SUBHEAD: ELECTRIC LOAD CALCULATION AND SELECTION OF TRANSFORMER AND EMERGENCY GENSET
A ELECTRIC LOAD CALCULATION
S. No. Description No. of Light, & Power A C Load Total Load Total Light & Total A C Connected Diversity Operational Essential No. of Total Energy
Unit load Per Unit Per Unit per Unit Power load Load load (KW) factor load (KW) load KW Hours Comsumed
per day in a day
1. Residential
1.1 ALL 1 BHK 70 0.50 3.50 4.00 35 245 280 0.5 140 140 10 1400
1.2 ALL 2 BHK 182 0.75 5.25 6.00 136.5 955.5 1092 0.5 546 546 10 5460
1.3 ALL 3 BHK 238 1.00 7.00 8.00 238 1666 1904 0.5 952 952 10 9520
2. COMMON AND COMMERCIAL SPACE BUA IN SQMT
2.1 CLUB HOUSE 490.99 1 4.00 1.00 25 4 25 29 0.5 14.5 14.5 10 145
2.2 PARKING AREA ON GROUND FLOOR IN PONT 3306.38 119 0.02 0.00 0 2.37 0 2.37 0.5 1.19 1.19 10 11.86
2.3 CORRIDOR AREA 476 POINT 0.015 0 0.02 7.14 0 7.14 0.9 6.43 6.43 16 102.82
3. UTILITIES
3.1 1 STREACHER LIFT (16P) IN EACH BLOCK 5 15 0 15.00 75 0 75 0.8 60 60 16 960
3.2 1 PESSENGERS LIFT (6P) IN EACH BLOCK 5 7 0 7.00 35 0 35 0.8 28 28 16 448
3.3 1 PESSENGERS LIFT (6P) IN CLUB HOUSE 1 7 0 7.00 7 0 7 0.8 5.6 5.6 8 44.8
3.4 WATER SUPPLY PUMPS 5 5 0 5.00 25 0 25 0.8 20 20 6 120
3.5 LANDSCAPE LIGHTING LOAD 1 5 0 5.00 5 0 5 0.8 4 4 8 32
3.6 FAÇADE & STREET LIGHTING LOAD 1 5 0 5.00 5 0 5 0.8 4 4 8 32
3.7 SEWERAGE TREATMENT PLANTS (300 KLD) 1 15 0 15.00 15 0 15 0.8 12 12 10 120
3.8 FIRE FIGHTING (JOCKEY PUMP) 1 10 0 10.00 10 0 10 0.8 8 8 0 0
TOTAL LOAD (1‐3) 600.01 2891.5 3491.51 1801.71 18396.48
KWH
B MAXIMUM DEMAND
Total load requirement = 1801.71 KW
Applying a power factor of 0.80 = 2252.14 KWA
Considering 80% loading of rated transformer capacity, minimum rating of transformer required = 2815.18 KVA
HENCE 01 NOS. OF 2500 KVA TRANSFORMER CAN BE SELECTED :‐ >>FOR ALL TYPE 1 TO 7 FLATS<< 1# 3000 KVA