Professional Documents
Culture Documents
Iac1 is shifted by a value equal to one-third the fault cur- Figure 3.69b – Trend of Isw2 current during a ground fault on DC side in
systems with the neutral point of the MV/LV transformer grounded without
rent DC component.
3 Fault analysis
Isw2 [A]
voltage at AC terminals trends to a square waveform due 400
0
Figure 3.68 – Trend of the voltage at AC converter terminal Vconv during
a ground fault on DC side in systems with the neutral point of the MV/LV -200
transformer grounded without ESS and PV plant and with Rg = 50 mΩ
-400
600
-600
0.4 0.45 0.5 0.55 0.6 0.65
400 t [s]
200
In converters sold on the market, when the current in
Vconv [V]
200 200
0 0
-200 -200
-400 -400
Isw1 [A]
Isw1 [A]
-600 -600
-800 -800
-1000 -1000
-1200 -1200
-1400 -1400
0.4 0.45 0.5 0.55 0.6 0.65 0.4 0.45 0.5 0.55 0.6 0.65
t [s] t [s]