collar
BMR-90 collar
Fig. 21: Straight installation with / without sleeve / socket. Fig. 22: A
ngled ceiling installation ≤ 45º with / without sleeve
socket.
Rotate the collar and drill the holes. If two Wavin BM-R90 feedthroughs are installed next to each
other, the distance between the pipes must be at least 100
Insert plugs and fix the collar using screws and washers. mm in the case of special partitioned sections (sloping pipes,
(Mounting the collar using the washers, plugs and screws partition via sleeve/socket or for ceiling installations). In the
provided). case of straight pipes without sleeve/ socket in the partition
area, the collar casings can adjoin each other (distance 0 mm).
Angled ceiling installation
III. Wall installation
Wrap insulating mat around the pipe.
Minimum wall specifications: wall must be at least 100 mm
Open the collar and position it around the pipe, whilst hooking thick, made from concrete, aerated concrete, lime sandstone
in the push-in fastening. Fill the remaining gap with cement or or lightweight partition walls (two-layer panelling on both
concrete (see general recommendations (4)). sides with 12.5 mm plasterboard panels and mineral wool
infill). The pipe must be clamped on both sides at a distance
Hold the collar firmly against the ceiling and mark the of ≤ 50 cm. For wall feedthroughs, a collar should always be
positions of the mounting holes. fitted on both sides of the wall.
Rotate the collar and drill the holes. Wrap insulating mat around the pipe. Open the collar and
position it around the pipe, whilst hooking in the push-in
Insert plugs and fix the collar using screws and washers. fastening. Fill the remaining gap with cement or concrete (see
(Mounting the collar using the washers, plugs and screws general recommendations (4)). Hold the collar firmly against
provided). the ceiling and mark the positions of the mounting holes.
Rotate the collar and drill holes.
Installation distances between BM-R90 fire protection
collars eg to external systems Insert plugs and fix the collar using screws and washers.
(Mounting the collar using the washers, plugs and screws
The distance to external, tested systems (inspected and provided).
approved) must be at least 50 mm between partitioned
sections. Repeat the steps described for the second collar required on
the opposite side.
35
2 x 12,5mm plasterboard
Acoustic insulation mat
The distance to external, tested systems (inspected and
approved) must be at least 50 mm between partitioned sec-
tions.
100 mm
100 mm
Fig. 25: 4
5° angled installation with / without sleeve / socket.
36
6. P
acking, transport
& storage
Handling
Maximum height:
1.5 meter
Maximum spacing:
1 meter
Support bar width: 75 mm
37
Wavin SiTech+
Product range
38
7. W
avin SiTech+
Product range
SiTech+ Pipe STEM S/PL
39
Wavin SiTech+
Product range
Diameter Article code Do1=Ds2 Z1
40
SiTech+ Bend STB 15°
32 3067708 32 49 8
40 3067709 40 52 8
50 3067710 50 55 9
75 3067711 75 63 13
90 3067712 90 69 15
110 3067713 110 79 16
125 3067714 125 88 20
160 3067715 160 97 25
32 3067716 32 51 10
40 3067717 40 55 11
50 3067718 50 58 13
75 3067719 75 68 18
90 3067720 90 76 22
110 3067721 110 88 24
125 3067722 125 96 29
160 3067723 160 109 36
32 3067724 32 54 13
40 3067725 40 56 15
50 3067726 50 65 17
75 3067727 75 75 22
90 3067728 90 85 26
110 3067729 110 96 33
125 3067730 125 105 38
160 3067731 160 121 48
41
Wavin SiTech+
Product range
SiTech+ Bend STB 67,5°
32 3067732 32 58 17
40 3067733 40 63 20
50 3067734 50 70 21
75 3067735 75 84 34
90 3067736 90 95 41
110 3067737 110 108 47
125 3067738 125 123 55
32 3067739 32 62 21
40 3067740 40 68 26
50 3067741 50 78 31
75 3067742 75 95 45
90 3067743 90 108 54
110 3067744 110 128 64
125 3067745 125 141 74
160 3067746 160 166 94
42
SiTech+ Branch STEA 45°
32x32 3067747 32 32 54 42 42
40x32 3067748 40 32 58 81 52
40x40 3067749 40 40 58 52 52
50x40 3067750 50 40 55 59 57
50x50 3067751 50 50 64 71 71
75x50 3067752 75 50 56 82 77
75x75 3067753 75 75 74 96 96
90x40 3076499 90 40 46 95 86
90x50 3067754 90 50 56 106 96
90x75 3067755 90 75 77 141 121
90x90 3067756 90 90 83 115 115
110x40 3076498 110 40 52 95 85
110x50 3067757 110 50 63 105 93
110x75 3067758 110 75 71 122 113
110x90 3067759 110 90 82 129 124
110x110 3067760 110 110 108 138 138
125x75 3067761 125 75 70 133 121
125x110 3067762 125 110 95 149 146
125x125 3067763 125 125 106 156 156
160x110 3067764 160 110 82 175 164
160x160 3067765 160 160 120 200 200
50x50 3067766 50 50 69 40 40
75x50 3067767 75 50 70 55 46
90x90 3067768 90 90 94 70 70
110x50 3067769 110 50 77 76 54
110x75 3067770 110 75 101 147 96
110x110 3067771 110 110 87 87 68
43
Wavin SiTech+
Product range
SiTech+ Branch STEA 87,5°
40x40 3067772 40 40 69 28 28
50x40 3067773 50 40 71 33 28
50x50 3067774 50 50 82 35 36
75x50 3067775 75 50 82 45 35
75x75 3067776 75 75 95 49 49
90x50 3067777 90 50 87 53 36
110x50 3067778 110 50 96 63 37
110x75 3067779 110 75 135 66 52
125x110 3067780 125 110 133 77 71
125x125 3067781 125 125 141 80 79
160x110 3067782 160 110 165 103 103
160x160 3067783 160 160 165 111 101
44
SiTech+ Double Branch STDA 87,5°
75x50x50 3067832 75 50 80 45 35
90x90x90 3075996 90 90 125 125 55
110x110x110 3067838 110 110 144 143 64
90x90x50 3071186 90 50 91 96 53 74 52
90x90x50 Left 3076751 90 50 91 96 53 74 52
90x90x50 Right 3076752 90 50 91 96 53 74 52
110x110x50 3071187 110 50 111 96 63 79 64
110x110x50 Left 3076749 110 50 111 96 63 79 64
110x110x50 Right 3076750 110 50 111 96 63 79 64
45
Wavin SiTech+
Product range
SiTech+ Access pipe STRE
50 3067784 50 83 50 36 80 65
75 3067785 75 102 75 50 111 93
90 3067786 90 118 90 60 132 110
110 3067787 110 135 110 72 155 128
125 3067788 125 142 125 74 162 146
160 3074215 160 200 160 121 236 141
40 3067790 40
50 3067791 50
75 3067792 75
90 3067793 90
110 3067794 110
125 3067795 125
160 3067796 160
32 3067797 32
40 3067798 40
50 3067799 50
75 3067800 75
90 3067801 90
110 3067802 110
125 3067803 125
160 3067804 160
SiTech+ Floorgully
46
SiTech+ Double Long Socket STLL
40 3074798 40 50 53
50 3074809 50 52 56
75 3074810 75 59 64
90 3085677 90 63 70
110 3067809 110 152 79
125 3074812 125 171 91
160 3074813 160 187 99
40x32 3067812 40 32 60 3
50x32 3067813 50 32 66 9
50x40 3067814 50 40 63 5
75x50 3067815 75 50 77 12
110x50 3067816 110 50 106 27
110x75 3067817 110 75 98 17
125x110 3067818 125 110 98 7
160x110 3067819 160 110 121 24
160x125 3067820 160 125 117 16
90x50 3067821 90 50 27 17
90x75 3067822 90 75 22 4
110x50 3076497 110 50 23 7
110x75 3076496 110 75 24 9
110x90 3067823 110 90 26 6
SiTech+ PP Reducer
940x32 3072601 40 32 65
50x40 3080421 50 40 55
47
Wavin SiTech+
Product range
SiTech+ Endcap STM
32 3080961 32 45
40 3067824 40 47,5
50 3067825 50 48,5
75 3067826 75 54,5
90 3067827 90 37,4
110 3067828 110 69,5
125 3067829 125 69
160 3067830 160 98,2
32/46 3067841 32 46 70 24
40/46 3078802 40 46 79 30
50/53 3078803 50 53 79 35
40/46 prolonged 3078804 40 46 125 30
32/46 3067843 32 46 52
40/46 3067844 40 46 54
50/53 3067845 50 53 55
48
Rubber for Traps
Gasket
32 4029792
40 4029793
50 4025545
75 4025784
90 4024428
110 4029796
125 4024430
160 4029798
32 4066447
40 4066448
50 4066449
75 4066450
90 4066451
110 4066452
125 4066453
160 4066454
49
Wavin SiTech+
Product range
Firecollar BM-R90
32 4059802
40 4026101
50 4026102
63 4026103
75 4026104
90 4026105
110 4026106
125 4026107
140 4026108
160 4026109
180 4026110
200 4026111
32 4048918
40 4048917
50 4065138
70 4065139
90 4065140
110 4065141
125 4065142
160 4065143
50
Notes
51
Discover our broad portfolio at wavin.com
Hot & Cold Water Foul Water Gas & Water Mains
Indoor Climate Storm Water Geotextiles
Soil & Waste
Wavin B.V. P.O. Box 173 | 8000 AD Zwolle | The Netherlands | Phone +31 (0)38 - 429 49 11
Internet www.wavin.com | E-mail info@wavin.com
Wavin operates a programme of continuous product development, and therefore reserves the right to modify or amend the specification of
their products without notice. All information in this publication is given in good faith, and believed to be correct at the time of going to press.
However, no responsibility can be accepted for any errors, omissions or incorrect assumptions.
2020-12
© 2020 Wavin Wavin reserves the right to make alterations without prior notice. Due to continuous product development, changes in