You are on page 1of 1

Technical Application Papers

The waveform of the AC current Iac1 (Figure 3.58) does Since the steady state value of Vdc is not constant, there
not change with respect to the no-fault condition (even is a high current flowing through the DC capacitors.
3 Fault analysis

if there is a DC component superimposed in each phase


and equal to Ig/3 = 8/3 = 2.7A), since the FEC still works
Figure 3.60 – Trend of the DC capacitors current Icap during a ground
in linear modulation. fault on DC side in systems with the neutral point of the MV/LV transformer
grounded without ESS and PV plant and with Rg = 50 mΩ
Figure 3.58 – Trend of Iac1 current during a ground fault on DC side in
systems with the neutral point of the MV/LV transformer grounded without 2500
ESS and PV plant and with Rg = 50 Ω
2000
250

200 1500

150
1000
100

Icap [A]
500
50
Iac1 [A]

0 0

-50
-500
-100
-1000
-150 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
t [s]
-200

-250
The DC capacitor discharge current comes from the FEC
0.4 0.45 0.5 0.55
t [s]
0.6 0.65 lower terminal; as a result, the converter, during the fault
transient, supplies a positive current flowing out of both
3.2.1.2 Low fault resistance Rg without ESS and terminals (Figures 3.61-3.62).
PV plant (S1=ON, S2=ON/OFF) This behavior corresponds to an abnormal FEC opera-
The decreasing values of the fault resistance Rg cause tion, since during normal operation current flows out of
voltage variations on the DC-Bus and give rise to a the upper terminal and into the lower one (Figures 3.61-
gradual loss of control by the converter. 3.62 before the fault).
As the Rg decreases, the earth fault current Ig has a higher The sum of the current from the upper terminal and of the
and higher DC component and Ig reaches such values current flowing through the capacitors makes the ground
that the use of protective devices is anyway required. fault current Ig (minus the load current).
In particular, e.g. with Rg = 50 mΩ, the FEC behaves like
a diode rectifier (Vdc < 1.35 ∙ √3 ∙ V1 as in Figure 3.59): Figure 3.61 – Trend of the upper terminal current Iconvdc1 during a ground
fault on DC side in systems with the neutral point of the MV/LV transformer
it works for longer and longer fractions of time in an ir- grounded without ESS and PV plant and with Rg = 50 mΩ
regular way, i.e. bypassing the controlled semiconductors 2500
(fault current flows in freewheeling diodes).
As we can see in Figure 3.59, as soon as the fault occurs 2000
(t = 0.5 s), Vdc decreases discharging the DC capacitors
(Figure 3.60) and reaching the steady state value, which 1500
guarantees a limited power delivery to the DC load.
1000
Iconvdc1 [A]

Figure 3.59 – Trend of Vdc voltage during a ground fault on DC side in


systems with the neutral point of the MV/LV transformer grounded without
ESS and PV plant and with Rg = 50 mΩ 500

900
0
800 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
t [s]
700
Vdc [V]

600

500

400

300

200

100
0
0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
t [s]

30 Faults in LVDC microgrids with front-end converters

You might also like