Professional Documents
Culture Documents
Magnetic Influence Qualifying Bus Bracing Qualifying Bracing Upgrades high-power lab tests while doing
When electric currents pass IEEE C37.20.1 and IEEE C37.20.2 It is impractical to install qualification testing of numerous
through conductor systems, require manufacturers to test additional bracing and take the low voltage and medium voltage
they generate magnetic bus configurations to specific entire switchgear to a high- circuit breaker conversions.
fields. For two parallel round short circuit current ratings. power lab for qualification The same testing is utilized
conductors, the magnetic fields This ensures there is no testing. A more reasonable in the qualification of Eaton’s
are circular. Based on “the right movement that is mechanically approach is to perform new replacement power circuit
hand rule” the two conductors or electrically detrimental calculations and build sample breakers. This methodology has
repel each when the current to the bus or insulating bus structures based on the been successfully proven and
flows in opposite directions. components. Calculations calculations. The calculations tested by Eaton for over twenty
determine the location of indicate where additional years.
insulating components (bracing) braces should be added to
to prevent movement of the bus compensate for the increase Re-Qualification Process
conductors prior to test. High- in short circuit currents. The Eaton’s Power Breaker Center
power lab testing at the rated samples are tested in a high- has trained a number of Eaton’s
short circuit current parameters power lab. After testing, the Power Systems Engineers
verifies the calculations. As bus system is analyzed and the (PSE) on the details of bus
long as the switchgear is applied results correlated to the original bracing calculations due to the
within its original tested rating, calculations. This approach high demand for this service.
the bus bracing is sufficient. can save $3,000-$8,000 Eaton researches the existing
per switchgear structure as switchgear bus configuration
Ampere’s Law Bus Bracing Upgrades compared to replacing with new by visiting the customer’s
For alternating currents the equipment. site during an outage of the
Many power systems incur
fields are time-varying. The changes over time and the short switchgear requiring analysis.
magnetic fields create forces on circuit capability of the system 100% Confidence factor The calculations are performed
the conductors that are directly often exceeds the original rating Eaton’s Power Breaker Center and a report is generated to
proportional to the square of the switchgear. Modern has established a calculation determine if additional bracing
of the current and inversely circuit breaker technology methodology that yields is required. The report also
proportional to the conductor incorporated into conversions conservative results within indicates the location of the
separation. If unrestrained the can compensate for the high 5-10% of the actual lab test additional braces. The bracing
conductors can experience short circuit currents, but the measurements. Adjustments materials are designed,
substantial movement during a bus system usually requires can be made for copper or fabricated and sent to the
short circuit event. additional bracing to prevent aluminum bus, compensation customer’s site for installation
damage during a maximum for different insulating materials, by a qualified Eaton Service
short circuit event. A system different spacings between Engineer.
F =M 2 ×10 −7 i1i2 cannot be rated any higher than bus bars and the shape and
its lowest rated component. configuration of the bus New Certification Labels
l d
conductors. The calculations and The Engineer also attaches a
tests are based on using any label to each structure to certify
bus configuration and material, its new bus bracing rating. The
so the method is not specific new certification is backed
to any particular manufacturer’s by Eaton and is valid unless
bus design. The methodology additional changes are made to
has been tested in hundreds of the switchgear.
Fault Currents--10 Cycles
Dynamic Response - Fixed Ends
Imax/rms= 2.70
Peak Current= 97 KA
Deflection (inches)
40,000 15.000
20,000
10.000 A
5.000
0 B
1 11 21 31 41 51 61 71 81 91 101 111 121 131 141 151 161 171 181 0.000
-20,000
-5.000 C
-40,000 -10.000
-60,000 -15.000
-80,000 -20.000
0
9
19
28
37
46
56
65
74
83
93
102
111
120
130
139
148
157
167
-100,000
6.0000
5.0000
4.0000
3.0000
2.0000
1.0000
0.0000
0 10 20 30 40
Span Distance (Inches)
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
© 2017 Eaton
All Rights Reserved Eaton is a registered trademark.
Printed in USA
Publication No. PA182404EN All trademarks are property
June 2017 of their respective owners.