Professional Documents
Culture Documents
Air in
two-par t
series
Concrete:
By Ken Hover
How Come and How Much?
compressive strength by 200 to 300 psi, keys to making concrete resistant to
and density drops by about 1%. damage from freezing and thawing of
As air content increases, paste con- associated with entrained water pushed ahead of
tent, aggregate content, or both have to air, you need a com- it) can squeeze into empty
decrease, and since paste, stone, and pelling reason to use it. Air voids in hardened concrete air voids. As long as the
sand are all stronger and denser than That compelling reason vary over a wide range of sizes, distance that ice and
air, a 1% increase in air content lowers is that air is one of the with 5 to 15 billion voids per water have to travel to
cubic yard. In typical freeze/thaw
resistant concrete, no point in the
paste should be farther than
0.008 to 0.010 inch from the
nearest air void.
get to the nearest air void is no more
than 1⁄ 100 inch, most concretes can tol-
erate the freezing pressures. All else being
equal, the shorter the travel distance Ta b l e 4 . 2 . 1 — To t a l a i r c o n t e n t f o r
(“the spacing factor”), the lower the frost-resistant concrete*
freezing pressure; so if 1⁄ 100 inch is good
for most concretes, 8⁄ 1000 inch is better. Nominal maximum Air content, as a percentage of
To space the bubbles close enough aggregate size, in inches. total concrete volume.
to control the freezing pressure requires Severe exposure Moderate exposure
a large number of microscopically small 3⁄ 8 7.5 6
bubbles. Unfortunately the air bubbles 1⁄ 2
in air-entrained concrete vary from the 7 5.5
3⁄4 6 5
size of cement grains to the size of coarse
aggregate particles, with an average ra- 1 6 4.5
dius in the range of 3 to 6 thousandths 11⁄ 2 5.5 4.5
of an inch (3 to 6 mils). 2 5 4
To know if the bubbles are close 3 4.5 3.5
enough in the hardened paste, you have * From ACI 318-02 Building Code for Structural Concrete, Section 4.2.1
to know how many bubbles you have.
To do that you need to know their total to the paste content, the total volume ■ Degree of saturation
volume and their average size. Volume of air should therefore be about 9% of ■ Presence of de-icing salts
we know, more or less, from standard the total mortar volume, and this is the ■ Geometry of the concrete mem-
air tests. Size we know only from mi- basis for the air contents required in ber, and
croscopic surveys of hardened concrete Table 4.2.1 of the ACI Building Code. ■ Tensile and compressive strength
or from nonstandard tests of fresh con- The table shows the required air con- of the concrete
crete. In some cases the specifier will re- tent for the severity of exposure and Usually we don’t know all of these
quire that tests be performed to evalu- nominal maximum aggregate size, re- factors in detail, but we also lack a re-
ate the average size of the air voids (using flecting the fact that mixes with larger liable way to take them all into account.
the ASTM C457 test method). Most of coarse aggregate particles usually re- The experience-based values in the table
the time, though, we just control the mix quire less water, cement, and sand, and cannot account for the specifics of all
on the basis of total air volume, with therefore have a lower mortar and air mixes, materials, and environments.
the amount required based on experi- content. (Smaller aggregates are not in- This means that meeting the code re-
ence, and with fingers crossed that the herently less durable than larger ag- quirements generally leads to durable
average bubble size will be small enough. gregates.) These code requirements are concrete, but not meeting the same re-
The total volume of air voids in minimum values and would not nor- quirements does not always mean that
the hardened concrete should be about mally be reduced in construction spec- the concrete will lack durability.
18% to 20% of the volume of the paste. ifications for projects in moderate or Furthermore, the question of com-
When the sand content is about equal severe freeze/thaw environments. pensating for air losses from the han-
But, is it a good idea to increase dling of the concrete is critical but not
these values in specifications to either necessarily new. What is new is increased
achieve more freeze/thaw protection or attention to testing air at the point of
to compensate for the normal and in- placement, and what we’ve found is
evitable losses in air volume that will that dropping, shaking, squeezing, and
result from placing, vibrating, and fin- vibrating concrete normally results in
ishing the concrete? This is an impor- a loss of air volume. One of life’s little
tant and complicated question. To an- compensations, however, is that the
swer it we must be realistic about our larger, and therefore less effective, air
inability to predict precisely the re- bubbles are most likely to be lost first,
quirements for freeze/thaw durability leaving the smaller and more effective
Schematic diagrams of two air-void sys- for a specific concrete in a specific en- air bubbles in the concrete.
tems that provide approximately equiva- vironment. Exactly how many voids are What makes this a balancing act is
lent protection against freezing and thaw- needed, what size, and how far apart that durability suffers when air content
ing. The air voids are the yellow circles, they are depend on several things: is too low, and strength and finisha-
and the black circles represent the zone ■ Number of freeze/thaw cycles bility can suffer when air content is too
of paste protected by a given air void. the concrete has to endure high. (Increasing air by 1% has about
On the left is a mix with 4 1 ⁄ 2% air and ■ Rate of freezing and duration of the same strength-reducing potential as
average bubble radius of 5 ⁄ 1000 inch. On below-freezing temperature adding 2 gallons of water per yard.
the right is 20% air and average bubble ■ Porosity and permeability of the Compensating for this requires a ce-
radius of 10 ⁄ 1000 inch. paste ment addition of around 35 to 45 pounds
■ Volume of the paste per yard.) Some specifiers solve this
problem by giving priority to freeze/thaw
durability, with far less emphasis on
strength. High air contents are the rule
for these specifiers, and high strength
acceptance criteria and steel trowel fin-
ishes are the exceptions.
Despite these complications, the
code requirements are somewhat con-
servative. The tolerance of ±11⁄ 2%, along
with the option of a 1% reduction when
f´c exceeds 5000 psi, is evidence of that
conservatism. (The Portland Cement
Association has recently reconfirmed
the reasonableness of these provisions.)
More good news is that the table val-
ues are based on 9% air content in mor-
tar for mixtures with water and cement
contents not reduced by water reduc-
ers, pozzolans, or blended aggregates.
When paste volume is decreased, so is
the volume of air needed for frost re-
sistance, and this can give us a bit of
playing room when it comes to air re-
quirements for modern mixes.
To explore this in more detail, re- Total air content required to achieve spacing factor of 0.008 inch for concrete
member that when it comes to air voids when w-c = 0.45 and average air bubble sizes shown. The value “alpha” is
and frost protection, what really mat- often used instead of radius to describe bubble size and is like the Fineness
ters is how far apart the air voids are, Moduluis for sand except that higher values of alpha mean smaller bubbles.
and this depends on the number, size,
and total volume of the bubbles rela- air-void radius were 5 mils. We could achieve frost resistance at 4%
tive to the paste volume—not to the hardened air if the average bubble size were about 41⁄ 2 mils, as is fully
concrete volume. What matters most possible with modern air-entraining admixtures. As long as the 4%
are these characteristics in the hardened air that remained in the hardened concrete was fine enough, this con-
concrete—not in the fresh concrete. The crete could sustain a 2% air loss during handling, from 6% at the
graph on page 60 shows the combined truck, and not jeopardize durability. If the air content had been in-
effect of bubble size and paste content creased to 8% in anticipation of a 2% loss, the strength could have
required to achieve a spacing factor of dropped by 500 psi or more.
0.008 inch in a mixture with a water- Air is almost always lost in the processes of placing, vibrating, and
cement ratio of 0.45. As water content finishing, and for many years the ACI 318 requirements have been gen-
is reduced (such as by water reducers erally satisfactory when air has been measured at the truck only. There-
or by improved aggregate grading) and fore, it is apparent that using these as required values at the chute prior
as bubble size decreases, the required to experiencing a 11⁄ 2% to 2% loss of the larger air bubbles has gener-
total air content decreases as well. ally worked. It may be necessary, however, to target higher values when
Let’s take the example of a mix- anticipated losses are greater or when construction operations selectively
ture with a 3⁄4-inch coarse aggregate remove the finer bubbles. Getting a handle on these situations will be
in a severe environment. For these con- discussed next month. ■
ditions the 318 Code requires a max-
imum w-c of 0.45 and a minimum air
content of 6%. ACI 211.1 (Mix Pro-
portioning) suggests a water require-
ment of about 305 pounds of water
per cubic yard for a 3- to 4-inch slump.
If, by using admixtures and aggregate
blending, we were able to reduce this
water content by 10% to 275 lb/CY,
we could develop adequate freeze/thaw
durability at an air content in the hard-
ened concrete of 5% if the average