Not found in LCC terminal arrangement

C2
Based on RTCC terminal
arrangement, SAU pull 4 cable from
terminal X3:1-4
With total terminal is 5

But based on wiring SAU pull from


RTCC X3: 2-6
There are terminal no. 6 on wiring,
which not available in the RTCC
terminal arrangement

Kindly confirm

Not found in LCC terminal arrangement

Kindly clarify
The connection between LCC
to K20 (OTI) and K27,K28
(WTI) are ABB scope?

Based on LCC Terminal


Arrangement, SAU only pull 3
cable from terminal X3:1-3

But based on wiring SAU pull


from LCC X3: 2,3,10/11,12

Kindly confirm

F2
Is the numbering should be
like this?

23 24 25 26 27 28 29

I do not find terminal X4


and X9 in RTCC terminal
arrangement
From the cable number, X4
in RTCC are X13, however
the terminal number still not
match with the wiring
I do not find terminal X5
in RTCC terminal Kindly confirm
arrangement

For example, cable from


+B1 (X4:19) LCC are going
to terminal X13 :34, while in
the wiring in this page it
should be go to X9:8
Is the numbering should be like this?
I do not find the terminal X4
or the cable number for this
connection in terminal
23 24 25 26 27 28 29
arrangement RTCC
In the terminal arrangement RTCC, we can see that
terminal RTCC X6:2-10 each are wired to terminal LCC
X6: 2-10 (Except LCC X6:7B)

While as per drawing the 110 VDC should be only come


X6 : 2 X6 : 3 X6 : 4 X6 : 5 X6 : 6 X6 : 7 X6 : 8 X6 : 9 X6 : 10 from RTCC X2:5

Meanwhile the RTCC X6: 1-10 are all connected, i cannot


find the source for RTCC X6:1 (It is said from +B1(X7:1),
but i could not find it in the drawing)

Please clarify

30 31 31B 32 33 33B 34 35

X41:26 X41:22 X41:24 X41:25 X41:27

The terminal arrangement from LCC


does not match with RTCC terminal
arrangement

Drawing from terminal arrangement


RTCC X6, terminal no 21-30 are
connected.
Also in the RTCC terminal number
23 are not used

Kindly clarify
In the LCC terminal, X6:35-48 are
not wired with RTCC. Meanwhile in
the drawing it should be connected
X6:38
X6:39
X6:40
X6:41
X6:42
+B3(X6:43)

However in the RTCC terminal, this


This is LCC Terminal, it does not cable number does not match the
match with the wiring LCC terminal
Terminal no X71: 61-66 are not found
What is the difference between Fan
Position and Fan Control?

It should be 24
Please confirm
Are 2 different source of 110 VDC
necessary?