You are on page 1of 3

HEPA Exhaust Air Scrubber Design & Fabrication

S/N# DESCRIPTION Spec

1 Centrifugal Blower Air Volume: 1200 CFM


Power: 1.1 KW, 220 V Static Pressure: 959Pa-1200Pa
Low noise.

2 Custom Design Air Handling Unit casing to SUS 304 grade stainless steel has excellent resistance to wide range of
be constructed of environment and many corrosive media. Dimension: 2Ft x 3Ft x 2Ft
1.2mm thickness of stainless steel
grade SUS 304
3 HEPA (H class) Air Filter Type Grade H14 HEPA filter (High Efficiency Air Filter) H14 applies to this equipment and
99.995%, All type of Clean room capture 99.97% of particles with a Diameter of 0.3 micro meter.
application. Virus, Carbon duct, Sea salt,
Radon progency
4 Pre Air Filter G Class, Air Filter Type Grade Pre Air Filter G2 applies to this equipment and capture 75% of particle
G2 75%, Pollen, Dust mites, Sanding Dust, bigger then
Spray Paint Dust, Textile Fibers. 10 micro meter.

5 Air Intake Screen Type: Cleanable filter


Prevent air borne debris such as pollen, Media: SS
insect and litter from entering intakes and Max Temperature:130 C
clogging. Life Expectancy 5+years
6 Germicidal UVC lamp Wave length- 185- 254 Nano meter.
kill up 99.9% of most viruses, air borne 220 Volt, 13Watt
bacteria and mold spores
7 UVC Lamp electrical control box 2 Pole RCCB: 220 V 30 mA RCCB is aimed to protect electrical shock,
electrocution and fire hazard. UV light Indicator.
8 Electrical Safety Control Box Residual 2 Pole RCCB: 220V 30mA RCCB is aimed to protecting an individual from
Current Circuit Breaker (RCCB), risks of electrical shock, electrocution and fire that are caused due to faulty
Waterproof. wiring or earth faults

9 Exhaust Flexible Duct Steel wire is frame work. The frame work of duct is protected by rubber wear
strip. Diameter 150mm, Length 6 Meter.
HEPA Exhaust Air Scrubber Design & Fabrication

S/N# DESCRIPTION Spec

10 Differential Pressure Gage Zero Center Indicate Positive, Negative or Differential Pressure.
Range: 60-0-60 Pascal. No power required, used in isolation / hospital units.
11 Exhaust Air Grill Box Grill Air Louver 300mmX300mm, White colored powder paint coated with
stainless steel SUS 304 Attenuation box. Wall penetration accessories for
150mm exhaust duct.
12 Wooden Crate and Packaging for Shipping wood cleated panel board box

13 General overhead cost


Negative Air Pressure Isolation Ward Design Condition
The CDC design requirement for airborne infection isolation rooms:
 Use of negative pressure rooms with close monitoring of air flow direction using manometer or
temporary or installed indicators placed in the room with door closed
 Negative pressure room engineering features include negative pressure
 Pressure differential of 2.5 Pa (0.01 inches of water column)
 Minimum of 6 ACH for existing facilities, greater than or equal to 12 ACH for areas under
renovation or for new construction
 Air from negative pressure rooms and treatment rooms exhaust directly to the outside if
possible.

Isolation Ward/Room dimension: L 10 Ft. X W 15 Ft. X H 12 Ft.

Room volume: 1800 cubic feet

Air Change per Hour: 12 ACH

Required exhaust air volume: 405 CFM

Air Sterilization method: 26 Watt UVC Germicide lamps

Negative HEPA Air Scrubber Design and Fabrication


 1118- 1471 CFM centrifugal blower exhaust unit, 220 V 50Hz, 1.1 KW.
 HEPA air filter H13 and pre filter
 UV Air sterilization
 Stainless steel SS 304 housing
 L 3 Feet X H 2 Feet X W 2 Feet