The Main Firefighting Systems

 Water system

 Manual
 Hose Cabinet
 Fire Hydrant
 Fire Extinguishers

 Automatic
 Sprinkler System
 Spray System
 Water Mist System

 Gas system

 Manual
 Fire Extinguishers

 Automatic
 Co₂ Network
 FM200 Network
 Novec 1230
 Aerosol

 Foam system

 Manual
 Fire Extinguishers

 Automatic
 Foam Network

ENG/ AHMED M. SHUHAYB MEP BIM ENGINEER


AHMED SHUAHYB OFFICE Tel: 0020-1093460618
ENGINEERING CONSULTANT Email: A.shuhayb@asec.work

Pipe In Firefighting

 Pipe Types
 Seamless Black steel ‫ﺷ ﻜﺔ اﻟﻤ ﺎە اﻟﺮﻃ ﺔ واﻟﺠﺎﻓﺔ ﺗﻜﻮن ﻣﻀﻐﻮﻃﺔ ﻧﻴ وﺟ‬
 ERW
 CPVC
 HDPE ‫ﺷ ﻜﺔ اﻟﻤ ﺎە اﻟﻤﺪﻓﻮﻧﺔ‬
 Galvanized ‫ف او ﻧﻈﺎم اﻟﺮﺷﺎﺷﺎت اﻟﺠﺎﻓﺔ‬ ‫ﺷ ﻜﺔ اﻟ‬
 Copper
 UPVC ‫ف‬ ‫ﺷ ﻜﺔ اﻟ‬

Bending pipe

o All pipe (R=12D) and (D) is the pipe diameter


o In black steel (D = 2” ↓ → R = 6D)
o In black steel (D = 2.5” ↑ → R = 5D)
 Hanger

ENG/ AHMED M. SHUHAYB MEP BIM ENGINEER


AHMED SHUAHYB OFFICE Tel: 0020-1093460618
ENGINEERING CONSULTANT Email: A.shuhayb@asec.work

 1.5 m – Distance between two Hanger


 Θ 10” – Diam Rod
 Modules = 0.37
 Trapeze Hanger
 2.5”x2.5”x0.25”
 2”

ENG/ AHMED M. SHUHAYB MEP BIM ENGINEER


AHMED SHUAHYB OFFICE Tel: 0020-1093460618
ENGINEERING CONSULTANT Email: A.shuhayb@asec.work

Pump Room

ENG/ AHMED M. SHUHAYB MEP BIM ENGINEER


AHMED SHUAHYB OFFICE Tel: 0020-1093460618
ENGINEERING CONSULTANT Email: A.shuhayb@asec.work

 Electrical Pump

 Diesel Pump

 Jockey Pump

ENG/ AHMED M. SHUHAYB MEP BIM ENGINEER


AHMED SHUAHYB OFFICE Tel: 0020-1093460618
ENGINEERING CONSULTANT Email: A.shuhayb@asec.work

Zone Control Station

Test & Drain Valve

 Siamese Connection

 Min Size 2.5”, 250 GPM.


 Shall not be less than 18 " or more than 48 " above grade.

 Fire Extinguishers

 Dry Powder, Wet Chemical, Co₂


 Lowest height from the ground = 10 cm
 The maximum height if the extinguisher weight is 18 Kg or less = 1.53 m
 The maximum height if the extinguisher weight is more than 18 Kg= 1.07 m

ENG/ AHMED M. SHUHAYB MEP BIM ENGINEER


AHMED SHUAHYB OFFICE Tel: 0020-1093460618
ENGINEERING CONSULTANT Email: A.shuhayb@asec.work

 Hose Cabinet

 Class1

 Hose Rack
 2.5"
 250 GPM
 Min Pressure 6.9 Bar
 Max Pressure 12.1 Bar
 Reinforced Cloth

 Class2

 Hose Reel
 1" :1.5"
 100 GPM
 Min Pressure 4.5 Bar
 Max Pressure 6.9 Bar
 Rubber

 Class3

 Min Pressure 6.9 Bar


 Max Pressure 12.1 Bar
 100 GPM,250 GPM
 1.5" ,2.5"
 Reinforced Cloth
 Rubber

Travel Distance

 39.7 m for Non SPK for 2.5 "

 61 m for SPK for 2.5 "

 39.7 m for SPK 1.5 "

 36.6 m for SPK 1 "

ENG/ AHMED M. SHUHAYB MEP BIM ENGINEER


AHMED SHUAHYB OFFICE Tel: 0020-1093460618
ENGINEERING CONSULTANT Email: A.shuhayb@asec.work

 Pressure Relief Valve -PRV

 Total Pressure = C ∗ P-Shut Off + P-Static


 If total pressure ≤ 12.1 (not required PRV)
 If total pressure > 12.1 (required PRV)
Where:
 P-Static →location of pump and tank ‫ﻏﺎﻟ ﺎ ﻳﻮﺿﻊ ﺼﻔﺮ اﻻ ﺣﺎﻟﺔ ﻟﻮ ﺎن ﻣ ﺴﻮب اﻟﺘﺎﻧﻚ ﻣﺨﺘﻠﻒ ﻣﻊ اﻟﻤﻀﺨﺔ‬
 C→ constant (in case governor =1) (in case no governor =1.21)

 Pressure Reducing Valve -PRV


 ‫ ﺎر‬12.1 ‫ﺣﺎﻟﺔ ﺎن ﺿﻐﻂ اﻟﺸ ﻜﺔ اﻋ ﻣﻦ‬ ‫اﻟﺸ ﻜﺔ‬ ‫ﻳﺘﻢ ﺗﺮﻛﻴ ﺔ ﻗ ﻞ دﺧﻞ اﻟﺰون او اﻟﺼﻨﺎدﻳﻖ او أي ﻣﻜﻮن‬

 Firefighting Tank
 Capacity Tank = GPM (According Calc.) x Time (30 :90 According Hazard)

ENG/ AHMED M. SHUHAYB MEP BIM ENGINEER


‫‪AHMED SHUAHYB OFFICE‬‬ ‫‪Tel: 0020-1093460618‬‬
‫‪ENGINEERING CONSULTANT‬‬ ‫‪Email: A.shuhayb@asec.work‬‬

‫ﻣﻀﺨﺎت اﻟﺤ ﻖ‪- :‬‬ ‫وط اﻟﻮاﺟﺐ ﺗﻮاﻓﺮﻫﺎ‬ ‫اﻟ‬


‫ال ‪ H ،Q‬اﻟﻤﺮادان‪.‬‬ ‫ان ﺗﻌ‬ ‫‪‬‬
‫ﻛﻔﺎءە‪.‬‬ ‫ا‬ ‫اﻟﺠﺰء اﻷوﺳﻂ ﻟﻠﻤﻨﺤ ﻟﺘﻌ‬ ‫ﺠﺐ ﻋﻨﺪ اﺧﺘ ﺎرﻫﺎ ﻻ ﺪ ان ﺗﻜﻮن‬ ‫‪‬‬
‫ﻋﻨﺪ ز ﺎدە ال ‪ Q‬ﻤﻘﺪار ‪ % 150‬ان ﻻ ﻘﻞ ال ‪H‬ﻋﻦ ‪ % 65‬ﻣﻦ ﻗ ﻤﺘﻪ اﻷﺻﻠ ﺔ‪.‬‬ ‫‪‬‬

‫‪Shut down pressure‬ﻻ ﻳ ﺪ ﻋﻦ ‪% 140‬‬ ‫‪‬‬

‫ان ﺗﻜﻮن اﻟﻤﻀﺨﺔ ﺧﻀﻌﺖ ﻟﻼﺧﺘ ﺎر‬ ‫‪‬‬

‫‪ENG/ AHMED M. SHUHAYB‬‬ ‫‪MEP BIM ENGINEER‬‬


AHMED SHUAHYB OFFICE Tel: 0020-1093460618
ENGINEERING CONSULTANT Email: A.shuhayb@asec.work

 Hazard Classifications
 Light Hazard
 Ordinary Hazard (Group 1)
 Ordinary Hazard (Group 2)
 Extra Hazard (Group 1) (Eh1)
 Extra Hazard (Group 2) (Eh2)

 Fire Sprinkler System Types - Alarm Check Valve


 Wet System
 Dry System
 Preaction System
o Single Interlock – ‫ﺣﺴﺎس ﻓﻘﻂ‬
o Double Interlock - ‫ﺣﺴﺎس ورﺷﺎش‬
o Non-Interlock - ‫ﺣﺴﺎس او رﺷﺎش‬
 Deluge System

ACV ‫ﺎﻟ ﺴ ﺔ ل‬ ‫ﻣ ﺎن ﺗﺮﻛ ﺐ وﺻﻠﺔ اﻟﺪﻓﺎع اﻟﻤﺪ‬

ENG/ AHMED M. SHUHAYB MEP BIM ENGINEER


AHMED SHUAHYB OFFICE Tel: 0020-1093460618
ENGINEERING CONSULTANT Email: A.shuhayb@asec.work

‫اﻻﻋﺘ ﺎرات اﻟﺘﺼﻤ ﻤ ﺔ ﻟﻠﺮﺷﺎﺷﺎت‬


Pendent and Upright
Type Hazard Max Max Min Max Min
Area Spacing Spacing Wall Wall
Light 18 m² 4.6 m 2.3 m
Standard Ordinary 12 m² 4.6 m 1.8 m 2.3 m
Extra 8.4 m² 3.7 m 1.85 m
Light 37 m² 6.1 m 3m
Extended Ordinary 37 m² 6.1 m 2.4 m 3m
10 cm
Extra 18.2 m² 4.3 m 2.1 m
‫ﻏ ﻗﺎ ﻞ را ﺎت‬ 12.1 m² 3.7 m 1.8 m 1.85 m
CMSA ‫ﻗﺎ ﻞ ﺪون ﻋﻮارض‬ 12.1 m² 3.7 m 1.8 m 1.85 m
‫ﻗﺎ ﻞ ﻌﻮارض را ﺎت‬ 9.3 m² 3m 1.8 m 1.5 m
Up to 9.1 m 9.3 m² 3.7 m 1.8 m 1.85 m
ESFR
Over 9.1 m 9.3 m² 3m 1.8 m 1.5 m

Side Wall
Type Hazard Area Max- S Max- L Max- W Min - W
Light – N -Com 18 m² 4.3 m 4.3 m 2.1 m
Light - Com 11 m² 4.3 m 3.7 m 1.85 m
Standard
Ordinary – N- Com 9.3 m² 3m 3m 1.5 m
Ordinary – Com 7.4 m² 3m 3m 1.5 m 10 cm
Light – N -Com 37 m² 8.5 m 4.3 m 2.1 m
Extended
Ordinary – N- Com 37 m² 7.3 m 4.3 m 2.1 m

ENG/ AHMED M. SHUHAYB MEP BIM ENGINEER


AHMED SHUAHYB OFFICE Tel: 0020-1093460618
ENGINEERING CONSULTANT Email: A.shuhayb@asec.work

ENG/ AHMED M. SHUHAYB MEP BIM ENGINEER


AHMED SHUAHYB OFFICE Tel: 0020-1093460618
ENGINEERING CONSULTANT Email: A.shuhayb@asec.work

‫اﻟﺤﺴ ــﺎ ﺎت اﻟﻬ ﺪروﻟ ﻜ ــﺔ ﻟﻤﻨﻈﻮﻣ ــﺔ اﻟﺤ ﻖ‬


 Sprinkler Calc.

 Hazard Classification
 Density = 0.1, 0.15, 0.2 gpm/ft²
 Area of sprinkler operation =1500 ft²
 No. of Sprinkler in space (Nr) = Ar / As
 No. of sprinkler in Operation (Ns) = Da / As
 Number of Sprinkler on Branch line (Nb) = 1.2√Da / S
 Qs= Ns x Flow per sprinkler
 Flow per sprinkler= Dd / As
 Q= K√P
K= 5.6, 8, … According to Ceiling Height – FM Global, P not less than 7 psi

 QT =Qs + Hose Allowance


 HP = Hs + HR + HF

ENG/ AHMED M. SHUHAYB MEP BIM ENGINEER


AHMED SHUAHYB OFFICE Tel: 0020-1093460618
ENGINEERING CONSULTANT Email: A.shuhayb@asec.work

 Hose Cabinet Calc.

Vertical Riser - Q=500 gpm, HR =6.9 Bar

Horizontal Riser - Q=750 gpm, HR =6.9 Bar

Vertical Riser

Many Hoses in floor

Sprinklers and Hoses

Q=1000 gpm, HR =6.9 Bar

Vertical Riser

Many Hoses in floor

Non-Sprinklers and Hoses Only

Q=1250 gpm, HR =6.9 Bar

ENG/ AHMED M. SHUHAYB MEP BIM ENGINEER


AHMED SHUAHYB OFFICE Tel: 0020-1093460618
ENGINEERING CONSULTANT Email: A.shuhayb@asec.work

‫ﻋﻨﺪ أﺧﺪ اﻟﺼﻨﺪوق ﻣﻦ اﻟﺼﺎﻋﺪ اﻟﺜﺎ ﻣﻤﻜﻦ ﺗﺄﺧﺬە ﻣﻦ أي دور وﻟ ﺲ اﻷ ﻌﺪ‬ 

Area ≤ 8000 ft2

Non-Sprinklers and Hoses Only

Q=1250 gpm, HR =6.9 Bar

Area ≤ 8000 ft2

Sprinklers and Hoses

Q=1000 gpm, HR =6.9 Bar

Area > 8000 ft2

Non-Sprinklers and Hoses Only

Q=1250 gpm, HR =6.9 Bar

Area > 8000 ft2

Sprinklers and Hoses

Q=1000 gpm, HR =6.9 Bar

2 Part – High and Low

Area ≤ 8000 ft2

Non-Sprinklers – Hoses Only

ENG/ AHMED M. SHUHAYB MEP BIM ENGINEER


AHMED SHUAHYB OFFICE Tel: 0020-1093460618
ENGINEERING CONSULTANT Email: A.shuhayb@asec.work

 Gas Calc.

 Co2 - mass
= Flooding Factor x Volume x Conversion Factor + Fan Leakage (1 min) + Leakage Rate

Applications where temperature of the enclosure Above 200°F (93°C)

For each additional 5°F above 200°F - 1 % increase in the calculated total
quantity of carbon dioxide shall be provided.

Applications where temperature of the enclosure below 0°F (−18°C)

For each 1°F below 0°F - 1 % increase in the calculated total quantity of
carbon dioxide shall be provided

ENG/ AHMED M. SHUHAYB MEP BIM ENGINEER


AHMED SHUAHYB OFFICE Tel: 0020-1093460618
ENGINEERING CONSULTANT Email: A.shuhayb@asec.work

 FM200 - mass

W = Room Volume X Flooding Factor Cf X Design Factor Calt

W= V/S x (C/100-C)

• V = Net Hazard Volume [m³]


• S = Specific vapor volume [m³/kg]
• S = 0.1269 + 0.0005131 x T (at sea level!)
• C = Concentration [%]

ENG/ AHMED M. SHUHAYB MEP BIM ENGINEER