FUNCTIONAL SPECIFICATION
20176.VAR.ELE.FUN
This document is property of Eni S.p.A. Eploration & Production Division. It shall neither be shown to Third Parties not used for purposes other than those for which it has been sent.
20176 EQP.ELE.FUN
Eni S.p.A. Rev. 1 June 2003
Exploration & Production Division Sheet 2 di 18
FOREWORD
INDEX
1. GENERAL……………………………………………………………………………..…….……4
1.1 SCOPE…………………………………………………………………………………..…..……4
1.2 NORMATIVE REFERENCES…………………………………………………………..…..…..4
1. GENERAL
1.1. SCOPE
This specification sets out the minimum requirements and the inspection plans for the
supply of the "Wind Energy Generation Systems" for onshore and offshore installations.
Any other additional information not covered by this specification will be specified in the
rules and publications in force and in the project technical documentation, particularly:
– Data Sheets
The technical requirements of this functional specification are based upon considerations
of performances and functionality, therefore the instructions contained in this document
are not meant to be discriminatory.
Any alternative suggestions will be considered, provided that the compliance with what
required in this document is satisfied both from functional and performance points of
view.
The main Normative References that entirely define the wind energy generation system
are herewith listed.
References are made to the Directives (when applicable) and European Normative
references (EN = CEI EN), in the absence of the above, National CEI/CEI UNEL
normative references and/or IEC publications relating to the place of installation and/or as
stated by the contract.
In any case, all the rules, fixed by the legislative provision acts and regulations in force, if
those exist, and under the jurisdiction of which the plants are installed, should be
respected.
Electric systems and equipment shall be in conformity with Directive 89/336/CEE, revised
and supplemented with directives 92/31/CEE, 93/68/CEE and 93/97/CEE, implemented
with D.Lgs. 615/96.
The preceding D.Lgs. 476/92 was repealed with exception for art. 14, comma 2.
Directive 73/23 CEE for electric material intended to be utilised within such voltage limits
as (50÷1000 Vac and 75÷1500 Vdc), implemented with legislative act L.791/77.
Its subsequent revision with directive 93/68 CEE, was implemented with D.Lgs 626/96.
A.W.E.A. TITLE
American Wind Energy Association ( NOTE 1 )
Standard Performances Testing of wind energy
A.W.E.A. 1.1 conversion systems
Standard procedure for measurement of acoustical
A.W.E.A. 2.1 emission from wind turbine generation systems: TIER I
Design Criteria recommended Practice Wind Energy
A.W.E.A. 3.1 Conversion System
Recommended Practice for the installation of wind
A.W.E.A. 6.1 conversion system
Standard procedure for meteorological measurements
A.W.E.A. 8.1 at a potential wind turbine site
Expert group study on recommended practice for wind
I.E.A. turbine testing and evaluation .8. Glossary of terms
International Energy Agency
20176 EQP.ELE.FUN
Eni S.p.A. Rev. 1 June 2003
Exploration & Production Division Sheet 6 di 18
Reference to the Normative References from paragraph 1.2 will be made for definitions,
symbols and abbreviations.
TABLE 1
SYMBOLS AND ABBREVIATIONS
MEASUR.
DEFINITION DESCRIPTION SYMBOL
UNIT
A system that includes one or more windmills,
Eolic System the relevant support systems, and a control --- ---
panel
Eolic Generator/ A windmill coupled with an electric generator --- ---
Windmill
A machinery that transforms the eolic energy
into rotational mechanic energy, complete with a
rudder device which is properly adjusted on the
Windmill main shaft, allowing the system correct --- ---
alignment.
Environment The installation site temperature in stagnant air
temperature conditions T °C
The maximum power generated by the eolic
Peak power generator on a proper load at the environment Wp W
temperature conditions.
Idle voltage supplied by the eolic generator, at
Empty voltage the environment temperature (T) Voc V
The design voltage of the generator
Rated voltage Vn V
Short circuit current The short circuit current generated by the eolic
generator. Isc A
The period of time in which there is not enough
Wind calmness wind to generate energy, expressed in days. --- ---
The wind generation system components will be designed and built according to the
installation site environmental conditions specified on the Data Sheet.
20176 EQP.ELE.FUN
Eni S.p.A. Rev. 1 June 2003
Exploration & Production Division Sheet 7 di 18
– The complete charge, and the constant charge of the accumulator batteries
simultaneously to power supply of loads.
– The power supply of loads by d.c. with continuity, every hour, day, and season of the
year, and under whatever wind conditions.
The system will be designed as to guarantee its performance under functional normal
conditions, and to ensure with a high level of certainty the power supply, even under poor
wind conditions during a period of time, and with a voltage specified on the Data Sheet.
The Supplier shall provide the Company with the calculation method applied for the sizing
of the system, taking into consideration the following parameters:
f) Energy necessary for feeding selected loads (Wh/day), based on the average daily
values in “no wind” conditions;
l) Safety coefficient.
It is the energy increase in relation to the energy absorbed from the users, which the
generator must produce in a year, to provide for all the different wind variations from
one year to the next one, and necessary to charge the batteries in a relatively short
period of time.
The Supplier shall specify the source of the values and data given in c) and d), if not
indicated in the Project Specifications.
20176 EQP.ELE.FUN
Eni S.p.A. Rev. 1 June 2003
Exploration & Production Division Sheet 8 di 18
The components, and the materials used shall be in compliance to the installation site,
the service conditions, and the transport conditions.
The eolic generation system, object of this Functional Specification, usually will include:
– Windmill
– Electric Generator
– Battery charge and d.c. power distribution control panel (if specified in the Data
Sheet)
2.4.3.3. Windmills
The windmills will be classified according to the rotor axis orientation with respect to the
wind direction; that is:
– Rotor with horizontal and parallel axis to the wind direction (frontal).
– Constant speed.
– Variable speed.
Unless otherwise specified on the Data Sheet, the components characteristics shall be:
– Aluminium cover for onshore installations, and in stainless steel AISI 304 (at least) for
offshore installations.
– The rotor axis and the bolts and nuts in stainless steel AISI 304.
The windmills shall be provided with an automatic breaking system in case of strong wind
gusts.
FIGURE 1
The horizontal axis eolic machine will include the following items:
– A vessel called "nacelle" containing the electric generator, the speed multiplier,
and some control equipment.
– The rotor, made up by a hub, on which from 1 to 3 blades will be mounted. It will
be possible to place it windward or leeward with respect to the support.
– The rudder for the orientation of the machine according to the wind direction.
– The control system, the instruments, and the cables necessary to transport the
produced electric energy, and to transmit the necessary signals.
FIGURE 2
20176 EQP.ELE.FUN
Eni S.p.A. Rev. 1 June 2003
Exploration & Production Division Sheet 11 di 18
The vertical axis eolic machine shall include the following items:
– Two or three curved blades with both the extremities connected to the shaft.
– A basement, containing the speed multiplier, and the electric generator, if any.
FIGURE 3
20176 EQP.ELE.FUN
Eni S.p.A. Rev. 1 June 2003
Exploration & Production Division Sheet 12 di 18
– variable speed and constant frequency generators, coupled with variable speed
windmills;
When not otherwise specified in the Data Sheet, the characteristics of the various
components shall be:
– aluminium enclosure for onshore installations or in stainless steel, at least AISI 304,
for offshore installations;
The tower shall be sized for the loads and stresses to which it is subjected (horizontal
component of the rotating machine and horizontal wind force), both in normal conditions
and in presence of severe atmospheric perturbations, as gusts, storms, hail, lightning, ice
or sand storms and salty fogs.
It shall be of the self-supporting type, fabricated with steel bars or tubes, suitably treated
for the environment conditions and in conformity with the provisions of the Project
Specification. In addition, the support structure shall be enough rigid and shall not
represent an obstacle for the flow of the wind and shall not produce turbulence
phenomena among the blades and the structure itself.
The adjustment and control system will include a number of non-dissipation units with
adjustable intervention threshold, equal to the number of windmills making up the eolic
generation system.
Each unit shall provide the control of the Pb or Ni-Cd accumulator batteries voltage, in
accordance with the Data Sheet.
Each single unit and related auxiliary equipment shall be installed on a panel and
assembled on a 19’’ rotating rack.
20176 EQP.ELE.FUN
Eni S.p.A. Rev. 1 June 2003
Exploration & Production Division Sheet 13 di 18
A temperature sensor properly placed within the battery room will be connected to the
system for the automatic control of the voltage value at the battery charge end.
Each unit shall act on its relevant windmill, which shall be inserted on the load in function
of the value of voltage in the batteries.
Each unit is functionally independent of the others, in order that the failure of one of the
units does not interfere with the operations of the others.
The electric charge regulator shall provide at least the following operating functions:
1) To rectify the a.c. power supplied by the generator, when requested in the Data
Sheet, through a silicon diodes Gretz bridges.
2) Selection of battery type and its related voltage parameters, which shall dictate
the various automatic interventions.
VE > VB
The regulator will stop the charge phase when the following conditions are
met:
VE ≥ V Max.
Ic = 0
where:V Max = Battery maximum charge voltage (given by the thermowell,
or by the pre-set maximum value)
Ic = Current between the panel and the battery
4) For Pb batteries, after each relatively deep discharge (up to 70 - 80% charge
status), the regulator shall recharge up to the compensation voltage and
maintain the battery at the buffer voltage.
20176 EQP.ELE.FUN
Eni S.p.A. Rev. 1 June 2003
Exploration & Production Division Sheet 14 di 18
b) Control System
Unless otherwise specified on the Data Sheets, the control system shall at least
provide the functions shown on Table 3.
TABLE. 3
Whenever required on the Data Sheets, this panel includes two sections, and is
integrated on the same Regulation and Control System Panel.
– Interconnections section: it shall include one or more terminal blocks for the
incoming and the outgoing of all the cables and the Panel internal cabling.
– D.C. distribution section: this section includes all the components (switches,
relays, etc.) for the power supply and the storage power supply in accordance
with the Data Sheet. The following control instruments, protection and
disconnecting devices, can be mounted on this panel in compliance with the
project specifications:
The charges connected to the panel must allow operating functions within the
battery voltage variation field; otherwise, a proper voltage stabiliser must be
inserted.
20176 EQP.ELE.FUN
Eni S.p.A. Rev. 1 June 2003
Exploration & Production Division Sheet 15 di 18
The connection circuits (and the corresponding disconnectors and fuses) among the
regulator, the storage battery and the users shall be designed in such a way that the
power supply will never take place from the photovoltaic field without having the
battery in parallel, because in the event of this happening, the voltage would be
increased above the safety limits.
If a d.c. panel (DCP type) is specified in the Data Sheet, separated or in place, the
d.c. distribution section will be eliminated.
The d.c. control panel functional and construction characteristics shall conform to the
relevant functional Specification and the Data Sheet.
The battery selection and the sizing will be carried out in accordance with the
specifications given on the Data Sheet.
The battery functional and construction characteristics shall conform to the relevant
functional Specification and the Data Sheet.
Unless otherwise indicated, the following conditions will apply:
– The self discharge characteristic shall not be greater than 2% per month at 25° C.
– The batteries will be of the lead-calcium type, or lead-antimony type with a low
content of antimony, or nickel-cadmium type. They shall be suitable to be used with
the wind systems.
– The batteries with the topping up possibility must be of the greater reserve of
electrolyte type, in such a way to schedule only one intervention each year.
– The battery capacity shall cover the longest “without wind” possible period (discharge
of at least 100 hours).
– The estimated degradation of capacity after 10 years of service, with the charging
cycles indicated on the Data Sheet, shall be as low as possible.
2.4.3.8. Accessories
When requested in the Data Sheet, some speed meters shall be included in the supply of
the eolic generation system. They will measure the rotations per minute for each eolic
generator.
The monitored data shall be available in analogic form to be passed to a processor
system.
The level of the output signal shall be in mV or in mA, in accordance with the Supplier's
standards.
The material necessary for the start-up shall be supplied for each system.
Based on previous experience and the utilised types, the spare parts provided will be the
ones the supplier consider to be necessary.
20176 EQP.ELE.FUN
Eni S.p.A. Rev. 1 June 2003
Exploration & Production Division Sheet 16 di 18
a) Painting
Painting and the relevant protective treatments will be done in accordance with the
prescriptions contained in the Data Sheet.
b) Tropicalisation
When required in the Data Sheet, equipment and materials will be subjected to
tropicalisation treatments in accordance with the relevant Reference Specification.
Packing for transport shall be defined by the Supplier according to the modalities required
by the Company.
The batteries shall, however, be dismantled in units suitable for transportation and their
re-assembly operations shall be as simple and as safe as possible.
2.5.1. Usefulness
This Functional Specification has to be considered as covering some aspects not defined
in the Supply Specification, which specifies the limit of supply, the design data and the
specific choices.
No specific application area is, therefore, addressed by this specification, which shall be
utilised both for plants on which the eolic generation is the main energy source and for
plant on which this type of power generation is auxiliary to a different energy source.
Particular limits and exclusions, if any, are indicated in the Data Sheet.
2.6. ERGONOMICS
The noise level of the system shall not be over 65 dBa , measured at a distance of 1 m
and at a height of 1 m.
2.7. SAFETY
The Supplier will guarantee that the material and components of the system, subject of
this Functional Specification will be designed according to a good practice to respect the
safety prescriptions contained in the Normative References.
20176 EQP.ELE.FUN
Eni S.p.A. Rev. 1 June 2003
Exploration & Production Division Sheet 17 di 18
When required, tests indicated in the Inspection Data Sheet (I.D.S.) shall be carried out
and are subdivided in:
– Type test;
– Special test.
For any inspection and test not included in the Normative References and in this
Specification and requested in the Inspection Data Sheet (I.D.S), the execution
procedures shall be defined on a case by case basis.
When required, the tests and inspections shall be carried out on:
They shall be as defined in the Functional Specifications and Inspection Data Sheets
(I.D.S.).
The type test aims at guaranteeing the compliance of a specific type of eolic generator
with the Normative References and the original design.
The type test shall be carried out on a prototype of eolic generator and the Supplier shall
be fully responsible for its execution.
The type tests shall be carried out in official laboratories.
The Company shall be exclusively responsible for the acceptance of eolic generators that
are similar to those supplied as prototypes and shall reserve the right to request the
execution of some of the type tests.
It includes tests and inspections not provided for in the type and acceptance tests, that
the Company may require from time to time.
The list of tests and inspections and any criteria of execution will be indicated in the
Inspection Data Sheet (I.D.S.).
20176 EQP.ELE.FUN
Eni S.p.A. Rev. 1 June 2003
Exploration & Production Division Sheet 18 di 18
2.10. DOCUMENTATION
The Supplier will deliver to the Company all the documents indicated in the Requested
Document Data Sheet (R.D.D.S.), in accordance with the agreed terms and schedule.
The technical documentation will be written in the official language indicated in the Data
Sheet and using the symbols indicated in the applied reference Rules.
The Supplier will include in his bid all the information and documentation required in the
Data Sheet (R.D.D.S.).
The approval of the documentation by the Company, if necessary, will refer to the formal
verification of the parameters indicated in the design's documents only.
The Supplier will deliver to the Company all the documentation necessary to the
execution of the system design and to the installation of the supplied system.
The Supplier will deliver to the Company, within the schedule and in the way indicated in
the Data Sheet, all the certificates relating to the type, acceptance and special tests.
The final technical documentation, with the only exception of the Supplier and
Subsuppliers catalogues and publications will include the following references:
b) Operations instructions;
c) Maintenance instructions.
The description and drawings can be contained in catalogues and documents of the
Supplier, as long as they satisfy the following conditions:
– they contain all data and information required in their final form
– they are relevant to the type supplied and the materials included in the supply are
clearly identified amongst those in the document.
The documentation subject to approval will be integral part of the final documentation
approved by the Company.