Preliminary Estimate

Name of Work- Retrofitting of Transplant OT and ICU in package 2 (Hospital Building)

Part 'A' BONE MARROW TRANSPLANT

MR S.N. Description UNIT QTY. Rate Total

SITC of air handling unit with thermal break frame structure


injected with minimum 48 mm thick 40 kg/m3 PUF insulation; GI
Panel shall be powder coated from both inner and outer side Fan
MR A1 section with BC fan , HEPA FILTER (MERV-17) ,Connected with NO. 1 #REF! #REF!
fire resistant flexible outlet connection, Motor selection (IE-3) to
suit the below capacity 125mm static. 8500 CFM

SITC of air cooled Condensing unit


following capacity with scroll compressor of suitable for
operation on 3 phase 415 V, 50 Hz AC supply. The condenser coil
in Cu tubes and aluminums, construction and first charge with
MR A2 refrigerant R-410a. The indoor should be complete with fan, fan NO. 1 #REF! #REF!
motor, copper tube, aluminum finned cooling coil, drain pan,
micron filter (washable) and microprocessor controller.11 TR

REFRIGERANT PIPING
Supply & fixing of interconnecting copper refrigerant pipe work
MR A3 duly insulated with elastomeric nitrile rubber for Copper piping NO. 1 #REF! #REF!
for Condensing unit.

DRAIN PIPING
MR A4 Providing and fixing of UPVC drain water piping complete with kg 1300 #REF! #REF!
6mm thick nitrile insulation. 32 mm dia ID

CONTROL CABLING
Supply and laying, testing & commissioning of following sizes of
MR A5 Copper conductor control cables effecting proper connections to No. 1 #REF! #REF!
equipment etc. complete as required.

i 3C x 1.5 Sq. mm

ii 4C x 1.5 Sq. mm

iii 4C x 16 Sq. mm

AIR DISTRIBUTION SYSTEM


MR A6 Supply and fabrication of site fabricated GSS Ducting for supply sqm. 200 1229 245800
air complete with all fittings ancillary material
i 24 Gauge
ii 22 Gauge

ACOSUTIC INSULATION
Supply & Fixing of Accoustic insulation to control the noise and
MR A7 vibration in the first piece of Ducts with 13 mm thick open cell sqm. 25 7046 176150
nitrile rubber insulation Class "1" fire retardant with alluminium
coted.
THERMAL INSULATION
MR A8 Supply & fixing of thermal insulation over the ducts for avoiding
condensation and to prevent heat loss complete with all
necessary accessories. Nitrile rubber insulation Thickness 19 mm
MR A9 ALUMINIUM GRILLS
Supply & Fixing of Alumiunm Powder coated supply air
FLEXIBLE CONNECTIONS
MR A10 Providing & fixing of flexible canvas connection between indoor
unit and duct to avoid the vibration transfer.
Control Valve Fitting For Refrigerant
MR A11 Controls such as filter drier, expansion valves, thermostat, pilot
solonate, Shutoff Valve.
MR A12 Stand For Outdoor Unit
MR A13 Duct Heater 6K.W with RH Control Pannel
MR A14 Control panel
Electrical control Pannel for AHU and Condenser Unit
VOLUME CONTROL DAMPER
MR A15 Powder coated extruded aluminum Square Diffuser with volume
control damper complete as required.
MR A16 SITC of differential pressure gauge
MR A17 SITC of Hygrometer

Part 'B' TRANSPLANT OT


PIPE:
Refrigerant piping

HEPA FILTERS:
Hepa Filters with Pleanum

DRAIN PIPE:
Supply & Installation of Drain Piping of requisite quantity 40 mm UPVC

AIR DISTRIBUTION SYSTEM:


Supply, installation, balancing and commissioning of Site fabricated SS sheet metalrectangular/round ducts of
following thickness including RTV Sealent necessary supports, hangers, nut & bolts, neoprene rubber gaskets, splitter
dampers, also Air balancing / Air Adjustement as per design requirements etc complete as per specifications in
accordance with the approved shop drawing.
MR B1 Lot 4
22 Gauge
24 Gauge

THERMAL INSULATION:
Supply, installation & testing of external thermal insulation on ducts, as per the specifications & approved shop
drawings. Thermal insulation for indoor ducts foamed Nitrile Rubber with Alu Foil completely closed cell structure.
18 mm thick for Supply & Return air duct Class "1" of requisite quantity

ACCOUSTIC LINING:

GRILL/DIFFUSERS:
Supply & Return air Grill / Diffusers in extruted, anodiserd aluminium as per false ceiling design.
VOLUME CONTROL DAMPER PANEL & CABLE
Control Panel for AHU, Outdoor, Digital Temp. Gauge , Hygrometer & Differential Pressure Gauge
Cabling, & Earthing wire of requisite quantity

Part 'B' TRANSPLANT ICU