Professional Documents
Culture Documents
3 Fault analysis
LV transformer grounded with ESS (Idcn = 125 A)
the IGBTs of the anodic star (Figure 3.84b).
4500
Figure 3.84a – Trend of Isw1 current during a ground fault on DC side in 4000
systems with the neutral point of the MV/LV transformer grounded with
ESS and Rg = 50 mΩ 3500
200 3000
0 2500
Ig [A]
2000
-200
1500
-400 1000
Isw1 [A]
-600 800
0
-800
100 10 1 0.1 0.01 0.001
Rsc [Ω]
-1000
-1200
0.4 0.45 0.5 0.55 0.6 0.65
t [s]
If the IGBT block is considered, the currents Isw1 and Isw2
Figure 3.84b – Trend of Isw2 current during a ground fault on DC side in change as shown in Figures 3.86a-b.
systems with the neutral point of the MV/LV transformer grounded with
ESS and Rg = 50 mΩ As it can be seen, unlike in Figures 3.84a-b, there is no
1200 longer the PWM control and in particular, since Isw2 flowed
only in the IGBT, now it is cancelled.
1000
As a result, the ESS contribution to the ground fault cur-
800 rent is interrupted.
600
Isw2 [A]
400
200 Figure 3.86a – Trend of Isw1 current during a ground fault on DC side in
systems with the neutral point of the MV/LV transformer grounded with
0 ESS, IGBT block and Rg = 50 mΩ
-200 200
-400 0
0.4 0.45 0.5 0.55 0.6 0.65
t [s] -200
-400
To sum up, Figure 3.85 depicts the DC ground fault
Isw1 [A]
-600
current values Ig as a function of the fault resistance Rg
with the ESS. -800
As we can see, with the decrease of Rg, the fault current
-1000
may reach values even higher than 33 times the FEC
nominal current on the DC side Idcn. -1200