You are on page 1of 1

Technical Application Papers

If, on the other hand, the fault is on the DC side, fault switched, with serious problems to devices connected
current flows in the freewheeling diodes without any to the DC-Bus.
Introduction

possibility for the IGBTs to limit it, even if an IGBT block It is thus apparent that the naive statements that fault
signal is sent by the control system (Figure I.2). currents are of no concern and that protection can be
Similar situations occur in all cases in which short circuit fully implemented by converters is not generally true. A
current path can include freewheeling diodes, hence all number of realistic cases exit in which converters can't
AC/DC IGBT converter, step-up and DC/DC bidirectional limit ground- or short circuit fault current.
converters may suffer from this effect. A thorough analysis of fault conditions and dedicated
Moreover, a similar effect may take place in the case of protection devices must therefore be used to safeguard
a DC ground fault in a microgrid with the neutral point installation and operator safety.
of the MV/LV transformer grounded or DC negative pole This Technical Application Paper deals with fault analy-
grounded. Both grounding configurations are widely used sis and protection in LVDC microgrids with front-end
as they guarantee operation safety from overvoltages. converters. In particular, Chapter 1 explains the main
However, when a ground fault occurs, the front-end con- advantages of LVDC microgrids; Chapter 2 shows the
verter may not be able to limit the AC grid contribution to description of the system configurations; Chapter 3
the fault current, even if the DC generators contribution deals with the short circuit and ground fault analysis both
may be switched off by IGBT block (Figure I.3). in case they occur on DC and AC front-end converter
It must be pointed out that ground faults are far more side, highlighting the situations in which the converter
frequent than short circuits in electrical installations, cannot limit fault currents; finally, Chapter 4 presents the
hence DC ground fault are expected to become more solutions offered by ABB to protect the plants against
and more frequent as DC section of installations extend. DC fault.
Similar cases can be made for several other configura- This Technical Application Paper includese three an-
tions of converters. nexes with the description of the main power-electronic-
Thyristor rectifiers, which are immune from this issue, switches, the main converter control methods, of the
can't be applied as front-end converters in DC distri- analyzed system electrical parameters, of the DC fault
bution with distributed generation, because in case of contribution of other types of converters.
reversal of power flow, they require voltage polarity to be

Figure I.2 – DC short circuit current components in an active LVDC microgrid

V1 I1 L R Ri

V2 DC Load
I2 L R +
Rsc Eo
V3 I3 L R

Figure I.3 – DC positive pole ground fault current path in an active LVDC microgrid with the neutral point of the MV/LV transformer grounded

V1 I1 L R Ri

V2 DC Load
I2 L R +
Rg Eo
V3 I3 L R

4 Faults in LVDC microgrids with front-end converters

You might also like