Professional Documents
Culture Documents
Test Device: Excitation
Test Device: Excitation
Overall assessement OK
Asset
Ipn 300.0 A Object Location
Isn 5.0 A Manufacturer ALCE Company KAHRAMAA
Rated burden 60.0 VA /1.00 ? Type 4MA72-PL AYC Country QATAR
Operating burden 60.0 VA /1.00 ? Serial number 2022-1004059591 Station 39631
Standard IEC 61869-2 Core 1S1-1S2 Feeder P9
Application Protection Tap Phase B
Class PX Optional 300-B IEC-ID
Frequency 50.0 Hz Comment
Rct max 0.312 Ω ?
Kx 16.93 ?
Ek 215.00 V Ie 0.0684 A ?
E1 107.50 V ? Ie1 0.0339 A ?
Burden
Burden cos φ: Z
V-meas I-meas
Excitation
Ls 0.001384 H Lm 11.028773 H Results at rated burden (60.00 VA) Results at operating burden (60.00 VA)
Kr 93.54 % Kx 16.93 Kx 16.93
Standard IEC 61869-2 Ts 4.066 s Ts 4.066 s
V-kn 229.648 V I-kn 0.0778 A
Ek OK
Ie OK Ie 0.0778 A
Ie1 OK Ie1 0.0339 A
Ratio
Turns ratio 59.9997 Results at rated burden (60.00 VA) Results at operating burden (60.00 VA)
εt -0.0005 % Ratio 300.0 : 4.995 Ratio 300.0 : 4.995
Polarity OK ε -0.1007 % ∆φ 3.28 min ε -0.1007 % ∆φ 3.28 min
εc 0.1386 % εc 0.1386 %
Residual magnetism
Residual flux
Residual magnetism
Excitation
1000.00
100.00
X1_X2_1
Rectified voltage
10.00
1.00
0.010
0.000 0.001 0.010 0.100 1.00 10.00
RMS current
1/2
0.010
0.000 0.001 0.010 0.100 1.00 10.00
RMS current
Current ratio error in % at % of rated current
VA/cos φ 1.00 % 5.00 % 10.00 % 20.00 % 50.00 % 100.00 % 120.00 % 200.00 %
-0.1
30.000 VA
-0.2
Current ratio error [%]
-0.3
15.000 VA
-0.4
-0.5
7.500 VA
-0.6
0.00 50.00 100.00 150.00 200.00 250.00
I/Ipn [%]
30
25
Phase [min]
30.000 VA
20
15
15.000 VA
10
5
7.500 VA
0
0.00 50.00 100.00 150.00 200.00 250.00
I/Ipn [%]
2/2