Professional Documents
Culture Documents
COMPANY SPECIFICATION
20217.VAR.ELE.SDS
PREMISE
Rev. 0 Pages 49
30/12/2004
Eni S.p.A. 20217.VAR.ELE.SDS
Rev.0 December 2004
Exploration & Production Division
Pag. 3 di 49
INDEX
1. PURPOSE................................................................................................................................
2. FOREWORD............................................................................................................................
1. PURPOSE
Purpose of the present specification is to describe the various modes of driving for electric
motors as well as illustrate the guidelines for their use and applicability on both onshore
and offshore plants.
2. FOREWORD
Indications given hereinafter are to be intended as general and not ultimate indications on
the matter, since final solutions that will be chosen, have to be tailored on effective
engineering and technical-economical requirements; which nevertheless are part of the
Company’s proven plants traditions.
In defining the types of motor driven systems, called for in this document, the following
definitions apply:
DRIVE SYSTEM: group of electrical equipment suitable to provide and/or cut the power
supply, to protect, check and monitor start and running of an electric motor.
The drive systems may be grouped into the following main two categories:
• FIXED SPEED DRIVES: under this category, fall all those systems that connect the
electric motors to the power network; motor’s rated speed only depends upon the
number of poles.
Starting systems may be at full voltage (D.O.L. type) or at reduced voltage.
• VARIABLE SPEED DRIVES: under this category, fall all those systems that connect the
electric motors to the power network throughout equipment and devices capable to
electronically regulate either the frequency and the voltage of supply system, thus
adjusting motor’s revolution speed.
Several transmission systems, especially designed for installation between the motor and
the driven machinery, allow the motor’s speed regulation by means of proper RPM
reduction and/or increase speed devices availble on the market, eg differential systems
and/or oil operated couplings.
Nevertheless, these systems are based on the steady (constant) speed of the driving motor
thus not falling, for the purposes of this specification, under the category of variable speed
drives.
Eni S.p.A. 20217.VAR.ELE.SDS
Rev.0 December 2004
Exploration & Production Division
Pag. 5 di 49
Electrical equipment to feed and control of motor drives, are generally located within the
distribution boards, installed indoor the plant’s electric cabin. In some cases, eg package
type supplies, said electrical equipment may be housed within proper boxes and/or local
panels, close to field users.
Depending upon the size (rated power) of motor to be supplied, the feeding switchboards
are subdivided as follows:
• “MCC” Motor Control Centre: it is a Low Voltage (LV) switchboard composed by a
number of drawers of various sizes, in withdrawable type execution. Drawers are
interchangeable with similar ones having equivalent mechanical and electrical features.
Rated power of electric motors supplied by this type of switchboards ranges from 0,25 to
0,55 kW.
• A more economical solution of MCC’s, denominated as “fixed execution”, in which the
motors control components are located within dedicated compartments instead of
withdrawable type drawers are also available on the market; this solution, obviously
requires more time spending for maintenance operations.
• “PC Power Centre”: it is still a Low Voltage (LV) switchboard which is normally used to
provide power supply to MCCs and other switchboards, as well as to electric motors
having rated power ranging from 55 kW up to 132 kW (in some cases motors with rated
power above 132 kW may also be supplied). In small size plants Power Motor Control
Centres (PMCC’s) are used, as constructive implementation of both PCs and MCC’s.
• “QMT”: it is a medium voltage switchboard which is normally used to provide power
supply to different type users, including electric motors having rated power 200 kW and
larger.
The voltage levels normally used for the power supply to electric motors, are as follows:
• 400 V, 3 phase, 50 Hz, for motors with rated power up to 200 kW
• 6 kV & 11 kW, 3 phase, 50 Hz, for MV motors with rated power 200 kW and larger
Small size motors (usually in the order of some hundreds watts), single phase supply at
230 V, 1 phase, 50 Hz, is normally used.
In compliance with regulations and laws in force to the country of installation, different
voltage levels and/or frequencies may be used
Eni S.p.A. 20217.VAR.ELE.SDS
Rev.0 December 2004
Exploration & Production Division
Pag. 6 di 49
60 • f
ns= [rpm/min]
P
where
ns= synchronous speed
f= frequency Hz
P= number of pair poles
The difference between speed of rotation (nr) and the synchronous speed (ns), is known as
‘slip’ (S) defined by the following formula:
ns − nr
S=
ns
Slip of cage type asynchronous motors mainly depends upon motor’s constructive features
and the load coupled to it; the slip raises with the increase of the load itself, in accordance
to the characteristic curve shown in Fig. 1, below.
In rated conditions of power supply and load, the slip figure is normally ranging between
0,01 and 0,05.
The torque developed by an asynchronous motor supplied at rated voltage and frequency,
has not a steady value but it varies according to a typical curve which depend on the
motor’s slip (see Fig. 1).
Fig. 1
Representation of the torque related to the speed of cage type asynchronous motors
fed at rated voltage and frequency
Eni S.p.A. 20217.VAR.ELE.SDS
Rev.0 December 2004
Exploration & Production Division
Pag. 7 di 49
In the above typical curve, the following ‘torque’ definition are given:
Cn: motor’s nominal torque, denotes the value for which the motor has been
designed and its own continuous duty guaranteed.
CM: maximum torque, denotes the value the motor can develop, that can
maintainable for short periods. Generally its value is about 200% of Cn.
Cs: “starting” or “locked rotor” torque, denotes the value developed during start
phase, when the motor is still idle. Its value mainly depends on motor’s
constructive features, the number of poles and the resistance of the rotor.
Cmin: minimum or stalling torque, denotes the value developed during start
phase. Its value mainly depends on motor’s constructive features.
Cr: denotes the resistant torque represented by the load coupled to the motor.
Ca: denotes the accelerating torque, that is the sudden difference between
starting torque (Cs) and the resistant torque (Cr)
Mechanical power (Pm) supplied by the motor is given by the following relationship:
Pm = ω • C [W]
Where:
Electrical power absorbed by the supply network depends upon the efficiency of the motor
(η) corresponding to operating point, given by the following relationship:
Pm
Pe= [W]
η
Eni S.p.A. 20217.VAR.ELE.SDS
Rev.0 December 2004
Exploration & Production Division
Pag. 8 di 49
In typical E&P electrical installations, the following motor drive types subdivided into starting
method, are normally used:
• Direct on line start [DOL] (fixed speed drive)
• Star-Delta start (fixed speed drive)
• Autotransformer start (fixed speed drive)
• Soft-start (fixed speed drive)
• Start and supply with both voltage and frequency variable (variable speed drive)
As it will become evident, all problems related to the start of asynchronous motors are
mainly connected to limit the starting current.
To do this it is necessary reducing the motor’s supply voltage by means of different
systems.
Reduction in supply voltage automatically reduce the Cs too which is essential to win the Cr
of the load.
To enable motor to reach its nominal speed it is therefore required that torque of the motor
be greater than Cr for all duration of the start.
Eni S.p.A. 20217.VAR.ELE.SDS
Rev.0 December 2004
Exploration & Production Division
Pag. 9 di 49
Among diverse drives, the fixed speed drive is the most common used system any time
operating machines requiring higher starting torques are present, by the matter of fact, fixed
speed drive, is the sole system. Major advantages are given by reduced costs ( simple
construction as constituted by a single power contactor), reduced maintenance
(replacement of power contactor in case of its damage, as the sole, required intervention).
As already stated, with this type of start an elevated starting torque is available.
Motor start is made at full voltage, hence with full torque and starting current: starting
current is not limited.
Co-ordination among the protection devices and the drives equipment of DOL low voltage
motors can be found on any Co-ordination Tables provided-for by the Manufacturers of
various electrical components.
Eni S.p.A. 20217.VAR.ELE.SDS
Rev.0 December 2004
Exploration & Production Division
Pag. 10 di 49
- Based upon the size of the motor and feeding switchboard, the following typical
schemes are applicable:
QM Automatic circuit breaker with opening coil and the magnetic protection F-50, for the
short circuit protection.
K-42 Power contactor, device which switch ‘on’ and ‘off’ the motor from the electrical
supply.
F-49 Thermal relay. Device protecting the motor from overload. Depending on the driven
equipment, thermal relay may be suitable for normal service or heavy duty.
F-64 Devices for the protection of earth faults occurring on motor-cable and it is
constituted by a ring type current transformer installed within the MCC compartment,
or the outgoing cable from earth fault relay F64.
Eni S.p.A. 20217.VAR.ELE.SDS
Rev.0 December 2004
Exploration & Production Division
Pag. 11 di 49
PBS Push Button Station (LOCAL). It is normally placed close to the motor and is fitted
with switches and/or buttons depending on required duty. An ammeter is provided
for motors having rated power of 7,5 kW and larger.
REMOTE Process control connection to DCS (REMOTE). By means of this connection both
‘start’ and ‘stop’ of the motor, are controlled.
NOTE: Proper integrated type devices for the protection and control of the motors, are
available on the market (Compact Motor Protection). Such devices are constituted
by a combination of a circuit breaker, fitted with adjustable magneto-thermal
element and power contactor. Use of these systems in E&P plants, is limited to
local units supplied with packaged type equipment.
Eni S.p.A. 20217.VAR.ELE.SDS
Rev.0 December 2004
Exploration & Production Division
Pag. 12 di 49
QM Automatic circuit breaker with opening coil and the magnetic protection F-50, for the
short circuit protection.
PBS Push Button Station (LOCAL). It is normally placed close to the motor and is fitted
with switches and/or buttons depending on required duty. An ammeter is also
provided.
RTD Thermo elements, normally used to give alarm for high temperature, installed inside
the magnetic core, which house the motor’s windings. Some time signals of the
thermo elements are delivered directly to supervision/management system for
monitoring from remote Control Room.
RA Anticondensation heater
NOTE: It is possibile to use starters provided with fuses and contactor in lieu of the circuit
breaker for low voltage motors, having rated power up to 600 kW approx.
This configuration allows room saving, because of reduced switchboards
dimensions, as well as the ninvestment costs.
Eni S.p.A. 20217.VAR.ELE.SDS
Rev.0 December 2004
Exploration & Production Division
Pag. 14 di 49
Fig. 3
Eni S.p.A. 20217.VAR.ELE.SDS
Rev.0 December 2004
Exploration & Production Division
Pag. 15 di 49
QM Automatic circuit breaker with opening coil and the magnetic protection F-50, for
the short circuit protection.
K42 Line power contactor (sized for a current equal at least to 58% of the rated value,
for starting times up to 20 s)
K42-Y Star power contactor (sized to 33%, for starting times up to 20 s; if exceeding
usually it is equivalent to the others)
F49 Motor thermal protection (it may be installed downstream the power contactor K-42
instead of upstream, in this case relay setting must be reduced of √3 with respect to
full line current)
Disadvantages of the Star-Delta starting system compared with Direct start (DOL)
1. It needs three (3) power contactors (line: K42; delta: K42-D and star: K42-Y),
instead of one, and the use of two cables (even if reduced cross-section), instead
of one, with significant increase in investment costs; mainly due to larger O.D.
dimensions of feeding switchboards as well as the required room in electric cabin
(negative impact in offshore plants).
As a matter of fact, its cost is three times bigger than the direct start
2. Reduction of the starting torque (Cs) to 1/3 extendes time duration and often make
difficulty the motor starting. Besides the Cmin (reduced of 1/3 too), may be smaller
than Cr. Operators may sometime not be aware of lost star phase running as the
motor starts anyhow, following the switching from star to delta (operated by a timer
which is adjusted so as the start be completed in short time); under these
conditions the motor is started at full voltage
3. Passing from star to delta a short interruption of power supply, is being faced,
caused by contactors commutation. Closing of contactor K42-D can occur in
“counterphase” with consequent instantaneous inrush current whose level is higher
than the theoretical one, linked to ‘slip’ figure corresponding at the moment the
star-delta commutation takes place.
In case the conditions about lost start described at point 2. above are met, the
peak current due to star-delta commutation shall be equivalent to the starting
current performed at full voltage, to be furtherly increased if said commutation
occurs in counterphase.
It is therefore necessary to pay attention in designing/engineering star-delta starting
system: the choice of commutation time to be very accurate.
4. It is also not possible to select the starting characteristics, as the parameters are
pre-defined and cannot be adjusted
Eni S.p.A. 20217.VAR.ELE.SDS
Rev.0 December 2004
Exploration & Production Division
Pag. 16 di 49
There is anyway the possibilità of drastically reduce peak current during switching from star
to delta and prevent motor deceleration, by unloading the current in eccess on proper
electric resistors, to connect before commutation (at the end of acceleration phase) and
disconnect once the commutation is completed (close transition system).
For this arrangement an additional fourth contactor (K42-D1) together with a transition
resistance R, have to be considered and provided (see schematic diagram below).
Switching from star to delta begins with the closing of K42-D1 which energises the
resistances R, followed by the opening of star contactor K42-Y; in this moment the motor is
connected to delta with the transition resistance R, connected in series with motor
windings, later delta contactor (K42-D) supplies the motor full voltage and disconnect the
resistances R (opening of K42-D1).
Eni S.p.A. 20217.VAR.ELE.SDS
Rev.0 December 2004
Exploration & Production Division
Pag. 17 di 49
Base starter’s operating cycle, can be subdivided into three different steps:
A “natural” time duration for starting ramp, associated to every motor/user, applies:
this time is tied with both inertial and mechanical characteristics of the system it self.
If duration of starting ramp is shorter: system’s acceleration increases together with the
absorbed peak current value.
Eni S.p.A. 20217.VAR.ELE.SDS
Rev.0 December 2004
Exploration & Production Division
Pag. 20 di 49
If duration of starting ramp is longer: the system, obviously, requires more time to reach
its full speed rate, but absorbed current value is reduced.
This phenomenon is generally advantageous, providing that (keeping into consideration
the system application in its whole) unacceptable operating condition due to speed rate
that is reached later, is determinated. It is necessary to consider presence of possible
other machinery or systems, whose operations are connected to that one in subject.
Starter’s managing software may be in any case tilored on operating features of the
user, which need functionalities or performances outside of normal applications.
Soft-starters may be provided with the following additional functions/features:
• starting ramp with control and limitation of starting current (Current-Limit)
• dwell-time
• energy saving
• the OVERRIDE to cut both energy saving function and malfunction supervision
system
• by-pass system
• soft-stop or control stopping ramp.
Eni S.p.A. 20217.VAR.ELE.SDS
Rev.0 December 2004
Exploration & Production Division
Pag. 21 di 49
3.3.4.3 Dwell-Time
Dwell-time starti begins at the moment the starting ramp is stopped and at the motor
terminals the full voltage is supplied.
The pause period has a time duration equal to duration of the starting ramp.
During the pause period, at the motor terminals the full voltage is steadely maintained:
the purpose is to give motor and load, time and manner to reach stable operating
conditions.
3.3.4.4 Energy-Saving
Energy-saving function regulates the motor supply on the effective load condition so
allowing energy saving. It is automatically actuated and remains continuosly running
for all the time ranging between expiring of Dwell-time and the moment the STOP
control is given.
During the starting ramp, the system’s software calculates a reference value for the
‘power factor’ (full load cosϕ).
For all the time the energy-saving function is ‘on’, the instant value of power factor
(cosϕ) is continuosly monitored with the above mentioned reference value. Result of
such comparison is used by microprocessor of the system to modulate the soft-starter’s
output voltage to effective motor instant torque demand, without wasting energy
required to generate an excessive and useless magnetic flux within the motor. This
way, allows power factor (cosϕ) to motor terminals be maintained at the highest possible
value, in function of effective power demand (load conditions).
Eni S.p.A. 20217.VAR.ELE.SDS
Rev.0 December 2004
Exploration & Production Division
Pag. 22 di 49
The described power factor management does not affect the motor capabilty to supply
the power required by load. Motor performances (together with its own speed) are in
no way involved. Energy-saving function is a purely electrical function, which simply
assures that – in every moment – motor to generate the required torque, but enabling it
to absorb a quantity of magnetisation current necessary to sustain such a torque only.
If energy-saving function is lost, the motor would absorb the maximum magnetisation
current instead, in a way not dependant from its own load status. Final purpose of
energy-saving function is, globally consedered, to reduce electric energy consumption.
Energy-saving function cannot improve the power factor (cosϕ) and rise it to values
bigger than full load ones, as such value depends on constructive features of the motor.
It is therefore wrong to affirm that the static type starter owns the characteristics of a
power factor improvement equipement.
Keeping into consideration that fluids have low attitude to be compressed but have
kinetic energy, rapid change in flow in a so short time can originate high pressure
strokes that put into hard test the pipe walls, which some time blow up (“water
hammer”). In order to avoid said dangerous effect modern softstarters are often
integrated also with a facility called “Pump Control”. It consists in performing both start
& stop by a special and controlled mode; in such a way torque of the motor match
completely the one of the pump, thus minimising either accelerating and decelerating
torques, hence the water hammer.
Above results is achieved thanks to special microprocessor provided with softstarter
having this function. As a matter of facts if water hammer is reduced by the use of
a simple controlled stop function, it is almost totally eliminated by the use of
pump control.
Controlled stop may be performed at any time after the acceleration ramp is over: even
with the softstarter by-passed.
Normal time duration of Soft-Stop ramp, is equal to twice the time duration set for Soft-
Start ramp.
Once the ramp for CONTROLLED STOP is activated, supply voltage at the motor
terminals is lineary decreased, beginning from full voltage (source of power supply) up
to a voltage value equal approx. to 40% of full one. When reaching such a voltage
level, the power connection is being automatically disabled and the unit motor/driven
equipment stops by inertia.
In no cases Soft-Stop function is to be considered - and therefore used - as a motor
brake. Emergency braking is to be redundant and of a mechanical type, in full
accordance to the rules and safety codes in force.
Eni S.p.A. 20217.VAR.ELE.SDS
Rev.0 December 2004
Exploration & Production Division
Pag. 24 di 49
• Mechanical stress (and related wear) of both motor and driven machinery, limited;
• Soft-stop and pump control functions capable to generate significant benefits in some
applications;
Eni S.p.A. 20217.VAR.ELE.SDS
Rev.0 December 2004
Exploration & Production Division
Pag. 25 di 49
In industrial plant applications where it is necessary to vary speed of electric motors driving
pumps, fans, mills, etc. the use of asynchronous type motors coupled to double conversion
static frequency converters (from a.c. to d.c. and again from d.c. to a.c. variable & voltage
frequency) provide a technically faster and profitable solution.
Furthermore the static frequency converters, mainly the PWM type (see next paragraphs),
have reached a high degree of reliability together with the best results to both efficiency
(98% approx.) and cosφ (>0,95).
Variable frequency drive primarily allows continuous adjusting of the speed thus enabling
precise positioning of the system on the best working point related with the effective
operating conditions.
In such a way an adequate energy saving is matched too.
The motor’s operating field may range from minimum frequencies of few Hertz up to a
maximum of twice the rated one.
Operative limits are given by motor Manufacturer which keeps into consideration the
cooling conditions, when working at low rate and mechanical restrictions of the rotor, when
running at high speed.
Drive unit in its whole is a multipart equipment that include use of power semi-conductors
components.
Besides, an aspect of great importance that sometime requires the utilisation of variable
speed drives even when the speed regulation would not be strictly needed, is that such
drives make possible to start motors assuring nominal torque for all operating phase with a
maximum current equal to the rated one
Eni S.p.A. 20217.VAR.ELE.SDS
Rev.0 December 2004
Exploration & Production Division
Pag. 26 di 49
Summarizing, two functioning fields are thus available (see figure 2).
1) Operation at constant torque:
- regulation field ranging between minimum frequency and the rated one (lower
frequencies), whereas the magnetic flux remains at a constant value,
- in this field we obtain a regulation with power proportional to speed.
2) Operation at constant power:
- regulation field ranging between rated frequency and the maximum one, range in
which the voltage remains at a constant value,
- in this field the magnetic flux and the torque decrease as the speed rises, whereas
the power remains at a constant value.
Eni S.p.A. 20217.VAR.ELE.SDS
Rev.0 December 2004
Exploration & Production Division
Pag. 27 di 49
Fig. 2
a) curves of the voltage ‘V’ and the power ‘P’ with reference to frequency;
b) curves of the torque with reference to frequency.
In big drives, where an incoming transformer is provided to achieve the 12phase rectifier
system at 12 pulses, two separate rectifier bridges: one on each winding, are installed.
c) filter circuit and d.c.rectifying
The components of circuit (reactances, capacitors, choppers, etc) sized in function of
VSD type, have the purpose of filtering and rectifying the current in order to allow correct
operation (on and off) of the inverter section.
d) current reverting section from d.c. to a.c. (commonly called inverter) and regeneration of
the power system (3phase, 1phase, etc).
e) control circuit that allows to modify and monitor both voltage and frequency values
coming from inverter, as well as the cycles of regenerated phases.
Eni S.p.A. 20217.VAR.ELE.SDS
Rev.0 December 2004
Exploration & Production Division
Pag. 29 di 49
Depending on technology and components utilized in the fabrication of drives, VSD can
be subdivided into the following main typologies:
a) Impressed current
This system deals with the use of tyristors in the rectifier section, which are
controlled by a circuit that measures the current output towards the user and try to
maintain it at a preset value.
Frequency is adjusted separately within inverter section.
In the impressed current VSD, reactance of motor is a parameter of the control
oscillating circuit that allows the inverter section to work.
Therefore value of said reactance, including the motor connecting cable, to be
known in order to “tune” the system.
Consequently the system is suitable to feed a single motor only, with known
parameters, besides cross-section area and length of the cable have to be already
defined during VSD purchasing activity.
This range of VSD is utilized for large motors only having rating sizes of 15 to 20
MW and over.
Eni S.p.A. 20217.VAR.ELE.SDS
Rev.0 December 2004
Exploration & Production Division
Pag. 32 di 49
b) Impressed voltage
This system deals with the use of tyristors in the rectifier section, which are
controlled by a circuit that measures the voltage output towards the user and try to
maintain it at a preset value.
Frequency is adjusted separately within inverter section.
The impressed voltage VSD in relation to motor performs as a 3phase voltage
generator.
Besides, if compared with the one “at impressed current”, in which main motor
parameters have to be carefully checked, with the impressed voltage converter the
control circuit is not influenced by motor’s parameters.
This range of VSD is utilized for large motors only having rating sizes of 15 to 20
MW and over.
Eni S.p.A. 20217.VAR.ELE.SDS
Rev.0 December 2004
Exploration & Production Division
Pag. 33 di 49
Generally within the VSD control system communication ports are provided in order to
allow connection of the drive to the plant’s management and control network (DCS) thus
transferring commands, measuring and controls to hierarchies of upper grade levels.
As an optional, VSD may be provided of a by-pass to allow power supply to motor in the
event of failure of the drive; in this condition by-pass effectively performs as a direct
starter.
Again the VSD can be switched off when motor has reached its speed rate to frequency
of the network so as to cut-off the drive form maintenance a/o energy saving, in this
case allowing the by-pass to close, the system is provided with a synchronizer between
the network and output voltage from VSD.
3.3.5.4.1 Harmonics
1
⋅ 100
n
In the case said distortions are unavoidable (eg very weak networks) it is possible to
reduce impact with the installation on same network feeding VSDs of properly sized
capacitors/reactors banks.
Use of PWM regulation, is possible contain problem of harmonics yet; it is likely to
obtain an output voltage with fundamental sinusoidal component containing high
frequency harmonics, hence easily filterable. In accordance to EMC Directive, to
reduce nuisance emissions on the network and the surrounding environments, speed
drives are provided with EMC inlet filters.
Reactive power absorbed by VSD mainly depends on type of rectifier utilized into
conversion and rectifier section.
In PWM where rectifier section is composed by diodes, cos φ is practically steady over
all working field and is about 0,95 to 1.
Obviously such cos φ is referred to fundamental current.
Again to this type of drives it is not necessary to provide power factor improvement
systems.
In impressed current a/o voltage drives, power factor is quite low (0,7 to 0,8) and
variable in relation to working rating.
Therefore, if the impact of VSD on the network is significant, it may be necessary to
provide power factor improvement, keeping into account presence of harmonic
components, which could damage the capacitors if not adequately tuned with
reactances.
3.3.5.5.1 Location
VSD drives are usually installed within dedicated eclosures/boards. For small power
units (low voltage) up to 30 to 45 kW can be housed inside dedicated section of power
distribution boards (MCC; PMCC).
The transformer of cabin.
Special care to be paid to cooling problems of VSD; for the sizing of ventilation and
conditioning systems of the cabins it is necessary to consider that power dissipated by
VSD is 4% of their own rating power.
Some times for lager units the cooling of VSD is nade with de-ionized water for which it
is necessary to define location of relevant heat exchangers.
Eni S.p.A. 20217.VAR.ELE.SDS
Rev.0 December 2004
Exploration & Production Division
Pag. 38 di 49
With VSD used to drive motors installed in hazardous areas, it is necessary that motors
in addition to Ex excecution suitable for specific installation are also provided of
temperature detectors to cause cut-off of power supply to motor as soon as the
maximum admissible temperature is reached.
3.3.5.5.4 Motors
Motors for VSD applications must be suitable for the working rate; it is appropriate to
specify the speed variation field to which the motor is submitted in order to assure
proper ventilation even to low revolution (rpm) rates. Besides, as the shape of output
voltage from VSD is not perfectly sinusoidal, in order to compensate bigger losses the
motor is oversized of approx. 10%. Some time harmonics can originate an increase of
motor’s sound level.
In extremely precise speed regulation system devoted to special working cycles only,
motors could be equipped with encoder for the right transmission of revolutions.
As already described for installations in hazardous areas, motors to be fitted with
suitable probes to avoid overcoming of maximum admissible temperatures (varistors,
thermostats, thermo-resistances, etc.), besides to limit induced currents on the shaft one
of the bearings is isolated.
Eni S.p.A. 20217.VAR.ELE.SDS
Rev.0 December 2004
Exploration & Production Division
Pag. 39 di 49
In following Table one the main characteristics relevant to different typologies of electric
motor drives previously described, are summarized.
It is to be noted that in general the best reliability of electric plant and the drives too, is
achieved by the use of as simple as possible equipement and devices. Under this side
direct start (DOL) is the winning one for its own low cost, reliability system’s simplicity
and its applicability is generally diffused in both low and medium voltages.
Nevertheless, when network condition impose starting current limitation, it is required to
use motor starting system at reduced voltage.
Among these systems the star-delta one is to be avoided because it does not give
resolutive solutions to the problem of starting current, indeed during commutation
between star and delta the re-connection current can be bigger than that of direct start
(DOL).
VSD system is the best system under the technical profile thus offering also the
opportunity to regulate the motor working speed, on the contrary it is much expensive.
The starting system with autotransformer is undoubtly the most proven and proposed
due to need of start motors at reduced voltage, in both low and medium networks.
Soft-start system, imposes itself on the market as it offer a large range of different
functions for the control of motor. Anyway its application in controlling start of medium
voltage motors is not largely diffused yet.
Eni S.p.A. 20217.VAR.ELE.SDS
Rev.0 December 2004
Exploration & Production Division
Pag. 40 di 49
TABLE 1
Simple construction, as Not advaisable to start big All asynchronous motors L.V. feeders (PMCC).:
constituted by a single motors on weak networks, with fixed speed. - 37kW ~ 1.000 $
power contactor. e.g. when the motor starting - 75kW ~ 1.400 $
DIRECT START Reduced maintenance. causes a network voltage - 132kW ~ 1.800 $
(DOL) Very high starting current. drop >=15% M.V. feeders (MVP) 6kV
Nominal characteristics of - contact + fus. 15.000 $
motor torques. - circuit breaker 25.000 $
System composed with Usable only for application To start motors on weak L.V. feeders PMCC):
three contactors and control where is requested a low network. - 37kW ~ 2.000 $
circuit with time relays. starting torque. The current during star- - 75kW ~ 2.600 $
STAR-DELTA Significant maintenance. delta commutation can - 132kW ~ 3.500 $
Reduction of starting current be higher than DOL
to 1/3 starting current.
Reduction of starting torque UNADVISABLE
to 1/3
System composed with The starting torque is Used to reduce the L.V. feeders PMCC):
three contactors, an reduced in relation with the voltage drops during - 37kW ~ 3.000 $
autotransformer and control square of starting chosen motor starting on weak - 75kW ~ 3.800 $
AUTO- circuit with time relays. voltage. networks. - 132kW ~ 5.200 $
TRANSFORMER Significant maintenance. To define characteristics of System used also to
Reduction of starting torque autotransformer is necessary start big motors. M.V. feeders 6kV
according to the a torques analysis. At medium voltage is - contact + fus. ~ 800kW
autotransformer output preferable than soft-start ~ 50.000 $
voltage. method. - Circ. brk ~ 1÷5000kW
Commutation between ~ 80.000 $
reduced voltage to nominal
voltage without interruption.
System based upon power In case of need of very high To start motors on weak Cost estimation for L.V.
thyristor technology with starting torque, the limitation network. drives, PMCC equipment
variation of output voltage. of starting current is not Allows to eliminate included.
Allows the soft satrting of significant. “water hammer” durino - 37kW ~ 3.000 $
motor limiting the starting start up and stop of the - 75kW ~ 5.000 $
current to a value necessary pumps. - 132kW ~ 7.000 $
SOFT-STARTER
to cope the resistant torque. The application of soft- Cost estimation for M.V.
Allows also the soft stop starter system is drives, MVP equipment
procedure and the partial advisable only for low included.
energy saving. voltage. - ~ 1800 kW ~ 70.000 $
- ~ 3600 kW ~ 75.000 $
- ~ 5000 kW ~ 85.000 $
System based upon power No limitations. Usable for all motors Cost estimation for L.V.
thyristor technology with Probable need of harmonics (synchronous and drives, PMCC equipment
output voltage and filtering system in case of asynchronous) with included.
frequency variation. Allows installation on weak network. power from fractions of - 37kW ~ 16.500 $
the soft start and soft stop of kW up to 50 MW and - 75kW ~ 19.000 $
the motor, and the running above. - 132kW ~ 42.000 $
VARIABLE
with speed variation.
The starting current is Cost estimation for M.V.
SPEED drastic reduced (maximum drives, MVP equipment
equal to motor rated included
DRIVE current). -for 350kW – 690V and
No limitation of the nominal input transformer
torque characteristic of the 6000/690V ~ 95.000 $
(VSD) motor.
Allows energy saving during -for 2000kW – 6kV and
the motor running, and also input transformer with two
the kinetic energy recover secondary windings
during motor stop phase. ~ 300.000 $
Eni S.p.A. 20217.VAR.ELE.SDS
Rev.0 December 2004
Exploration & Production Division
Pag. 41 di 49
Cn
∆U< (1 − ) • 100 (%)
CM
Thus replacing CM=1,5•Cn, a ∆U<18 % is obtained.
This is maximum voltage drop value to motor terminals. If voltage drop on supply cable
equal to approx. 3 to 5% is considered, together with a greater current absorbed by
motors caused by the lowering of voltage, the voltage drop tolerated in the network must
normally be less then 10 to 14%.
Apparent starting power absorbed by a motor comes from the following relationship:
SAVV= U • 3 • I AVV
Voltage drop at starting depends on short circuit power SK3 af the network and it is given
by the following relationship:
∆U=100/(1+SK3/SAVV) (%)
Short circuit power SK3 to keep into account is that of the network without considering
motor contribution. For networks supplied by their own generator, short circuit power
determined by transient reactance (X’d) of generetor is to be considered instead of the
subtransient one (X”d). As a matter of facts either the subtransient reactance and the
asynchronous motors contribution ends in few cycles, without significantly contributing
to sustain voltage of network
1. Example
Network 400 V supplied by a transformer Srt=800 kVA; Ucc=5%; short circuit power on
primari side SK3 = 100 MVA.
Motor to be started: 132 kW; In = 232 A; ISTART = 7,1•In
Eni S.p.A. 20217.VAR.ELE.SDS
Rev.0 December 2004
Exploration & Production Division
Pag. 42 di 49
2. Example
Network 400 V supplied by a 900 kVA generator with subtransient reactance equal to
X’d=19%.
Motor to be started: 132 kW; In = 232 A; ISTART = 7,1• In
Network transient short circuit power supplied by the generetor itself is:
SK3 = 100•Srg/X’d=100•900/19=4737 kVA = 4,7 MVA
Motor starting power as already calculated in example 1 above, is 1,14 MVA, voltage
drop becomes:
∆U=100/(1+SK3/SAVV)=100/(1+4,74/1,14)=19,4%
It is evident that the motor cannot be direct started.
Calculation formulas represented above are simplified, but they offer a sufficient degree
of precision and mainly basic parameters for the initial plant’s selection.
Other calculation methods that utilize the various parameters (R+jx) of equipment
composing the plant, can be used for a more accurate analysis of the electric system.
Eni S.p.A. 20217.VAR.ELE.SDS
Rev.0 December 2004
Exploration & Production Division
Pag. 43 di 49
Direct starting method is the one to be preferred because of its own simplicity
characteristic. In the case, as in example 2 of previous paragraph, its utilization is not
possible, it becomes necessary to consider alternative methods at reduced voltage.
As first investigation it is necessary that starting torque Cs of the motor, supplied at
reduced voltage, is adequate to win the resistant torque Cr during starting of motor-user
unit.
If, as an example, torque Cr at starting is presumed to be 30% approx. of starting torque
Cs of motor, referred to rated voltage V1, it is then necessary:
a) To consider a safety margin of 1.3, so that
Cr= 1,3•30% ≈ 40% of Cs
b) Calcolate the reduce voltage V2 sufficient to guarantee such a torque, being:
V2 2
0 .4 = ( ) ;
V1
It becomes:
V2 = 0,4 ⋅ V1 = 0,63 ⋅ V1
a) Star-delta starting
Star-delta starting, anyway not recommended, would not guarantee starting of the
motor because the voltage to the motor itself should be 1/√3 V1 = 58%
b) Autotransformer starting
Voltage V2 of the autotransformer is selected at approx. 65% of V1.
Starting current supplied by the network, is:
I’START= ISTART•(V2)2.
Keeping into consideration the example 2 of previous paragraph, we get:
I’START= 7,1•0,652=3• In
To which the corrispondent starting power, is:
c) Soft-starter starting
Starting current of the motor can be monitored/contpumprolled by the current limit
function that in order to guarantee the required torque shall be approx. ISTART < 65%
of the starting current at full voltage, which is:
0,65•7,1• In < 4,6• In
Power requested to the network at starting phase, shall be in worst condition.
Where:
Q = flow of the liquid
H = head (refer to Figure 3.1; H = Hd + Pd + Ft )
γ = specific density
The right size of the motor/pump system is obtained when in the working rate the level of
upper static head of pumping liquidi s maintained steady (see Figure 3.1 = ProducingFluid
Level). Infact this condiction means that pumped volume is equal to that one regenerated
within the well.
If the flow were bigger the level of static head would lower up to cause cavitation of the
pump.
If the flow were less, the correct exploitation of the well would not occur.
It becomes evident that if the motor pump system could regulate the flow, reaching of the
balance point would be optimized.
Such a possibility is assured varying speed revolutions of the pump.
Variations of the pump characteristics in function of speed in comparison with rated speed,
are as follow:
n1
Q1 = • Qn
n
2
⎛n ⎞
H 1 = ⎜ 1 ⎟ • Hn
⎝n⎠
3
⎛n ⎞
P1 = ⎜ 1 ⎟ • Pn
⎝n⎠
where:
• Qn, Hn, Pn are respectively the flow, the head and the power at speed rate of the pump
(n).
• Q1, H1, P1, are respectively the flow, the head and the power at the new speed rate of
the pump (n1).
As previously stated varying the frequency of supply to motor can change the speed.
The frequency is therefore selected in relation to flow and dimensional characteristics of the
well and it is to be regulated on the variation of static head.
Variable Speed Drive systems VSD can be automatically regulated, frequency of supply to
motor may be adjusted by means of a signal coming from a proportional pressure
transducer to free static head (see the PSI system of REDA or the PHD of CENTRILIFT).
On the VSD drive it is possible to set the relevant parameters corresponding to determined
static head value
If the static head is going to increase, the transducer will deliver to pump a signal for
accelerating; on the contrary if the static head decreases the same transducer will ‘order’
motor to decelerate accordingly.
Eni S.p.A. 20217.VAR.ELE.SDS
Rev.0 December 2004
Exploration & Production Division
Pag. 46 di 49
Hd = vertical distance between the wellhead and estimated producing fluid level at the expected
capacity
Ft = friction head in tubing (head required required to overcome friction loss in the tubing)
Pd = discharge pressure head (head required to overcome friction in the surface pipe,
valves and fittings and to overcome elevation changes between wellhead and tank
battery).
Fig 3.1
Eni S.p.A. 20217.VAR.ELE.SDS
Rev.0 December 2004
Exploration & Production Division
Pag. 47 di 49
b) Operating data
For each working point of the motor, included that one at rated voltage / frequency:
Pm = absorbed power [HP oppure kW]
Fm = operating frequency of the motor [Hz]
Vm = supply voltage at motor terminals [V]
Vjb = supply voltage at surface terminal box [V]
Im = absorbed current by motor [A]
Transformer sizing
To define the main transformer ratio, the values of motor working operation at rated
voltage and rated frequency must be considered.
During this operation the output voltage and frequency of the VSD (V & F), are the
same of the supply network (e.g. 380 V – 50 Hz or 480 V 60 Hz, etc.).
The transformer ratio is chosen in order that, with the above working operation, the
voltage at the terminals of the surface box shall be equal to Vjb.
As the voltage drop within cables connection between the transformer and the surface
terminal is normally negligible, it can be assume Vjg=V2 where V2 is the secondary
voltage of the transformer at full load condition.
Eni S.p.A. 20217.VAR.ELE.SDS
Rev.0 December 2004
Exploration & Production Division
Pag. 49 di 49
In case that the voltage drop within cables connection between the transformer and the
surface terminal is not negligible, the relevant drop value must be considered to define
the transformer ratio.
The ratio M = V/V2 corresponds to transformer ratio at full load.
To define the steps of the transformer tap changer, the other working operations points
of the motor must be considered.
The tap changer range shall be chosen in order to warranty as much as possible, that in
all ratio steps, the transformer magnetic flux will remain equal or less of the nominal
one; moreover the following conditions must be verified:
VSD Fm
M1 = with V SD< Vn and VSD ≤ Vn
V jb Fn
where:
Vjb = V2 secondary voltage of transformer (and/or surface box) corresponding to
the considered working point
M1 = transformer ratio corresponding to the selected tap changer
Vn e Fn = voltage and frequency (rated) of the supplì system (380 V – 50 Hz or 480 V
– 60 Hz, etc.)
VSD = VSD output voltage relevant to the working condition considered
Fm = VSD output frequency relevant to the working condition considered
The number of steps of the tap changer between the ratio M and M1, must be chosen
with regular steps; it i salso advaisable to increase the number of steps in addition to
those caculated.
The transformer rated power must be chosen in order to cope all the working condition
of the motor.
It can be defined by means of the following relation:
3 • V2 MAX • I 2 MAX
where V2MAX e I2MAX are the maximum forseen values of the secondary voltage and
current.
Anyhow transformer rated power must bigger than kVA absorbed by motor.
An over-sizing of at least 20% must be considered.