Calculation Months .................................... Jan to Dec Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ................................................ Calculated Space L/s Sizing .............. Individual peak space loads
Calculation Months .................................... Jan to Dec Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ................................................ Calculated Space L/s Sizing .............. Individual peak space loads
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' UG Administration '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 2000 HEATING DATA AT DES HTG
COOLING OA DB / WB 38.5 °C / 22.3 °C HEATING OA DB / WB -3.0 °C / -6.2 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 22.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 2 m² 422 - 2 m² - -
Wall Transmission 8 m² 132 - 8 m² 142 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 2 m² 108 - 2 m² 187 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 12 m² 10 - 12 m² 41 -
Partitions 23 m² 124 - 23 m² 585 -
Ceiling 12 m² 3 - 12 m² 18 -
Overhead Lighting 60 W 60 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 178 -26 - 307 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 1431 95 - 1280 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' UG Administration '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 8 0.704 - 132 - 142
WINDOW 1 2 3.687 0.792 108 422 187
TABLE 2.1.A. COMPONENT LOADS FOR SPACE '' UG Class29 '' IN ZONE '' Zone 2 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 44.6 °C / 23.9 °C HEATING OA DB / WB -3.0 °C / -6.2 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 22.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 6 m² 1161 - 6 m² - -
Wall Transmission 29 m² 368 - 29 m² 516 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 6 m² 404 - 6 m² 558 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 30 m² 39 - 30 m² 102 -
Partitions 22 m² 143 - 22 m² 420 -
Ceiling 30 m² 14 - 30 m² 48 -
Overhead Lighting 150 W 150 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 160 W 160 - 0 0 -
People 26 2134 2057 0 0 0
Infiltration - 633 32 - 768 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5205 2089 - 2412 0
TABLE 2.1.B. ENVELOPE LOADS FOR SPACE '' UG Class29 '' IN ZONE '' Zone 2 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 16 0.704 - 234 - 288
WINDOW 1 3 3.673 0.792 224 645 310
WINDOW 2 3 3.678 0.792 179 516 248
N EXPOSURE
WALL 13 0.704 - 134 - 229
TABLE 3.1.A. COMPONENT LOADS FOR SPACE '' UG Class30 '' IN ZONE '' Zone 3 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 44.6 °C / 23.9 °C HEATING OA DB / WB -3.0 °C / -6.2 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 22.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 6 m² 1161 - 6 m² - -
Wall Transmission 29 m² 364 - 29 m² 516 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 6 m² 404 - 6 m² 558 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 30 m² 39 - 30 m² 102 -
Partitions 22 m² 143 - 22 m² 420 -
Ceiling 30 m² 14 - 30 m² 48 -
Overhead Lighting 150 W 150 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 160 W 160 - 0 0 -
People 26 2134 2057 0 0 0
Infiltration - 633 26 - 768 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5202 2083 - 2412 0
TABLE 3.1.B. ENVELOPE LOADS FOR SPACE '' UG Class30 '' IN ZONE '' Zone 3 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 16 0.704 - 234 - 288
WINDOW 1 3 3.673 0.792 224 645 310
WINDOW 2 3 3.678 0.792 179 516 248
S EXPOSURE
WALL 13 0.704 - 131 - 229
TABLE 4.1.A. COMPONENT LOADS FOR SPACE '' UG Class31 '' IN ZONE '' Zone 4 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 2000 HEATING DATA AT DES HTG
COOLING OA DB / WB 38.5 °C / 22.3 °C HEATING OA DB / WB -3.0 °C / -6.2 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 22.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 703 - 3 m² - -
Wall Transmission 13 m² 213 - 13 m² 229 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 179 - 3 m² 310 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 20 m² 17 - 20 m² 70 -
Partitions 29 m² 159 - 29 m² 749 -
Ceiling 20 m² 5 - 20 m² 32 -
Overhead Lighting 102 W 102 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 160 W 160 - 0 0 -
People 26 2134 2057 0 0 0
Infiltration - 303 21 - 522 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 3975 2077 - 1912 0
TABLE 4.1.B. ENVELOPE LOADS FOR SPACE '' UG Class31 '' IN ZONE '' Zone 4 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 13 0.704 - 213 - 229
WINDOW 1 3 3.673 0.792 179 703 310
TABLE 5.1.A. COMPONENT LOADS FOR SPACE '' UG Class32 '' IN ZONE '' Zone 5 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 2000 HEATING DATA AT DES HTG
COOLING OA DB / WB 38.5 °C / 22.3 °C HEATING OA DB / WB -3.0 °C / -6.2 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 22.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 703 - 3 m² - -
Wall Transmission 13 m² 214 - 13 m² 231 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 179 - 3 m² 310 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 21 m² 17 - 21 m² 71 -
Partitions 17 m² 90 - 17 m² 422 -
Ceiling 21 m² 5 - 21 m² 33 -
Overhead Lighting 104 W 104 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 160 W 160 - 0 0 -
People 26 2134 2057 0 0 0
Infiltration - 309 23 - 533 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 3916 2079 - 1599 0
TABLE 5.1.B. ENVELOPE LOADS FOR SPACE '' UG Class32 '' IN ZONE '' Zone 5 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 13 0.704 - 214 - 231
WINDOW 1 3 3.673 0.792 179 703 310
TABLE 6.1.A. COMPONENT LOADS FOR SPACE '' UG Computer Laborator 1* '' IN ZONE '' Zone 6 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 40.7 °C / 22.0 °C HEATING OA DB / WB -3.0 °C / -6.2 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 22.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 696 - 3 m² - -
Wall Transmission 15 m² 226 - 15 m² 266 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 184 - 3 m² 310 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 22 m² 20 - 22 m² 76 -
Partitions 32 m² 138 - 32 m² 612 -
Ceiling 22 m² 6 - 22 m² 35 -
Overhead Lighting 111 W 111 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1500 W 1500 - 0 0 -
People 10 718 601 0 0 0
Infiltration - 380 -44 - 569 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 3978 557 - 1868 0
TABLE 6.1.B. ENVELOPE LOADS FOR SPACE '' UG Computer Laborator 1* '' IN ZONE '' Zone 6 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
S EXPOSURE
WALL 15 0.704 - 226 - 266
WINDOW 1 3 3.673 0.792 184 696 310
TABLE 7.1.A. COMPONENT LOADS FOR SPACE '' UG Computer Laborator 2* '' IN ZONE '' Zone 7 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 44.6 °C / 23.9 °C HEATING OA DB / WB -3.0 °C / -6.2 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 22.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 192 - 3 m² - -
Wall Transmission 28 m² 346 - 28 m² 501 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 227 - 3 m² 310 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 22 m² 30 - 22 m² 76 -
Partitions 18 m² 119 - 18 m² 342 -
Ceiling 22 m² 10 - 22 m² 35 -
Overhead Lighting 111 W 111 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1500 W 1500 - 0 0 -
People 10 718 601 0 0 0
Infiltration - 468 11 - 569 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 3722 612 - 1832 0
TABLE 7.1.B. ENVELOPE LOADS FOR SPACE '' UG Computer Laborator 2* '' IN ZONE '' Zone 7 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 15 0.704 - 180 - 266
WINDOW 1 3 3.673 0.792 227 192 310
W EXPOSURE
WALL 13 0.704 - 166 - 234
TABLE 8.1.A. COMPONENT LOADS FOR SPACE '' UG Computer Laboratory 1 '' IN ZONE '' Zone 8 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 44.6 °C / 23.9 °C HEATING OA DB / WB -3.0 °C / -6.2 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 22.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 192 - 3 m² - -
Wall Transmission 15 m² 180 - 15 m² 266 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 227 - 3 m² 310 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 22 m² 30 - 22 m² 76 -
Partitions 32 m² 214 - 32 m² 612 -
Ceiling 22 m² 10 - 22 m² 35 -
Overhead Lighting 111 W 111 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1500 W 1500 - 0 0 -
People 10 718 601 0 0 0
Infiltration - 468 17 - 569 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 3650 618 - 1868 0
TABLE 8.1.B. ENVELOPE LOADS FOR SPACE '' UG Computer Laboratory 1 '' IN ZONE '' Zone 8 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 15 0.704 - 180 - 266
WINDOW 1 3 3.673 0.792 227 192 310
TABLE 9.1.A. COMPONENT LOADS FOR SPACE '' UG Computer Laboratory 2 '' IN ZONE '' Zone 9 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 44.6 °C / 23.9 °C HEATING OA DB / WB -3.0 °C / -6.2 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 22.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 192 - 3 m² - -
Wall Transmission 28 m² 346 - 28 m² 501 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 227 - 3 m² 310 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 22 m² 30 - 22 m² 76 -
Partitions 18 m² 119 - 18 m² 342 -
Ceiling 22 m² 11 - 22 m² 36 -
Overhead Lighting 112 W 112 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1500 W 1500 - 0 0 -
People 10 718 601 0 0 0
Infiltration - 472 0 - 574 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 3727 601 - 1838 0
TABLE 9.1.B. ENVELOPE LOADS FOR SPACE '' UG Computer Laboratory 2 '' IN ZONE '' Zone 9 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 15 0.704 - 180 - 266
WINDOW 1 3 3.673 0.792 227 192 310
W EXPOSURE
WALL 13 0.704 - 166 - 234
TABLE 10.1.A. COMPONENT LOADS FOR SPACE '' UG Library '' IN ZONE '' Zone 10 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Sep 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 40.7 °C / 22.0 °C HEATING OA DB / WB -3.0 °C / -6.2 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 22.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 4 m² 835 - 4 m² - -
Wall Transmission 16 m² 246 - 16 m² 290 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 4 m² 221 - 4 m² 373 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 25 m² 22 - 25 m² 84 -
Partitions 74 m² 218 - 74 m² 977 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 124 W 124 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 8 539 282 0 0 0
Infiltration - 424 -136 - 635 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 2879 145 - 2359 0
TABLE 10.1.B. ENVELOPE LOADS FOR SPACE '' UG Library '' IN ZONE '' Zone 10 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
S EXPOSURE
WALL 16 0.704 - 246 - 290
WINDOW 1 4 3.687 0.792 221 835 373
TABLE 11.1.A. COMPONENT LOADS FOR SPACE '' UG Multi-purpose hall '' IN ZONE '' Zone 11 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1900 HEATING DATA AT DES HTG
COOLING OA DB / WB 40.3 °C / 22.8 °C HEATING OA DB / WB -3.0 °C / -6.2 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 22.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 7 m² 1239 - 7 m² - -
Wall Transmission 27 m² 404 - 27 m² 473 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 7 m² 388 - 7 m² 620 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 42 m² 41 - 42 m² 141 -
Partitions 45 m² 216 - 45 m² 847 -
Ceiling 42 m² 13 - 42 m² 66 -
Overhead Lighting 208 W 207 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 350 W 350 - 0 0 -
People 25 2162 3333 0 0 0
Infiltration - 1387 -29 - 2126 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 6407 3304 - 4272 0
TABLE 11.1.B. ENVELOPE LOADS FOR SPACE '' UG Multi-purpose hall '' IN ZONE '' Zone 11 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 27 0.704 - 404 - 473
WINDOW 1 7 3.673 0.792 388 1239 620
TABLE 12.1.A. COMPONENT LOADS FOR SPACE '' UG Science Laboratory 1 '' IN ZONE '' Zone 12 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 44.6 °C / 23.9 °C HEATING OA DB / WB -3.0 °C / -6.2 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 22.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 516 - 3 m² - -
Wall Transmission 17 m² 236 - 17 m² 291 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 181 - 3 m² 250 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 24 m² 32 - 24 m² 82 -
Partitions 32 m² 206 - 32 m² 605 -
Ceiling 24 m² 11 - 24 m² 38 -
Overhead Lighting 120 W 120 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2200 W 2200 - 0 0 -
People 16 1384 2133 0 0 0
Infiltration - 506 36 - 615 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5392 2169 - 1880 0
TABLE 12.1.B. ENVELOPE LOADS FOR SPACE '' UG Science Laboratory 1 '' IN ZONE '' Zone 12 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 17 0.704 - 236 - 291
WINDOW 1 3 3.706 0.792 181 516 250
TABLE 13.1.A. COMPONENT LOADS FOR SPACE '' UG Science Laboratory 2 '' IN ZONE '' Zone 13 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 44.6 °C / 23.9 °C HEATING OA DB / WB -3.0 °C / -6.2 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 22.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 3 m² 516 - 3 m² - -
Wall Transmission 17 m² 236 - 17 m² 291 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 3 m² 181 - 3 m² 250 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 24 m² 32 - 24 m² 82 -
Partitions 33 m² 152 - 33 m² 363 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 120 W 120 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2200 W 2200 - 0 0 -
People 16 1384 2133 0 0 0
Infiltration - 506 50 - 615 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5326 2183 - 1600 0
TABLE 13.1.B. ENVELOPE LOADS FOR SPACE '' UG Science Laboratory 2 '' IN ZONE '' Zone 13 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 17 0.704 - 236 - 291
WINDOW 1 3 3.706 0.792 181 516 250
TABLE 14.1.A. COMPONENT LOADS FOR SPACE '' UG Science Laboratory 3 '' IN ZONE '' Zone 14 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 44.6 °C / 23.9 °C HEATING OA DB / WB -3.0 °C / -6.2 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 22.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 4 m² 231 - 4 m² - -
Wall Transmission 29 m² 358 - 29 m² 519 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 4 m² 273 - 4 m² 373 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 25 m² 33 - 25 m² 85 -
Partitions 34 m² 223 - 34 m² 641 -
Ceiling 25 m² 12 - 25 m² 39 -
Overhead Lighting 124 W 124 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2200 W 2200 - 0 0 -
People 16 1384 2133 0 0 0
Infiltration - 523 56 - 635 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5361 2188 - 2292 0
TABLE 14.1.B. ENVELOPE LOADS FOR SPACE '' UG Science Laboratory 3 '' IN ZONE '' Zone 14 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 16 0.704 - 196 - 290
WINDOW 1 4 3.687 0.792 273 231 373
W EXPOSURE
WALL 13 0.704 - 162 - 229
TABLE 15.1.A. COMPONENT LOADS FOR SPACE '' UG Science Laboratory 4 '' IN ZONE '' Zone 15 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 43.6 °C / 23.6 °C HEATING OA DB / WB -3.0 °C / -6.2 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 22.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 5 m² 390 - 5 m² - -
Wall Transmission 29 m² 450 - 29 m² 519 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 5 m² 309 - 5 m² 435 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 28 m² 35 - 28 m² 95 -
Partitions 23 m² 143 - 23 m² 435 -
Ceiling 28 m² 12 - 28 m² 44 -
Overhead Lighting 139 W 139 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2200 W 2200 - 0 0 -
People 16 1384 2133 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5062 2133 - 1528 0
TABLE 15.1.B. ENVELOPE LOADS FOR SPACE '' UG Science Laboratory 4 '' IN ZONE '' Zone 15 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 18 0.704 - 234 - 324
WINDOW 1 3 3.673 0.792 220 197 310
E EXPOSURE
WALL 11 0.704 - 215 - 195
WINDOW 1 1 3.706 0.792 89 193 125
TABLE 16.1.A. COMPONENT LOADS FOR SPACE '' UG Sports activities hal '' IN ZONE '' Zone 16 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1800 HEATING DATA AT DES HTG
COOLING OA DB / WB 42.1 °C / 23.2 °C HEATING OA DB / WB -3.0 °C / -6.2 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 22.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1731 - 12 m² - -
Wall Transmission 57 m² 860 - 57 m² 999 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 752 - 12 m² 1118 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 63 m² 72 - 63 m² 215 -
Partitions 42 m² 237 - 42 m² 801 -
Ceiling 63 m² 24 - 63 m² 100 -
Overhead Lighting 315 W 315 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 800 W 800 - 0 0 -
People 25 3847 6778 0 0 0
Infiltration - 1168 11 - 1614 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 9806 6789 - 4847 0
TABLE 16.1.B. ENVELOPE LOADS FOR SPACE '' UG Sports activities hal '' IN ZONE '' Zone 16 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 28 0.704 - 390 - 499
WINDOW 1 3 3.678 0.792 167 402 248
WINDOW 2 3 3.673 0.792 208 502 310
S EXPOSURE
WALL 28 0.704 - 470 - 501
WINDOW 1 3 3.706 0.792 168 368 250
WINDOW 2 3 3.673 0.792 208 460 310
TABLE 17.1.A. COMPONENT LOADS FOR SPACE '' UG Tawjih '' IN ZONE '' Zone 17 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 44.6 °C / 23.9 °C HEATING OA DB / WB -3.0 °C / -6.2 °C
OCCUPIED T-STAT 24.0 °C OCCUPIED T-STAT 22.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 2 m² 387 - 2 m² - -
Wall Transmission 6 m² 86 - 6 m² 105 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 2 m² 135 - 2 m² 187 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 10 m² 13 - 10 m² 34 -
Partitions 21 m² 179 - 21 m² 524 -
Ceiling 10 m² 5 - 10 m² 16 -
Overhead Lighting 50 W 50 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 211 -3 - 256 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 1458 117 - 1122 0
TABLE 17.1.B. ENVELOPE LOADS FOR SPACE '' UG Tawjih '' IN ZONE '' Zone 17 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 6 0.704 - 86 - 105
WINDOW 1 2 3.687 0.792 135 387 187
ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 33.7 24.6 65 95.5 1144.3 1079.1 1812.8 0.0 0.0
0100 33.0 24.6 67 95.5 1102.1 1041.2 1767.4 0.0 0.0
0200 32.3 24.6 68 95.5 1055.4 998.3 1716.4 0.0 0.0
0300 31.8 24.6 69 95.5 1012.2 958.9 1672.8 0.0 0.0
0400 31.3 24.6 70 95.5 974.3 924.6 1631.8 0.0 0.0
0500 31.2 24.5 71 95.5 946.9 900.4 1603.0 0.0 0.0
0600 31.5 24.5 71 95.5 934.9 890.8 1591.7 0.0 0.0
0700 32.2 24.4 71 95.5 938.5 914.0 1618.4 0.0 0.0
0800 33.4 24.5 70 95.5 962.5 932.0 1639.9 0.0 0.0
0900 35.2 24.5 69 95.5 1007.0 965.3 1679.3 0.0 0.0
1000 37.3 24.5 67 95.5 1072.4 1027.0 1753.3 0.0 0.0
1100 39.6 24.6 65 95.5 1152.2 1089.3 1826.1 0.0 0.0
1200 41.8 24.7 63 95.5 1230.0 1145.6 1890.8 0.0 0.0
1300 43.5 24.6 61 95.5 1292.5 1222.9 1983.0 0.0 0.0
1400 44.6 24.6 60 95.5 1339.0 1281.5 2052.7 0.0 0.0
1500 45.0 24.8 60 95.5 1363.7 1261.5 2025.5 0.0 0.0
1600 44.6 24.8 60 95.5 1363.5 1269.2 2034.7 0.0 0.0
1700 43.6 24.7 60 95.5 1378.6 1288.6 2057.9 0.0 0.0
1800 42.1 24.8 59 95.5 1409.8 1313.5 2086.7 0.0 0.0
1900 40.3 24.7 58 95.5 1428.5 1355.6 2137.9 0.0 0.0
2000 38.5 24.7 58 95.5 1430.6 1348.9 2129.5 0.0 0.0
2100 37.0 24.7 58 95.5 1410.9 1345.0 2126.3 0.0 0.0
2200 35.6 24.8 61 95.5 1334.7 1246.9 2009.3 0.0 0.0
2300 34.5 24.6 64 95.5 1183.4 1142.4 1889.4 0.0 0.0
ZONE: Zone 2
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 33.7 24.6 60 347.4 4109.4 4041.3 5964.0 0.0 0.0
0100 33.0 24.6 61 347.4 4014.5 3950.7 5860.6 0.0 0.0
0200 32.3 24.6 62 347.4 3918.4 3858.6 5757.0 0.0 0.0
0300 31.8 24.7 63 347.4 3831.8 3717.0 5588.8 0.0 0.0
0400 31.3 24.6 63 347.4 3755.8 3691.5 5565.8 0.0 0.0
0500 31.2 24.6 64 347.4 3699.3 3647.4 5517.9 0.0 0.0
0600 31.5 24.7 64 347.4 3670.7 3567.6 5420.3 0.0 0.0
0700 32.2 24.6 64 347.4 3670.7 3620.2 5487.9 0.0 0.0
0800 33.4 24.7 64 347.4 3708.0 3603.6 5462.5 0.0 0.0
0900 35.2 24.6 63 347.4 3783.5 3726.5 5609.3 0.0 0.0
1000 37.3 24.8 60 347.4 4230.3 4057.3 5966.5 0.0 0.0
1100 39.6 24.7 56 347.4 4665.6 4551.1 6540.8 0.0 0.0
1200 41.8 24.7 54 347.4 4964.5 4855.1 6882.2 0.0 0.0
1300 43.5 24.9 53 347.4 5144.2 4929.5 6953.1 0.0 0.0
1400 44.6 24.6 52 347.4 5205.1 5128.2 7187.0 0.0 0.0
1500 45.0 24.7 53 347.4 5140.4 5033.8 7077.7 0.0 0.0
1600 44.6 24.8 54 347.4 5035.1 4874.8 6893.1 0.0 0.0
1700 43.6 24.6 53 347.4 4985.7 4932.2 6973.4 0.0 0.0
1800 42.1 24.6 54 347.4 4893.9 4833.3 6855.9 0.0 0.0
1900 40.3 24.8 56 347.4 4769.0 4610.6 6596.3 0.0 0.0
2000 38.5 24.7 56 347.4 4629.8 4520.2 6498.5 0.0 0.0
2100 37.0 24.7 57 347.4 4493.3 4399.5 6364.6 0.0 0.0
2200 35.6 24.6 58 347.4 4349.7 4265.9 6213.9 0.0 0.0
2300 34.5 24.6 59 347.4 4209.8 4134.3 6066.5 0.0 0.0
ZONE: Zone 3
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 33.7 24.6 60 347.2 4130.8 4054.6 5979.3 0.0 0.0
0100 33.0 24.6 61 347.2 4030.7 3959.8 5871.2 0.0 0.0
0200 32.3 24.6 62 347.2 3931.3 3865.2 5764.8 0.0 0.0
0300 31.8 24.7 63 347.2 3842.6 3721.1 5593.6 0.0 0.0
0400 31.3 24.6 63 347.2 3765.2 3702.3 5579.2 0.0 0.0
0500 31.2 24.6 64 347.2 3707.5 3652.1 5523.8 0.0 0.0
0600 31.5 24.6 64 347.2 3678.2 3582.2 5438.9 0.0 0.0
0700 32.2 24.6 64 347.2 3677.4 3610.8 5476.0 0.0 0.0
0800 33.4 24.6 64 347.2 3714.2 3655.0 5527.8 0.0 0.0
0900 35.2 24.4 62 347.2 3789.2 3809.5 5704.6 0.0 0.0
1000 37.3 24.5 59 347.2 4235.5 4191.5 6144.6 0.0 0.0
1100 39.6 24.7 56 347.2 4669.7 4541.6 6531.2 0.0 0.0
1200 41.8 24.6 54 347.2 4965.7 4858.8 6888.6 0.0 0.0
1300 43.5 24.7 53 347.2 5142.2 5026.9 7074.3 0.0 0.0
1400 44.6 24.7 52 347.2 5201.9 5080.1 7131.5 0.0 0.0
1500 45.0 24.9 53 347.2 5139.4 4914.4 6925.8 0.0 0.0
1600 44.6 24.6 53 347.2 5039.8 4981.1 7032.5 0.0 0.0
1700 43.6 24.7 54 347.2 4998.3 4878.0 6898.5 0.0 0.0
1800 42.1 24.7 54 347.2 4915.2 4813.2 6825.9 0.0 0.0
1900 40.3 24.7 55 347.2 4798.2 4678.1 6677.8 0.0 0.0
2000 38.5 24.8 56 347.2 4664.3 4499.5 6470.8 0.0 0.0
2100 37.0 24.6 57 347.2 4529.7 4476.8 6457.6 0.0 0.0
2200 35.6 24.5 58 347.2 4383.8 4370.9 6342.4 0.0 0.0
2300 34.5 24.6 59 347.2 4238.1 4164.8 6103.7 0.0 0.0
ZONE: Zone 4
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 33.7 24.7 56 265.3 3520.9 3431.5 4793.0 0.0 0.0
0100 33.0 24.8 57 265.3 3454.8 3326.6 4671.1 0.0 0.0
0200 32.3 24.5 56 265.3 3381.6 3345.4 4701.9 0.0 0.0
0300 31.8 24.7 58 265.3 3313.6 3212.2 4547.0 0.0 0.0
0400 31.3 24.6 58 265.3 3253.7 3175.7 4508.4 0.0 0.0
0500 31.2 24.6 59 265.3 3210.0 3136.4 4465.6 0.0 0.0
0600 31.5 24.8 59 265.3 3189.9 3053.4 4365.6 0.0 0.0
0700 32.2 24.5 59 265.3 3193.5 3149.3 4483.6 0.0 0.0
0800 33.4 24.5 58 265.3 3228.1 3205.4 4549.3 0.0 0.0
0900 35.2 24.6 58 265.3 3294.1 3207.3 4545.3 0.0 0.0
1000 37.3 24.5 57 265.3 3393.0 3342.5 4700.1 0.0 0.0
1100 39.6 24.8 56 265.3 3514.4 3376.6 4728.7 0.0 0.0
1200 41.8 24.7 55 265.3 3632.6 3522.4 4892.4 0.0 0.0
1300 43.5 24.5 53 265.3 3727.8 3676.2 5067.8 0.0 0.0
1400 44.6 24.7 53 265.3 3798.8 3680.1 5065.1 0.0 0.0
1500 45.0 24.7 52 265.3 3836.7 3746.5 5140.6 0.0 0.0
1600 44.6 24.8 53 265.3 3837.3 3690.5 5077.3 0.0 0.0
1700 43.6 24.8 52 265.3 3866.1 3743.6 5134.2 0.0 0.0
1800 42.1 24.7 52 265.3 3924.7 3807.7 5206.3 0.0 0.0
1900 40.3 24.7 51 265.3 3963.8 3853.3 5257.8 0.0 0.0
2000 38.5 24.8 52 265.3 3975.4 3828.5 5227.2 0.0 0.0
2100 37.0 24.8 52 265.3 3949.5 3826.8 5228.2 0.0 0.0
2200 35.6 24.7 53 265.3 3829.0 3716.9 5106.7 0.0 0.0
2300 34.5 24.7 55 265.3 3582.0 3485.2 4850.4 0.0 0.0
ZONE: Zone 5
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 33.7 24.5 55 261.4 3498.8 3508.1 4915.5 0.0 0.0
0100 33.0 24.7 56 261.4 3438.5 3351.2 4729.9 0.0 0.0
0200 32.3 24.4 56 261.4 3371.0 3378.9 4771.6 0.0 0.0
0300 31.8 24.6 57 261.4 3307.8 3268.8 4644.4 0.0 0.0
0400 31.3 24.4 57 261.4 3251.8 3250.8 4628.6 0.0 0.0
0500 31.2 24.7 59 261.4 3210.0 3117.1 4468.9 0.0 0.0
0600 31.5 24.5 58 261.4 3188.6 3168.4 4534.8 0.0 0.0
0700 32.2 24.6 59 261.4 3187.9 3120.4 4476.4 0.0 0.0
0800 33.4 24.5 58 261.4 3213.9 3189.5 4558.8 0.0 0.0
0900 35.2 24.6 58 261.4 3267.0 3209.1 4577.6 0.0 0.0
1000 37.3 24.6 57 261.4 3350.8 3305.7 4687.1 0.0 0.0
1100 39.6 24.8 56 261.4 3454.5 3327.4 4701.3 0.0 0.0
1200 41.8 24.8 55 261.4 3555.8 3427.1 4810.8 0.0 0.0
1300 43.5 24.8 54 261.4 3637.9 3518.6 4919.0 0.0 0.0
1400 44.6 24.6 53 261.4 3699.6 3651.9 5067.4 0.0 0.0
1500 45.0 24.6 53 261.4 3733.2 3676.8 5093.9 0.0 0.0
1600 44.6 24.6 53 261.4 3735.6 3694.0 5114.4 0.0 0.0
1700 43.6 24.6 53 261.4 3770.5 3721.5 5144.7 0.0 0.0
1800 42.1 24.8 53 261.4 3839.4 3710.9 5125.6 0.0 0.0
1900 40.3 24.5 51 261.4 3891.3 3858.6 5299.1 0.0 0.0
2000 38.5 24.8 52 261.4 3915.8 3805.3 5233.1 0.0 0.0
2100 37.0 24.9 52 261.4 3901.4 3747.9 5165.4 0.0 0.0
2200 35.6 24.6 52 261.4 3791.4 3747.3 5174.8 0.0 0.0
2300 34.5 24.8 55 261.4 3553.1 3450.8 4838.9 0.0 0.0
ZONE: Zone 6
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 33.7 24.5 59 265.5 3185.9 3165.5 4604.3 0.0 0.0
0100 33.0 24.6 60 265.5 3127.0 3053.7 4476.1 0.0 0.0
0200 32.3 24.8 62 265.5 3067.8 2930.4 4329.0 0.0 0.0
0300 31.8 24.7 62 265.5 3016.2 2926.9 4330.4 0.0 0.0
0400 31.3 24.6 62 265.5 2972.5 2910.2 4314.8 0.0 0.0
0500 31.2 24.6 62 265.5 2943.7 2856.6 4251.7 0.0 0.0
0600 31.5 24.6 62 265.5 2936.8 2874.4 4275.0 0.0 0.0
0700 32.2 24.7 63 265.5 2951.9 2849.3 4242.6 0.0 0.0
0800 33.4 24.6 62 265.5 2996.2 2922.9 4321.7 0.0 0.0
0900 35.2 24.7 61 265.5 3070.3 2963.9 4372.8 0.0 0.0
1000 37.3 24.6 60 265.5 3176.3 3098.5 4532.1 0.0 0.0
1100 39.6 24.5 58 265.5 3305.4 3261.6 4723.8 0.0 0.0
1200 41.8 24.6 57 265.5 3432.4 3340.0 4795.1 0.0 0.0
1300 43.5 24.7 56 265.5 3550.1 3423.0 4887.0 0.0 0.0
1400 44.6 24.7 55 265.5 3664.0 3555.6 5037.0 0.0 0.0
1500 45.0 24.6 54 265.5 3748.2 3665.9 5158.5 0.0 0.0
1600 44.6 24.8 54 265.5 3782.5 3636.3 5123.1 0.0 0.0
1700 43.6 24.7 54 265.5 3771.2 3659.1 5151.7 0.0 0.0
1800 42.1 24.7 55 265.5 3709.6 3604.5 5091.2 0.0 0.0
1900 40.3 24.7 55 265.5 3614.4 3516.3 4992.7 0.0 0.0
2000 38.5 24.7 56 265.5 3515.2 3424.0 4889.3 0.0 0.0
2100 37.0 24.7 57 265.5 3430.4 3344.9 4801.3 0.0 0.0
2200 35.6 24.6 58 265.5 3338.4 3258.7 4704.2 0.0 0.0
2300 34.5 24.6 59 265.5 3250.1 3175.5 4611.7 0.0 0.0
ZONE: Zone 7
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 33.7 24.8 56 248.4 3362.9 3257.0 4721.0 0.0 0.0
0100 33.0 24.7 57 248.4 3307.9 3236.2 4700.4 0.0 0.0
0200 32.3 24.7 57 248.4 3242.4 3181.8 4640.7 0.0 0.0
0300 31.8 24.8 58 248.4 3179.8 3084.0 4526.3 0.0 0.0
0400 31.3 24.6 58 248.4 3124.2 3085.9 4534.7 0.0 0.0
0500 31.2 24.6 59 248.4 3083.0 3028.2 4468.4 0.0 0.0
0600 31.5 24.7 59 248.4 3062.5 2986.3 4418.4 0.0 0.0
0700 32.2 24.6 59 248.4 3063.3 3009.2 4447.5 0.0 0.0
0800 33.4 24.6 59 248.4 3091.5 3034.9 4476.6 0.0 0.0
0900 35.2 24.6 58 248.4 3147.9 3111.7 4566.4 0.0 0.0
1000 37.3 24.6 57 248.4 3279.7 3247.3 4720.8 0.0 0.0
1100 39.6 24.7 56 248.4 3383.3 3299.3 4773.3 0.0 0.0
1200 41.8 24.6 55 248.4 3479.2 3432.4 4925.7 0.0 0.0
1300 43.5 24.6 54 248.4 3576.2 3507.5 5007.0 0.0 0.0
1400 44.6 24.6 53 248.4 3654.9 3598.7 5109.9 0.0 0.0
1500 45.0 24.8 53 248.4 3705.6 3582.7 5085.6 0.0 0.0
1600 44.6 24.8 53 248.4 3721.6 3617.0 5127.5 0.0 0.0
1700 43.6 24.9 53 248.4 3710.7 3572.6 5068.7 0.0 0.0
1800 42.1 24.8 53 248.4 3671.7 3575.1 5081.7 0.0 0.0
1900 40.3 24.9 54 248.4 3619.7 3488.3 4976.9 0.0 0.0
2000 38.5 24.7 54 248.4 3563.7 3477.8 4965.7 0.0 0.0
2100 37.0 24.8 55 248.4 3530.5 3413.1 4890.9 0.0 0.0
2200 35.6 24.8 55 248.4 3500.2 3390.3 4864.7 0.0 0.0
2300 34.5 24.8 56 248.4 3406.9 3308.0 4773.2 0.0 0.0
ZONE: Zone 8
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 33.7 24.6 58 243.6 3112.9 3042.8 4486.3 0.0 0.0
0100 33.0 24.6 59 243.6 3062.2 2996.7 4436.0 0.0 0.0
0200 32.3 24.5 59 243.6 3008.9 3003.7 4456.7 0.0 0.0
0300 31.8 24.6 60 243.6 2961.7 2893.6 4314.2 0.0 0.0
0400 31.3 24.5 60 243.6 2921.6 2892.2 4324.3 0.0 0.0
0500 31.2 24.6 61 243.6 2895.9 2829.5 4246.6 0.0 0.0
0600 31.5 24.5 61 243.6 2891.6 2847.5 4276.4 0.0 0.0
0700 32.2 24.6 61 243.6 2909.1 2833.2 4257.9 0.0 0.0
0800 33.4 24.5 60 243.6 2955.7 2923.7 4360.5 0.0 0.0
0900 35.2 24.6 59 243.6 3031.9 2967.9 4408.1 0.0 0.0
1000 37.3 24.6 58 243.6 3183.1 3097.6 4553.7 0.0 0.0
1100 39.6 24.6 56 243.6 3305.4 3241.6 4718.1 0.0 0.0
1200 41.8 24.6 55 243.6 3416.1 3349.0 4838.0 0.0 0.0
1300 43.5 24.7 54 243.6 3520.9 3413.5 4905.8 0.0 0.0
1400 44.6 24.8 54 243.6 3600.7 3455.3 4949.8 0.0 0.0
1500 45.0 24.7 53 243.6 3646.1 3521.9 5025.0 0.0 0.0
1600 44.6 24.6 53 243.6 3650.2 3582.5 5097.1 0.0 0.0
1700 43.6 24.8 54 243.6 3623.7 3484.4 4975.8 0.0 0.0
1800 42.1 24.7 54 243.6 3565.0 3451.1 4941.1 0.0 0.0
1900 40.3 24.9 55 243.6 3488.6 3331.4 4805.5 0.0 0.0
2000 38.5 24.7 56 243.6 3404.1 3293.4 4766.5 0.0 0.0
2100 37.0 24.7 56 243.6 3341.4 3249.0 4718.7 0.0 0.0
2200 35.6 24.9 57 243.6 3282.5 3124.8 4570.9 0.0 0.0
2300 34.5 24.7 58 243.6 3166.8 3077.4 4524.0 0.0 0.0
ZONE: Zone 9
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 33.7 24.8 56 248.8 3366.0 3268.5 4746.9 0.0 0.0
0100 33.0 24.7 57 248.8 3310.8 3241.9 4719.2 0.0 0.0
0200 32.3 24.8 58 248.8 3245.1 3136.8 4601.4 0.0 0.0
0300 31.8 24.5 58 248.8 3182.5 3166.5 4640.3 0.0 0.0
0400 31.3 24.8 59 248.8 3126.8 3002.2 4440.8 0.0 0.0
0500 31.2 24.5 59 248.8 3085.5 3097.5 4565.9 0.0 0.0
0600 31.5 24.7 60 248.8 3065.1 2975.4 4416.6 0.0 0.0
0700 32.2 24.6 59 248.8 3066.0 3008.1 4457.7 0.0 0.0
0800 33.4 24.6 59 248.8 3094.5 3032.8 4485.5 0.0 0.0
0900 35.2 24.5 58 248.8 3151.3 3137.5 4609.9 0.0 0.0
1000 37.3 24.5 57 248.8 3283.6 3250.6 4736.7 0.0 0.0
1100 39.6 24.6 56 248.8 3387.7 3348.9 4846.3 0.0 0.0
1200 41.8 24.6 55 248.8 3484.2 3425.6 4929.5 0.0 0.0
1300 43.5 24.6 54 248.8 3581.5 3510.8 5023.0 0.0 0.0
1400 44.6 24.7 53 248.8 3660.4 3580.5 5099.5 0.0 0.0
1500 45.0 24.6 53 248.8 3711.3 3658.6 5189.1 0.0 0.0
1600 44.6 24.9 53 248.8 3727.2 3568.8 5077.9 0.0 0.0
1700 43.6 24.8 53 248.8 3716.1 3609.2 5130.6 0.0 0.0
1800 42.1 24.8 54 248.8 3676.7 3545.3 5050.5 0.0 0.0
1900 40.3 24.7 54 248.8 3624.3 3527.7 5033.8 0.0 0.0
2000 38.5 24.8 55 248.8 3567.9 3437.2 4931.4 0.0 0.0
2100 37.0 24.8 55 248.8 3534.4 3414.9 4903.6 0.0 0.0
2200 35.6 24.9 55 248.8 3503.7 3372.8 4858.7 0.0 0.0
2300 34.5 24.7 56 248.8 3410.2 3348.5 4845.1 0.0 0.0
ZONE: Zone 10
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 33.7 24.6 71 192.2 1915.6 1815.2 3262.0 0.0 0.0
0100 33.0 24.5 72 192.2 1844.1 1794.3 3241.5 0.0 0.0
0200 32.3 24.4 72 192.2 1772.3 1758.1 3201.6 0.0 0.0
0300 31.8 24.4 74 192.2 1709.9 1673.3 3096.7 0.0 0.0
0400 31.3 24.5 75 192.2 1657.2 1591.8 2993.9 0.0 0.0
0500 31.2 24.4 75 192.2 1622.9 1594.6 3001.7 0.0 0.0
0600 31.5 24.5 76 192.2 1615.9 1542.0 2932.4 0.0 0.0
0700 32.2 24.4 75 192.2 1636.4 1604.9 3014.5 0.0 0.0
0800 33.4 24.4 74 192.2 1693.5 1654.7 3075.2 0.0 0.0
0900 35.2 24.6 74 192.2 1787.8 1666.8 3081.9 0.0 0.0
1000 37.3 24.6 71 192.2 1921.1 1807.2 3253.4 0.0 0.0
1100 39.6 24.6 69 192.2 2082.7 1951.2 3425.8 0.0 0.0
1200 41.8 24.5 66 192.2 2241.3 2137.1 3650.9 0.0 0.0
1300 43.5 24.7 65 192.2 2387.1 2225.0 3750.6 0.0 0.0
1400 44.6 24.6 63 192.2 2526.2 2399.2 3953.6 0.0 0.0
1500 45.0 24.5 61 192.2 2627.5 2543.1 4127.3 0.0 0.0
1600 44.6 24.6 61 192.2 2666.3 2542.9 4123.8 0.0 0.0
1700 43.6 24.6 61 192.2 2648.4 2516.2 4091.3 0.0 0.0
1800 42.1 24.7 62 192.2 2568.5 2408.2 3967.1 0.0 0.0
1900 40.3 24.7 64 192.2 2447.6 2294.4 3832.9 0.0 0.0
2000 38.5 24.7 66 192.2 2322.6 2175.8 3691.9 0.0 0.0
2100 37.0 24.6 67 192.2 2216.1 2123.2 3633.7 0.0 0.0
2200 35.6 24.6 68 192.2 2102.2 1994.1 3477.5 0.0 0.0
2300 34.5 24.6 70 192.2 1993.8 1889.3 3351.5 0.0 0.0
ZONE: Zone 11
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 33.7 24.6 60 427.6 5344.4 5218.9 7886.3 0.0 0.0
0100 33.0 24.6 61 427.6 5194.0 5092.0 7741.8 0.0 0.0
0200 32.3 24.8 62 427.6 5028.9 4823.4 7421.9 0.0 0.0
0300 31.8 24.5 62 427.6 4878.2 4846.9 7468.0 0.0 0.0
0400 31.3 24.6 64 427.6 4747.8 4648.2 7232.1 0.0 0.0
0500 31.2 24.5 64 427.6 4657.4 4578.9 7155.3 0.0 0.0
0600 31.5 24.4 64 427.6 4625.7 4609.1 7198.2 0.0 0.0
0700 32.2 24.5 64 427.6 4653.0 4593.4 7177.3 0.0 0.0
0800 33.4 24.6 64 427.6 4757.3 4603.6 7179.2 0.0 0.0
0900 35.2 24.6 62 427.6 4939.2 4822.5 7437.3 0.0 0.0
1000 37.3 24.7 61 427.6 5194.4 4996.1 7629.7 0.0 0.0
1100 39.6 24.6 59 427.6 5501.5 5340.6 8016.1 0.0 0.0
1200 41.8 24.7 57 427.6 5797.8 5610.4 8323.6 0.0 0.0
1300 43.5 24.7 56 427.6 6032.4 5830.9 8580.2 0.0 0.0
1400 44.6 24.7 55 427.6 6203.0 5980.9 8747.3 0.0 0.0
1500 45.0 24.7 54 427.6 6288.3 6104.5 8889.7 0.0 0.0
1600 44.6 24.8 55 427.6 6276.0 6041.8 8813.5 0.0 0.0
1700 43.6 24.9 55 427.6 6305.2 5972.7 8725.9 0.0 0.0
1800 42.1 24.8 54 427.6 6379.0 6098.3 8873.0 0.0 0.0
1900 40.3 24.8 54 427.6 6407.1 6131.1 8911.0 0.0 0.0
2000 38.5 24.8 54 427.6 6380.8 6109.7 8886.9 0.0 0.0
2100 37.0 24.8 55 427.6 6288.2 6021.0 8780.6 0.0 0.0
2200 35.6 24.8 56 427.6 6010.4 5794.3 8533.0 0.0 0.0
2300 34.5 24.6 59 427.6 5487.7 5371.6 8059.7 0.0 0.0
ZONE: Zone 12
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 33.7 24.9 55 359.9 4664.1 4505.3 6100.9 0.0 0.0
0100 33.0 24.6 55 359.9 4599.2 4537.1 6145.6 0.0 0.0
0200 32.3 24.5 55 359.9 4534.8 4514.3 6126.7 0.0 0.0
0300 31.8 24.5 56 359.9 4478.2 4446.6 6052.0 0.0 0.0
0400 31.3 24.7 57 359.9 4430.1 4324.1 5908.5 0.0 0.0
0500 31.2 24.5 56 359.9 4397.1 4388.1 5991.3 0.0 0.0
0600 31.5 24.6 57 359.9 4386.3 4314.6 5903.8 0.0 0.0
0700 32.2 24.6 57 359.9 4398.0 4327.8 5919.3 0.0 0.0
0800 33.4 24.6 57 359.9 4439.2 4368.6 5964.5 0.0 0.0
0900 35.2 24.7 56 359.9 4510.6 4400.3 5995.1 0.0 0.0
1000 37.3 24.7 54 359.9 4754.3 4645.5 6266.4 0.0 0.0
1100 39.6 24.7 53 359.9 5001.6 4891.4 6535.9 0.0 0.0
1200 41.8 24.7 51 359.9 5191.0 5102.1 6767.5 0.0 0.0
1300 43.5 24.6 50 359.9 5321.9 5261.0 6942.5 0.0 0.0
1400 44.6 24.9 50 359.9 5391.7 5192.9 6852.8 0.0 0.0
1500 45.0 24.7 50 359.9 5390.0 5301.3 6980.4 0.0 0.0
1600 44.6 24.8 50 359.9 5347.8 5225.8 6894.1 0.0 0.0
1700 43.6 25.0 51 359.9 5311.9 5116.5 6766.7 0.0 0.0
1800 42.1 24.6 51 359.9 5238.2 5174.0 6842.4 0.0 0.0
1900 40.3 24.9 52 359.9 5139.5 4969.6 6607.6 0.0 0.0
2000 38.5 24.8 52 359.9 5032.3 4902.1 6536.6 0.0 0.0
2100 37.0 24.8 53 359.9 4931.5 4805.5 6431.5 0.0 0.0
2200 35.6 24.7 54 359.9 4830.0 4732.3 6353.5 0.0 0.0
2300 34.5 24.5 54 359.9 4735.5 4742.2 6377.2 0.0 0.0
ZONE: Zone 13
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 33.7 24.4 54 355.5 4668.8 4674.3 6310.6 0.0 0.0
0100 33.0 24.7 55 355.5 4609.3 4513.0 6121.3 0.0 0.0
0200 32.3 24.7 56 355.5 4550.2 4456.3 6059.5 0.0 0.0
0300 31.8 24.5 55 355.5 4498.2 4476.3 6090.6 0.0 0.0
0400 31.3 24.6 56 355.5 4453.7 4386.9 5987.6 0.0 0.0
0500 31.2 24.7 57 355.5 4422.5 4327.8 5919.7 0.0 0.0
0600 31.5 24.5 56 355.5 4410.6 4390.0 5997.4 0.0 0.0
0700 32.2 24.6 56 355.5 4418.3 4340.7 5937.6 0.0 0.0
0800 33.4 24.6 56 355.5 4451.8 4376.6 5977.3 0.0 0.0
0900 35.2 24.7 56 355.5 4511.4 4412.7 6014.5 0.0 0.0
1000 37.3 24.7 54 355.5 4741.1 4638.5 6263.9 0.0 0.0
1100 39.6 24.6 52 355.5 4972.3 4911.0 6557.5 0.0 0.0
1200 41.8 25.0 52 355.5 5146.1 4944.2 6587.0 0.0 0.0
1300 43.5 24.7 50 355.5 5265.0 5184.0 6859.8 0.0 0.0
1400 44.6 24.7 50 355.5 5326.2 5222.0 6898.0 0.0 0.0
1500 45.0 24.9 50 355.5 5320.6 5145.4 6805.3 0.0 0.0
1600 44.6 24.7 50 355.5 5280.1 5202.2 6876.3 0.0 0.0
1700 43.6 24.8 50 355.5 5249.7 5131.1 6794.7 0.0 0.0
1800 42.1 24.8 51 355.5 5185.5 5068.8 6726.5 0.0 0.0
1900 40.3 24.6 51 355.5 5098.4 5050.0 6712.6 0.0 0.0
2000 38.5 24.6 52 355.5 5003.1 4961.4 6616.5 0.0 0.0
2100 37.0 24.5 52 355.5 4912.6 4896.9 6549.7 0.0 0.0
2200 35.6 24.8 54 355.5 4820.7 4688.3 6307.6 0.0 0.0
2300 34.5 24.8 54 355.5 4734.1 4597.4 6207.3 0.0 0.0
ZONE: Zone 14
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 33.7 24.8 54 357.8 4866.5 4705.5 6377.7 0.0 0.0
0100 33.0 24.7 54 357.8 4800.5 4699.6 6376.3 0.0 0.0
0200 32.3 24.9 55 357.8 4724.0 4547.6 6201.0 0.0 0.0
0300 31.8 24.7 55 357.8 4652.2 4540.5 6200.2 0.0 0.0
0400 31.3 24.5 55 357.8 4588.8 4561.6 6233.1 0.0 0.0
0500 31.2 24.7 56 357.8 4543.2 4446.7 6099.9 0.0 0.0
0600 31.5 24.7 56 357.8 4523.4 4399.2 6044.2 0.0 0.0
0700 32.2 24.4 56 357.8 4529.9 4525.0 6197.3 0.0 0.0
0800 33.4 24.5 55 357.8 4570.8 4527.2 6196.4 0.0 0.0
0900 35.2 24.8 56 357.8 4646.8 4499.4 6154.6 0.0 0.0
1000 37.3 24.5 54 357.8 4813.7 4780.8 6466.9 0.0 0.0
1100 39.6 24.9 54 357.8 4946.9 4752.2 6427.8 0.0 0.0
1200 41.8 24.9 53 357.8 5069.4 4861.0 6543.6 0.0 0.0
1300 43.5 24.7 51 357.8 5190.1 5102.1 6818.9 0.0 0.0
1400 44.6 24.7 51 357.8 5286.2 5188.5 6912.0 0.0 0.0
1500 45.0 24.7 50 357.8 5346.1 5239.0 6965.6 0.0 0.0
1600 44.6 24.6 50 357.8 5361.1 5290.6 7025.3 0.0 0.0
1700 43.6 24.9 51 357.8 5341.8 5156.1 6867.0 0.0 0.0
1800 42.1 24.5 50 357.8 5286.9 5244.9 6977.8 0.0 0.0
1900 40.3 24.7 51 357.8 5214.9 5082.8 6791.9 0.0 0.0
2000 38.5 24.8 52 357.8 5137.4 4977.4 6672.6 0.0 0.0
2100 37.0 24.6 52 357.8 5087.8 5005.4 6712.1 0.0 0.0
2200 35.6 24.8 53 357.8 5042.2 4904.3 6595.3 0.0 0.0
2300 34.5 24.5 53 357.8 4923.1 4883.4 6583.2 0.0 0.0
ZONE: Zone 15
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 33.7 24.5 54 337.8 4692.4 4690.4 6583.9 0.0 0.0
0100 33.0 24.7 55 337.8 4638.6 4529.8 6393.4 0.0 0.0
0200 32.3 24.8 56 337.8 4582.0 4444.9 6295.8 0.0 0.0
0300 31.8 24.5 55 337.8 4529.0 4531.5 6408.2 0.0 0.0
0400 31.3 24.7 56 337.8 4481.2 4360.4 6204.3 0.0 0.0
0500 31.2 24.5 56 337.8 4442.6 4414.6 6275.7 0.0 0.0
0600 31.5 24.7 57 337.8 4417.3 4286.1 6120.8 0.0 0.0
0700 32.2 24.4 56 337.8 4405.9 4411.7 6277.1 0.0 0.0
0800 33.4 24.7 57 337.8 4412.4 4292.9 6130.5 0.0 0.0
0900 35.2 24.7 56 337.8 4437.7 4333.5 6177.1 0.0 0.0
1000 37.3 24.6 55 337.8 4611.4 4542.4 6415.2 0.0 0.0
1100 39.6 24.9 55 337.8 4746.2 4551.1 6410.1 0.0 0.0
1200 41.8 24.6 53 337.8 4849.7 4807.1 6709.3 0.0 0.0
1300 43.5 24.8 53 337.8 4947.0 4773.5 6657.2 0.0 0.0
1400 44.6 24.5 52 337.8 5016.4 4986.0 6906.3 0.0 0.0
1500 45.0 24.8 52 337.8 5048.2 4909.5 6810.1 0.0 0.0
1600 44.6 24.9 52 337.8 5056.6 4864.3 6758.7 0.0 0.0
1700 43.6 24.6 51 337.8 5061.8 5024.7 6947.0 0.0 0.0
1800 42.1 24.9 52 337.8 5040.0 4844.3 6731.4 0.0 0.0
1900 40.3 24.5 52 337.8 4999.7 4979.6 6898.9 0.0 0.0
2000 38.5 24.8 53 337.8 4946.2 4799.9 6687.2 0.0 0.0
2100 37.0 24.6 53 337.8 4903.8 4863.4 6769.1 0.0 0.0
2200 35.6 24.7 53 337.8 4857.8 4744.6 6629.8 0.0 0.0
2300 34.5 24.9 54 337.8 4745.3 4574.7 6434.5 0.0 0.0
ZONE: Zone 16
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 33.7 24.6 59 654.5 8356.0 8203.5 12269.6 0.0 0.0
0100 33.0 24.8 60 654.5 8168.4 7875.5 11895.3 0.0 0.0
0200 32.3 24.6 60 654.5 7965.1 7816.9 11844.8 0.0 0.0
0300 31.8 24.6 61 654.5 7776.7 7656.8 11665.7 0.0 0.0
0400 31.3 24.7 62 654.5 7610.2 7430.3 11398.3 0.0 0.0
0500 31.2 24.6 62 654.5 7485.3 7383.4 11354.8 0.0 0.0
0600 31.5 24.6 63 654.5 7419.7 7302.1 11260.3 0.0 0.0
0700 32.2 24.7 63 654.5 7414.2 7165.2 11087.6 0.0 0.0
0800 33.4 24.7 63 654.5 7486.7 7254.5 11191.9 0.0 0.0
0900 35.2 24.6 62 654.5 7638.3 7538.7 11536.3 0.0 0.0
1000 37.3 24.7 61 654.5 7890.8 7672.7 11677.5 0.0 0.0
1100 39.6 24.6 60 654.5 8209.4 8044.6 12108.1 0.0 0.0
1200 41.8 24.5 58 654.5 8525.7 8457.8 12573.8 0.0 0.0
1300 43.5 24.5 57 654.5 8814.2 8728.5 12893.1 0.0 0.0
1400 44.6 24.7 56 654.5 9082.9 8826.7 12985.5 0.0 0.0
1500 45.0 24.7 55 654.5 9277.6 9080.8 13278.2 0.0 0.0
1600 44.6 24.7 55 654.5 9361.7 9086.1 13275.9 0.0 0.0
1700 43.6 24.9 55 654.5 9445.9 9044.9 13216.1 0.0 0.0
1800 42.1 24.7 55 654.5 9524.9 9282.5 13501.4 0.0 0.0
1900 40.3 24.6 54 654.5 9525.9 9424.6 13675.7 0.0 0.0
2000 38.5 24.9 55 654.5 9472.8 9070.5 13246.9 0.0 0.0
2100 37.0 24.7 55 654.5 9365.1 9143.4 13341.8 0.0 0.0
2200 35.6 24.8 56 654.5 9067.0 8766.6 12910.8 0.0 0.0
2300 34.5 24.6 58 654.5 8531.6 8417.8 12532.9 0.0 0.0
ZONE: Zone 17
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 33.7 24.6 68 97.3 982.8 922.8 1520.0 0.0 0.0
0100 33.0 24.4 68 97.3 945.6 938.8 1543.5 0.0 0.0
0200 32.3 24.6 71 97.3 908.8 852.8 1438.0 0.0 0.0
0300 31.8 24.5 71 97.3 876.5 847.0 1433.6 0.0 0.0
0400 31.3 24.4 72 97.3 848.9 827.4 1411.5 0.0 0.0
0500 31.2 24.4 72 97.3 830.1 815.0 1397.5 0.0 0.0
0600 31.5 24.4 72 97.3 824.3 812.3 1394.9 0.0 0.0
0700 32.2 24.4 72 97.3 831.7 813.0 1395.3 0.0 0.0
0800 33.4 24.3 71 97.3 856.4 843.1 1431.5 0.0 0.0
0900 35.2 24.5 71 97.3 898.9 862.5 1452.3 0.0 0.0
1000 37.3 24.6 66 97.3 1067.5 996.3 1603.9 0.0 0.0
1100 39.6 24.7 61 97.3 1234.5 1150.4 1782.5 0.0 0.0
1200 41.8 24.7 58 97.3 1354.1 1281.8 1934.9 0.0 0.0
1300 43.5 24.7 56 97.3 1428.5 1349.7 2011.8 0.0 0.0
1400 44.6 24.6 55 97.3 1458.1 1400.1 2068.9 0.0 0.0
1500 45.0 24.7 56 97.3 1439.6 1365.3 2029.1 0.0 0.0
1600 44.6 24.7 57 97.3 1399.6 1315.5 1971.0 0.0 0.0
1700 43.6 24.8 58 97.3 1372.8 1286.2 1936.9 0.0 0.0
1800 42.1 24.7 59 97.3 1326.6 1254.3 1901.2 0.0 0.0
1900 40.3 24.7 60 97.3 1266.8 1189.6 1826.0 0.0 0.0
2000 38.5 24.6 62 97.3 1202.6 1149.6 1781.4 0.0 0.0
2100 37.0 24.6 63 97.3 1142.2 1097.9 1722.3 0.0 0.0
2200 35.6 24.6 65 97.3 1081.1 1019.4 1632.7 0.0 0.0
2300 34.5 24.5 67 97.3 1023.9 986.5 1596.4 0.0 0.0