Hilti PROFIS Engineering 3.0.

93

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/malaysia.html
Company: Page: 1
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Copy - Copy - Copy - Concrete - Apr 9, 2024 (1) Date: 9/04/2024
Fastening point:

Specifier's comments:

1 Input data
Anchor type and diameter: HSA M8 hnom1
Return period (service life in years): 50
Item number: 2004123 HSA M8x70 20/10/-
Effective embedment depth: hef = 30.0 mm, hnom = 39.0 mm
Material:
Evaluation Service Report: ETA 11/0374
Issued I Valid: 27/10/2023 | -
Proof: Design Method ETAG (No. 001 Annex C/2010)
Stand-off installation: eb = 0.0 mm (no stand-off); t = 6.0 mm

Anchor plate :
R lx x ly x t = 230.0 mm x 150.0 mm x 6.0 mm; (Recommended plate thickness: not calculated)

Profile: Double flat bar, ; (L x W x T) = 150.0 mm x 89.0 mm x 5.0 mm


Base material: uncracked concrete, C25/30, fc,cube = 30.00 N/mm ; h =400.0 mm
2

Installation: hammer drilled hole, Installation condition: Dry


Reinforcement: no reinforcement or reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement

R
- The anchor calculation is based on a rigid anchor plate assumption.

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

1
Hilti PROFIS Engineering 3.0.93

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/malaysia.html
Company: Page: 2
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Copy - Copy - Copy - Concrete - Apr 9, 2024 (1) Date: 9/04/2024
Fastening point:

1.1 Load combination


Case Description Forces [kN] / Moments [kNm] Seismic Fire Max. Util. Anchor [%]
1 Combination 1 N = 11.000; Vx = 2.000; Vy = -4.000; no no 88
Mx = 0.344; My = 0.200; Mz = 0.000;

2 Load case/Resulting anchor forces

y
Anchor reactions [kN]
Tension force: (+Tension, -Compression)
3 4
Anchor Tension force Shear force Shear force x Shear force y
1 1.711 1.118 0.500 -1.000
Tension x
2 1.018 1.118 0.500 -1.000
3 5.031 1.118 0.500 -1.000
4 4.338 1.118 0.500 -1.000 1 2

max. concrete compressive strain: 0.11 [‰]


max. concrete compressive stress: 3.45 [N/mm ]
2
Compression
resulting tension force in (x/y)=(-9.2/22.0): 12.097 [kN]
resulting compression force in (x/y)=(81.2/-71.5): 1.097 [kN]

Anchor forces are calculated based on the assumption of a rigid anchor plate.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

2
Hilti PROFIS Engineering 3.0.93

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/malaysia.html
Company: Page: 3
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Copy - Copy - Copy - Concrete - Apr 9, 2024 (1) Date: 9/04/2024
Fastening point:

3 Tension load (ETAG, Annex C, Section 5.2.2)


Load [kN] Capacity [kN] Utilization bN [%] Status
Steel Strength* 5.031 11.786 43 OK
Pullout Strength* 5.031 5.915 86 OK
Concrete Breakout Failure** 6.742 7.962 85 OK
Splitting failure** N/A N/A N/A N/A

* highest loaded anchor **anchor group (anchors in tension)

3.1 Steel Strength

N
NSd £ NRd,s = Rk,s ETAG 001 Annex C, Table 5.2.2.1
gM,s

NRk,s [kN] gM,s NRd,s [kN] NSd [kN]


16.500 1.400 11.786 5.031

3.2 Pullout Strength

y c · NRk,p
NSd £ NRd,p = ETAG 001 Annex C, Table 5.2.2.1
gM,p

NRk,p [kN] yc g M,p NRd,p [kN] NSd [kN]


8.100 1.095 1.500 5.915 5.031

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

3
Hilti PROFIS Engineering 3.0.93

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/malaysia.html
Company: Page: 4
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Copy - Copy - Copy - Concrete - Apr 9, 2024 (1) Date: 9/04/2024
Fastening point:

3.3 Concrete Breakout Failure

N
NSd £ NRd,c = Rk,c ETAG 001 Annex C, Table 5.2.2.1
gM,c
0 Ac,N
NRk,c = NRk,c · 0
· y s,N · y re,N · y ec1,N · y ec2,N ETAG 001 Annex C, Eq. (5.2)
Ac,N
0 1,5
NRk,c = k1 · √fck,cube · hef ETAG 001 Annex C, Eq. (5.2a)
0
Ac,N = scr,N · scr,N ETAG 001 Annex C, Eq. (5.2b)
c
y s,N = 0.7 + 0.3 · 1.00 ETAG 001 Annex C, Eq. (5.2c)
ccr,N £
hef
y re,N = 0.5 + 1.00 ETAG 001 Annex C, Eq. (5.2d)
200 £
1
y ec1,N = 1.00 ETAG 001 Annex C, Eq. (5.2e)
2 · ec1,N £
1+
scr,N
1
y ec2,N = 1.00 ETAG 001 Annex C, Eq. (5.2e)
2 · ec2,N £
1+
scr,N

2 0 2
Ac,N [mm ] Ac,N [mm ] ccr,N [mm] scr,N [mm]
15,300 8,100 45.0 90.0

ec1,N [mm] y ec1,N ec2,N [mm] y ec2,N y s,N y re,N


0.0 1.000 19.7 0.696 1.000 1.000
0
k1 NRk,c [kN] gM,c NRd,c [kN] NSd [kN]
10.100 9.090 1.500 7.962 6.742

Group anchor ID
1, 3

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

4
Hilti PROFIS Engineering 3.0.93

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/malaysia.html
Company: Page: 5
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Copy - Copy - Copy - Concrete - Apr 9, 2024 (1) Date: 9/04/2024
Fastening point:

4 Shear load (ETAG, Annex C, Section 5.2.3)


Load [kN] Capacity [kN] Utilization bV [%] Status
Steel Strength (without lever arm)* 1.118 8.480 14 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength** 2.236 11.447 20 OK
Concrete edge failure in direction y-** 4.123 29.684 14 OK

* highest loaded anchor **anchor group (relevant anchors)

4.1 Steel Strength (without lever arm)

V
VSd £ VRd,s = Rk,s ETAG 001 Annex C, Table 5.2.3.1
gM,s

VRk,s [kN] gM,s VRd,s [kN] VSd [kN]


10.600 1.250 8.480 1.118

4.2 Pryout Strength

V
VSd £ VRd,cp = Rk,cp ETAG 001 Annex C, Table 5.2.3.1
gM,c,p
VRk,cp = k · NRk,c ETAG 001 Annex C, Eq. (5.6)
0 A
NRk,c = NRk,c · 0c,N · y s,N · y re,N · y ec1,N · y ec2,N ETAG 001 Annex C, Eq. (5.2)
Ac,N
0 1,5
NRk,c = k1 · √fck,cube · hef ETAG 001 Annex C, Eq. (5.2a)
0
Ac,N = scr,N · scr,N ETAG 001 Annex C, Eq. (5.2b)
c
y s,N = 0.7 + 0.3 · £ 1.00 ETAG 001 Annex C, Eq. (5.2c)
ccr,N
hef
y re,N = 0.5 + 1.00 ETAG 001 Annex C, Eq. (5.2d)
200 £
1
y ec1,N = 1.00 ETAG 001 Annex C, Eq. (5.2e)
2 · ec1,V £
1+
scr,N
1
y ec2,N = 1.00 ETAG 001 Annex C, Eq. (5.2e)
2 · ec2,V £
1+
scr,N

2 0 2
Ac,N [mm ] Ac,N [mm ] ccr,N [mm] scr,N [mm] k-factor
15,300 8,100 45.0 90.0 1.000

ec1,V [mm] y ec1,N ec2,V [mm] y ec2,N y s,N y re,N


0.0 1.000 0.0 1.000 1.000 1.000
0
NRk,c [kN] gM,c,p VRd,cp [kN] VSd [kN]
9.090 1.500 11.447 2.236

Group anchor ID
2, 4

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

5
Hilti PROFIS Engineering 3.0.93

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/malaysia.html
Company: Page: 6
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Copy - Copy - Copy - Concrete - Apr 9, 2024 (1) Date: 9/04/2024
Fastening point:

4.3 Concrete edge failure in direction y-

V
VSd £ VRd,c = Rk,c ETAG 001 Annex C, Table 5.2.3.1
gM,c
0 Ac,V
VRk,c = VRk,c · 0
· y s,V · y h,V · y a,V · y ec,V · y re,V ETAG 001 Annex C, Eq. (5.7)
Ac,V
0 a b 1,5
VRk,c = k1 · dnom · lf · √fck,cube · c1 ETAG 001 Annex C, Eq. (5.7a)
0,5
a = 0.1 · () lf
c1
ETAG 001 Annex C, Eq. (5.7b)
0,2

= 0.1 · (
c )
d nom
b ETAG 001 Annex C, Eq. (5.7c)
1
0 2
Ac,V = 4.5 · c1 ETAG 001 Annex C, Eq. (5.7d)
c2
y s,V = 0.7 + 0.3 · 1.00 ETAG 001 Annex C, Eq. (5.7e)
1.5 · c1 £
0,5
y h,V = (1.5h· c ) 1
³ 1.00 ETAG 001 Annex C, Eq. (5.7f)


1
2
y a,V =
(cos aV) +
2
(sin2.5a )
V ³ 1.00 ETAG 001 Annex C, Eq. (5.7g)

1
y ec,V = 1.00 ETAG 001 Annex C, Eq. (5.7h)
2 · ec,V £
1+
3 · c1

lf [mm] dnom [mm] k1 a b


30.0 8.00 2.400 0.045 0.056
2 0 2
c1 [mm] Ac,V [mm ] Ac,V [mm ]
150.0 137,250 101,250

y s,V y h,V aV [°] y a,V ec,V [mm] y ec,V y re,V


1.000 1.000 14.04 1.026 0.0 1.000 1.000
0
VRk,c [kN] gM,c VRd,c [kN] VSd [kN]
32.025 1.500 29.684 4.123

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

6
Hilti PROFIS Engineering 3.0.93

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/malaysia.html
Company: Page: 7
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Copy - Copy - Copy - Concrete - Apr 9, 2024 (1) Date: 9/04/2024
Fastening point:

5 Combined tension and shear loads (ETAG, Annex C, Section 5.2.4)


bN bV a Utilization bN,V [%] Status
0.850 0.195 1.500 88 OK

a a
bN + bV £ 1.0

6 Displacements (highest loaded anchor)


Short term loading:

NSk = 3.726 [kN] dN = 0.1863 [mm]


VSk = 0.828 [kN] dV = 0.2580 [mm]
dNV = 0.3182 [mm]
Long term loading:

NSk = 3.726 [kN] dN = 0.5590 [mm]


VSk = 0.828 [kN] dV = 0.3937 [mm]
dNV = 0.6837 [mm]

Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!

The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

7 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering
calculates the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions
explained above. The proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results
must be checked for agreement with the existing conditions and for plausibility!
• Checking the transfer of loads into the base material is required in accordance with ETAG 001, Annex C(2010)Section 7! The software
considers that the grout is installed under the anchor plate without creating air voids and before application of the loads.
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 4.1 of ETAG 001, Annex C! For larger
diameters of the clearance hole see Chapter 1.1. of ETAG 001, Annex C!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
• The characteristic bond resistances depend on the return period (service life in years): 50

Fastening meets the design criteria!

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

7
Hilti PROFIS Engineering 3.0.93

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/malaysia.html
Company: Page: 8
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Copy - Copy - Copy - Concrete - Apr 9, 2024 (1) Date: 9/04/2024
Fastening point:

8 Installation data
2 2
Anchor plate, steel: S 275; E = 210,000.00 N/mm ; fyk = 275.00 N/mm Anchor type and diameter: HSA M8 hnom1
Profile: Double flat bar, ; (L x W x T) = 150.0 mm x 89.0 mm x 5.0 mm Item number: 2004123 HSA M8x70 20/10/-
Hole diameter in the fixture: df = - mm Maximum installation torque: 15 Nm
Plate thickness (input): 6.0 mm Hole diameter in the base material: 8.0 mm
Recommended plate thickness: not calculated Hole depth in the base material: 44.0 mm
Drilling method: Hammer drilled Minimum thickness of the base material: 100.0 mm
Cleaning: Manual cleaning of the drilled hole according to instructions for use is
required.

Hilti HSA stud anchor with 39 mm embedment, M8 hnom1, Steel galvanized, installationwith torque control bar per ETA 11/0374

8.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • Manual blow-out pump • Torque controlled cordless impact tool
• Properly sized drill bit • Hilti SFC 22-A drill driver
• Torque wrench
• Installation torque control bar with suitable
screw driver or torque wrench
• Hammer

y
115.0 115.0
35.0

3 4
75.0
80.0

x
75.0

1 2
35.0

35.0 160.0 35.0

Coordinates Anchor [mm]


Anchor x y c-x c+x c-y c+y
1 -80.0 -40.0 1,000.0 1,160.0 150.0 780.0
2 80.0 -40.0 1,160.0 1,000.0 150.0 780.0
3 -80.0 40.0 1,000.0 1,160.0 230.0 700.0
4 80.0 40.0 1,160.0 1,000.0 230.0 700.0

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

8
Hilti PROFIS Engineering 3.0.93

www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/malaysia.html
Company: Page: 9
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Copy - Copy - Copy - Concrete - Apr 9, 2024 (1) Date: 9/04/2024
Fastening point:

9 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior
to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you
put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by
you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with
regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to
interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability
for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for
the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do
not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software
in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan