Professional Documents
Culture Documents
MGSG M4
MGSG M4
Microgrid
R L C
P load+ JQ load
Island mode
When the grid frequency is outside the range of +/- 1 Hz the inverter should cease to energize
the utility line within 0.2 seconds.
Thus the grid voltage and frequency should be estimated and monitored fast and accurate
enough in order to cope with the standard
Source: IEEE-1547-2003- IEEE Standard for Interconnecting Distributed Resources with Electric Power Systems
‘a’- DR ≤ 30kW,
maximum clearing
times;
DR > 30kW, default
clearing times.
The utility cannot control voltage and frequency in the island, creating the possibility of
damage to customer equipment in a situation over which the utility has no control.
Utilities, along with the PV distributed resource owner, can be found liable lines that results
from voltage or frequency excursions outside of the acceptable ranges.
Islanding may create a hazard for utility line-workers or the public by causing a line to
remain energized that is assumed to be disconnected from all energy sources
Re-closing into an island may result in re-tripping the line or damaging the distributed
resource equipment, or other connected equipment, because of out of- phase closure.
Islanding may interfere with the manual or automatic restoration of normal service by the
utility.
Where, ∆ 𝐏 is the real power output of the grid, ∆ 𝐐 is the reactive power output the grid.
If PLOAD =PDG there is no power mismatch between the power produced by the PV system.
If QLOAD=QDG there is no reactive power mismatch between the PV system and the utility.
The behavior of the system during islanding depends on the value of P & Q at the instant of
opening of the recloser.
FCRIT, Dept. of Electrical Engg. Ms. Misbah Khan
MICROGRID AND SMARTGRID
COURSE CODE- EEDO7021
Islanding Detection 1. Active Frequency Drift (AFD)
methods: • A slightly distorted is the output current
waveform, representing a zero-current
section for a drift-up procedure.
• This is achieved by forcing the present sine wave
distorted wave
frequency in the past cycle to be
DG current output
moderately (0.5 − 1.5 Hz) greater than the
voltage frequency and maintaining the
inverter current at zero from the end of its t1 t2
as:
𝟐∗𝒕𝟐
𝐜𝐟 = Active frequency drift waveform
𝒕
• where 𝐭𝟐 is the zero time of the AFD
signal and 𝐭 is the period of the utility
voltage.
• Fig. shows that drift being added in sine
signal along with the distorted waveform.
FCRIT, Dept. of Electrical Engg. Ms. Misbah Khan
MICROGRID AND SMARTGRID
COURSE CODE- EEDO7021
Islanding Detection 2. Sandia Frequency Shift (SFS)
methods:
• Also called active frequency drift with positive feedback (AFDPF), this is an expansion of the
AFD technique and is another technique that uses positive feedback.
• In this technique, the beneficial feedback is applied to the PCC voltage frequency. To enforce
the positive feedback, AFD’s 'chopping fraction' is a function of the error in the line frequency.
f0 cf0
𝐜𝐟
ω 1/2π K π/2 = 𝐜𝒇𝟎 + 𝐤(𝒇 − 𝒇𝟎 )
ϴinv
• where, k -acceleration gain, 𝒄𝒇𝟎 -chopping factor when there is no frequency error and
𝒇 − 𝒇𝟎 -difference between the estimated frequency and nominal value.
• Positive feedback formulated as linear function of deviation in frequency of PCC voltage is
applied to chopping fraction (cf) which causes frequency to deviate from nominal value in
absence of the grid.
FCRIT, Dept. of Electrical Engg. Ms. Misbah Khan
MICROGRID AND SMARTGRID
COURSE CODE- EEDO7021
Islanding Detection 3. Sandia Voltage Shift (SVS)
methods: • In this technique the voltage amplitude acts as a positive feedback to the current reference.
Thus, if there is a decrease in the amplitude of voltage at the PCC (usually it is the RMS value
that is measured in practice), the inverter reduces its current output and thus its power
output.
• When the utility is attached, when the power is lowered, there is little or no impact on the
voltage. If the utility is absent and voltage is lowered, the amplitude will be further decreased
as dictated by the Ohm's law the load impedance (RLC) to the decreased current.
• This extra reduction in voltage amplitude leads to a further decrease in the output current of
the PV inverter, resulting in a possible decrease in voltage that the UVP can be detected.
• The energy output of the inverter can either be increased or decreased, resulting in a
respective OVP or UVP trip. However, it is preferable to react with a decrease in energy and
an UVP trip because this is less probable to harm the loading devices.
LOAD
CONTROL current
i
- voltage
+ MONITORING
PLL
iref PLL
phase
CURRENT
CALCULATOR
frequency amplitude
P Q
dQ
-
+ Kf < +
+
Q_DG FG
-
+ Kv < +
+
P_DG
VG
Why ????????
Reasons :
1. Characteristic of inverters are not similar to existing protection equipment's
2. Different inverter designs have different characteristic and hence they do not have any
standardized characteristic that symbolize inverters as class of equipment
3. Fundamental characteristic of inverter units vary clearly depending on design and application.
4. Low fault current capacity in inverter units.
5. For Micro sources with larger no. of PEIs reduction in Micro grid fault level during change over
from grid connected to stand alone operation
6. Systematic understanding of Micro grid dynamics before, during and after islanding is
necessary to resolve protection issues for Micro grids properly.
7. Realistic evaluation on the benefits - before islanding the Micro grids
• Micro grid provides continuous power supply to priority loads during any disturbance in utility.
• The existing protective equipment may fail to clear the fault quickly if loads of the Micro grid is
voltage- sensitive then it requires separation times of fewer than 50ms.
• Relay time required to direct and interrupt the circuit on receiving the trip signal for an over/
under voltage is up to 2 cycles and for medium voltage is three to five cycles.
• Hence, if a quick acting solid state CB is not available at PCC between micro grid and utility
grid; other methods must be employed to avoid the voltage falling below 50% for three cycles
or longer.
• Options (ii) and (iii) are suitable choices for Microgrids with micro sources at more than one
location.
• For fault within Micro grid, protection system must be sufficiently time delayed to avoid micro
sources generation loss due to utility disturbances
• Realize coordination through PCM
• Feeder sections employ - directional over current relay.
• The operating times of relays (if same), leads to reduced selectivity.
• Thus by employing differential protection schemes around each circuit segment appropriate
selectivity has to be achieved
• High-speed communication is necessary to and from all protective devices that trip any faulted
circuit.
5. Re-Synchronization
• It is responsibility of PCM to synchronize and reconnect the micro grid to the utility grid through
synchronism check schemes.
• This may need a few seconds to minutes, depending upon the nature of the loads and feeder.
• The PCM contains the control scheme to bring all micro sources into synchronization with utility
grid.
• PCM provides both options for manual and automatic resynchronization as per requirement.
Source: http://microgrids.eu/documents/a._oudalov_protection_and_control_issues_%20network_designs.pdf
Source: http://microgrids.eu/documents/a._oudalov_protection_and_control_issues_%20network_designs.pdf
Source: http://microgrids.eu/documents/a._oudalov_protection_and_control_issues_%20network_designs.pdf
Source: http://microgrids.eu/documents/a._oudalov_protection_and_control_issues_%20network_designs.pdf