Installation of Air Conditioning System including Supplying of All necessary Fixtures at your Auditorium of Kaliyaganj Municipality.

SCHEDULE OF WORK/ ITEM(S)

Sl No. Description of Work/ Item(s) No. of Qty UNITS Quantity Justification

1.00 AHU system with High Static Blower connected with Dx Condensing Unit
Double skin Dx coil Floor-mounted AHU consisting of fan section, filter section, cooling coil
1.01 section and other standard accessories with SS drain pipe - 15000 CFM, 50mm WC Static 2 Nos 2 Nos. Quantity of AHU - 2
Pressure
Air-cooled Condensing Unit with Hermetically sealed Scroll Compressor, Inner grooved
Copper Condenser with Hydrophobic Blue/ Thermoguard coating, Shell & Tube Condenser
1.02 & Microprocessor Control suitable for R22 refrigerant - 42 TR Nominal Capacity 2 Nos 2 Nos. Quantity of Condensing unit - 2

V.I.pad for condensing Unit 2 set for 2 Nos. AHU & Condensing
1.03 2 Set 2 Nos.
units
Hard Drawn Copper refrigerant piping (19 G) Each condensing unit consisting of
1.04 182 Rmt 30 Rmt per ckt X 6 Ckt
3 Nos.ckt
Thermal Insulation with 19 mm thick Aluminium Foil faced Nitrile Rubber tube Each condensing unit consisting of
1.05 182 Rmt 30.5 Rmt per ckt
3 Nos.ckt
1.06 Hard PVC 25 NB Condensate water Drain line 112 Rmt 91 Rmt per AHU Quantity of AHU - 2
1.07 GSS ducting metal as per IS 655 - 20 G GSS Sheets 550 Sqmt
1.08 GSS ducting metal as per IS 655 - 22 G GSS Sheets 750 Sqmt Supply Air duct = 892 sqmt
2200 sqmt considering 1.5 X Supply Air Duct
GSS ducting metal as per IS 655 - 24 G GSS Sheets
1.09 900 Sqmt extra for Returm Air duct

Duct thermal insulation with 19 mm thick Aluminium foil faced Nitrile Rubber. pasted with Quantity of Thermal Insulation =
1.10 Fevicol adhesive and covered with 24G Aluminium sheet cladding 2200 Sqmt 2200 sqmt
Quantity of duct
Duct & Plenum acoustic lining with 12mm thick FG rigid board wrapped with RP tissue paper
and finally 32G Aluminium perforated sheet considering 20 Rmt. from the
1.11 350 Sqmt 320 Sqmt machine mouth connection at the
suply air duct

Extruded Aluminium powder coated supply air diffusers with MS opposed blade volume
1.12 control damper 19 Sqmt 19 Sqmt 36 Nos. Diffuser shown in drawing

2.0 Next
Extruded Aluminium powder coated return air grille / diffusers without volume control damper Quantity of Return Air Diffuser =
2.01 19 Sqmt 19 Sqmt
Quantity of Suppy Air Diffuser
GSS Duct damper made of 18G GSS sheet with manually operated lever, quadrant, ON-OFF
2.02 19 Sqmt 19 Sqmt 8.5 Sqmt. for per AHU
indication, etc
Fusible Link Fire Damper with fire rating of 1 & 1/2 hours. The fusible link shall melt at a
2.03 temperature of 65-70°C 12 Sqmt 12 Sqmt 6 Sqmt. for per AHU

2.04 Fresh air system with GSS dampers, bird screen, rain protection cowl, etc 2 Set 2 set 2 Set for 2 Nos. AHU
Installation, testing & commissioning with vacummising , Nitrogen
2.05 pressure testing, first charge of refrigerant
a) Double skin Dx coil Floor-mounted AHU - 15000 CFM, 50mm WC SP 2 Nos 2 Nos. 2 Nos. for 2 Nos. AHU

b) Air-cooled Condensing Unit - 42 TR Nominal Capacity


2.06 2 Nos 2 Nos. 2 Nos. for 2 Nos. Condensing units

Total in Figures (Basic)

Exclusion of job :
a) 415V, 3 phase, 50 Hz, 4 wire power to be terminated at condensing units through MCB.
b) 415V, 3 phase, 50 Hz, 3 wire power to be terminated at AHUs through MCB.
c) All civil works, like wall cutting, RCC Foundation/pedestal of the AHUs and
condensing units etc and carpentry work such as enclosure for system components.
d) Free power for installation / testing / commissioning
e) Suitable provision for the drain line termination & its outlet.
f) Provision of Scaffolding, if applicable. If not arranged from your side
the same will be charged extra.
g) Lockable storage place at site.

57/B, Feeder Road, Barrackpore, Kolkata - 700 120, email : alphagamma.sales@gmail.com


Details of Installation of Air Conditioning System including Supplying of All necessary Fixtures at
Auditorium of Kaliyaganj Municipality.
Quantity Justification

Sl No. Description of Work/ Item(s) No. of UNITS Quantity Justification


Qty
AHU system with High Static Blower connected
1 with Dx Condensing Unit
Double skin Dx coil Floor-mounted AHU consisting
of fan section, filter section, cooling coil section and
other standard accessories with SS drain pipe -
1.01 15000 CFM, 50mm WC Static Pressure 2 Nos 2 Nos. Quantity of AHU - 2

Air-cooled Condensing Unit with Hermetically


sealed Scroll Compressor, Inner grooved Copper
Condenser with Hydrophobic Blue/ Thermoguard
coating, Shell & Tube Condenser & Microprocessor
1.02 Control suitable for R22 refrigerant - 42 TR Nominal 2 Nos 2 Nos. Quantity of Condensing
unit - 2
Capacity

V.I.pad for condensing Unit 2 set for 2 Nos. AHU &


1.03 2 Set 2 Nos.
Condensing units
Hard Drawn Copper refrigerant piping (19 G) 30 Rmt
1.04 182 Rmt per ckt X Each condensing unit
6 Ckt consisting of 3 Nos.ckt
Thermal Insulation with 19 mm thick Aluminium
1.05 Foil faced Nitrile Rubber tube 182 Rmt 30.5 Rmt Each condensing unit
per ckt consisting of 3 Nos.ckt

Hard PVC 25 NB Condensate water Drain line 91 Rmt


1.06 112 Rmt per AHU Quantity of AHU - 2
GSS ducting metal as per IS 655 - 20 G GSS Sheets
1.07 550 Sqmt
Supply Air duct = 892
GSS ducting metal as per IS 655 - 22 G GSS Sheets 2200 sqmt
1.08 750 Sqmt sqmt considering 1.5 X
Supply Air Duct extra
GSS ducting metal as per IS 655 - 24 G GSS Sheets for Returm Air duct
1.09 900 Sqmt
Duct thermal insulation with 19 mm thick
Aluminium foil faced Nitrile Rubber. pasted with 2200 Quantity of Thermal
### Fevicol adhesive and covered with 24G Aluminium 2200 Sqmt sqmt Insulation = Quantity of
sheet cladding duct

Duct & Plenum acoustic lining with 12mm thick FG considering 20 Rmt.
rigid board wrapped with RP tissue paper and 320 from the machine
1.11 finally 32G Aluminium perforated sheet 350 Sqmt Sqmt mouth connection at
the suply air duct
Extruded Aluminium powder coated supply air
1.12 diffusers with MS opposed blade volume control 19 Sqmt 19 Sqmt 36 Nos. Diffuser shown
damper in drawing

2.0
Extruded Aluminium powder coated return air grille Quantity of Return Air
2.01 / diffusers without volume control damper 19 Sqmt 19 Sqmt Diffuser = Quantity of
Suppy Air Diffuser
GSS Duct damper made of 18G GSS sheet with
2.02 manually operated lever, quadrant, ON-OFF 19 Sqmt 19 Sqmt 8.5 Sqmt. for per AHU
indication, etc
Fusible Link Fire Damper with fire rating of 1 & 1/2
2.03 hours. The fusible link shall melt at a temperature 12 Sqmt 12 Sqmt 6 Sqmt. for per AHU
of 65-70°C

Fresh air system with GSS dampers, bird screen,


2.04 rain protection cowl, etc 2 Set 2 set 2 Set for 2 Nos. AHU

Installation, testing & commissioning with


vacummising , Nitrogen

2.05 pressure testing, first charge of refrigerant


a) Double skin Dx coil Floor-mounted AHU - 15000 2 Nos 2 Nos. 2 Nos. for 2 Nos. AHU
CFM, 50mm WC SP

b) Air-cooled Condensing Unit - 42 TR Nominal 2 Nos. for 2 Nos.


2.06 Capacity 2 Nos 2 Nos.
Condensing units
Total in Figures (Basic)

Exclusion of job :
a) 415V, 3 phase, 50 Hz, 4 wire power to be terminated at condensing units through MCB.
b) 415V, 3 phase, 50 Hz, 3 wire power to be terminated at AHUs through MCB.
c) All civil works, like wall cutting, RCC Foundation/pedestal of the AHUs and
condensing units etc and carpentry work such as enclosure for system components.
d) Free power for installation / testing / commissioning
e) Suitable provision for the drain line termination & its outlet.
f) Provision of Scaffolding, if applicable. If not arranged from your side
the same will be charged extra.
g) Lockable storage place at site.